Plan Review Details - Permit 22080638
Plan Review Stops For Permit 22080638
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-08-16 Cont ID  
Sent By cpuell Date 2022-08-16 Time 06:41 Rev Time 0.00
Received By cpuell Date 2022-08-16 Time 06:41 Sent To  
Notes
2022-08-16 06:41:19OWNER ADDRESS UPDATED

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-10-24 Cont ID  
Sent By jwitmer Date 2022-10-24 Time 10:14 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-09-20 Cont ID  
Sent By jwitmer Date 2022-09-20 Time 10:27 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-09-20 10:27:52TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-11-08 Cont ID  
Sent By jwitmer Date 2022-11-08 Time 11:10 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-10-24 Cont ID  
Sent By jwitmer Date 2022-10-24 Time 10:53 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-10-24 10:53:41WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22080638
 ADD: 255 EVERNIA ST. # 1518
 CONT: DESIGN CONCEPTS REMODELING
 TEL: 954-543-1327
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. OCT. 24TH/2022
 ACTION: DENIED / VINYL FLOORING
 WE TRIED REACHING OUT TO THE CONTRACTOR AT 954-643-1327
 (FROM APP) AND FROM OUR RECORDS 954-970-7338 WHICH
 TURNED OUT TO BE A FAX.
 1) THE SUBMITTED DOCUMENTS DIVERSIFIED INDUSTRIES SOUND
 TRANSMISSION 6-INCH CONCRETE SLAB WITH SUSPENDED
 CEILING-GYPSUM BOARD WITH 3 ?? INCH FIBERGLASS
 INSULATION OVERLAID WITH DURALUX FLOOR AND FLOOR
 MUFFLER UNDERLAYMENT. AGAIN, WE DO NOT EXCEPT TEST
 REPORTS WITH DROPPED CEILINGS, ONLY 6 INCH SLABS. THE
 ONLY EXCEPTION ARE BUILDINGS THAT THE BUILDING
 DEPARTMENT HAS PROOF OF 8-INCH CONCRETE SLABS NO
 DROPPED CEILINGS.
 THE STRAND AT 255 EVERNIA DOES HAVE 8-INCH CONCRETE
 SLABS. ORIGINAL BUILD. PERMIT 99121621. THIS BUILDING
 WE WILL ACCEPT 8-INCH CONCRETE SLABS NO DROPPED
 CEILINGS. WE NEED TO SEE ALL 3 TEST REPORTS FOR STC,
 IIC AND FLAME SPREAD OR FOR VINYL LVT/ LPT WITHIN
 TENANT SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL
 COMPLY WITH THE REQUIREMENTS OF THE COC FF-1 PILL TEST
 (CPSC 16 CFR PART 1630) OR WITH ASTM D2859. LVT & LPT
 LUXURY VINYL TILE. FLOOR FINISH CLASSIFICATION AS
 REQUIRED IN SECTION 804.2 CLASSIFICATION AND 804.3
 TESTING AND IDENTIFICATION OF THE 2020 FBC-B. 804.2 &
 804.3/ ASTM E648 OR NFPA 253
  
 1ST ROUND OF COMMENTS. THE CONTRACTOR SUBMITTED SPECS
 FOR FLOOR MUFFLER ULTRASEAL FLOOR UNDERLAYMENT 2MM. THE
 CITY IS IN RECEIPT OF THE FLAME SPREAD REPORT. WE HAVE
 A TEST REPORT FOR THE STC= 73DB BUT IT IS FOR A 6-INCH
 CONCRETE SLAB WITH DROPPEDDRYWALL GRID CEILING
 CONSISTING OF 5/8 INCH TYPE X GYPSUM BOARD, 12 INCH
 PLENUM WITH 3 ?? INCH FIBERGLASS INSULATION.
  
 2ND REQUEST. FLOOR INSULATION/ UNDERLAYMENT (FBC-B
 2020) FOR TILE, STONE, MARBLE, VINYL (LYT/ LYP),
 LAMINATE FLOORING AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C)2ND REQUEST. FBC-B 804.4.4.1 SOFT FLOOR FINISHES
 (LVT/ LPT OR LAMINATED OR ENGINEERED WOOD FLOORING)
 WITHIN TENANT SPACE. INTERIOR FLOOR COVERING MATERIALS
 SHALL COMPLY WITH THE REQUIREMENTS OF THE COC FF-1 PILL
 TEST (CPSC 16 CFR PART 1630) OR WITH ASTM D2859. LVT &
 LPT LUXURY VINYL TILE. FLOOR FINISH CLASSIFICATION AS
 REQUIRED IN SECTION 804.2 CLASSIFICATION AND 804.3
 TESTING AND IDENTIFICATION OF THE 2020 FBC-B. 804.2 &
 804.3/ ASTM E648 OR NFPA 253
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-09-20 Cont ID  
Sent By jwitmer Date 2022-09-20 Time 10:28 Rev Time 0.00
Received By jwitmer Date 2022-09-20 Time 10:03 Sent To  
Notes
2022-09-20 10:03:42WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22080638
 ADD: 255 EVERNIA ST. # 1518
 CONT: DESIGN CONCEPTS REMODELING
 TEL: 954-543-1327
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 20/2022
 ACTION: DENIED / VINYL FLOORING
  
 1) THE CONTRACTOR SUBMITTED SPECS FOR FLOOR MUFFLER
 ULTRASEAL FLOOR UNDERLAYMENT 2MM. THE CITY IS IN
 RECEIPT OF THE FLAME SPREAD REPORT. WE HAVE A TEST
 REPORT FOR THE STC= 73DB BUT IT IS FOR A 6-INCH
 CONCRETE SLAB WITH DROPPEDDRYWALL GRID CEILING
 CONSISTING OF 5/8 INCH TYPE X GYPSUM BOARD, 12 INCH
 PLENUM WITH 3 ?? INCH FIBERGLASS INSULATION.
  
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 ???PILL TEST???
 (CPSC 16 CFR PART 1630) OR WITH ASTM D2859. LVT & LPT
 LUXURY VINYL TILE. FLOOR FINISH CLASSIFICATION AS
 REQUIRED IN SECTION 804.2 CLASSIFICATION AND 804.3
 TESTING AND IDENTIFICATION OF THE 2020 FBC-B. 804.2 &
 804.3/ ASTM E648 OR NFPA 253
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-10-21 Cont ID  
Sent By pleduc Date 2022-10-21 Time   Rev Time 0.00
Received By pleduc Date 2022-10-21 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-08-17 Cont ID  
Sent By pleduc Date 2022-08-17 Time   Rev Time 0.00
Received By pleduc Date 2022-08-17 Time 12:22 Sent To  
Notes
2022-08-17 12:27:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET FOR THE ACTUAL
 PROPOSED VINYL FLOORING.
  
 VINYL FLOORING IS MANUFACTURED AROUND THE WORLD AND NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT
 NAME AND SPEC SHEETS OF THE PROPOSED FINISHED
 VINYL FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 PLEASE ENSURE THE APPLICABLE PROTECTION AND PROVIDE A
 NOTE OF ACKNOWLEDGMENT ON THE FLOOR PLAN.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-11-08 Cont ID  
Sent By jwitmer Date 2022-11-08 Time 11:10 Rev Time 0.00
Received By jwitmer Date 2022-11-01 Time 15:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-10-24 Time   Rev Time 0.00
Received By lmarchan Date 2022-10-20 Time 15:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-09-20 Time   Rev Time 0.00
Received By cdecoeur Date 2022-08-16 Time 09:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-08-25 Cont ID  
Sent By ccole Date 2022-08-25 Time 14:07 Rev Time 0.00
Received By ccole Date 2022-08-25 Time 13:50 Sent To  
Notes
2022-08-25 14:07:43PLUMBING SUB-PERMIT REQUIRED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-09-20 Cont ID  
Sent By jwitmer Date 2022-09-20 Time 10:28 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***