Plan Review Details - Permit 22080597
Plan Review Stops For Permit 22080597
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-20 Cont ID  
Sent By lbond Date 2023-07-20 Time 11:48 Rev Time 0.00
Received By lbond Date 2023-07-20 Time 11:48 Sent To  
Notes
2023-07-20 11:53:06FBC 107.2.1.
  
 CLARIFY SCOPE OF WORK WITH A CLEAR FLOOR PLAN TO SCALE
 WITH DEMENSIONS EXISTING AND PROPOSED.
 NOT A COMPBINATION OF A 3D MODEL AND A 2D FLOOR PLAN.
  
 USE THE PROPOSED LAYOUT BACKGROUND FOR ALL TRADES AND
 INCLUDE WHAT REQUIRED FOR THOSE TRADES ACCORDINGLY.
  
 ANY QUESTIONS OR CONCERNS, PLEASE DO NOT HESITATE TO
 CONTACT ME:
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-06 Cont ID  
Sent By lbond Date 2023-04-06 Time 10:11 Rev Time 0.00
Received By lbond Date 2023-04-06 Time 10:11 Sent To  
Notes
2023-04-06 10:12:53COMPLY TO ALL TRADES COMMENTS FIRST.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-07-26 Cont ID  
Sent By jleahy Date 2023-07-26 Time 15:10 Rev Time 0.00
Received By jleahy Date 2023-07-26 Time 15:08 Sent To  
Notes
2023-07-26 15:11:31NO ELECTRICAL WORK SHOWN JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-04-06 Cont ID  
Sent By rperdomo Date 2023-04-06 Time 15:01 Rev Time 0.00
Received By rperdomo Date 2023-04-06 Time 13:04 Sent To  
Notes
2023-04-06 15:02:46FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE ELECTRICAL SCOPE OF WORK. FBC 107.2.1
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-26 Cont ID  
Sent By jleahy Date 2023-07-26 Time 15:11 Rev Time 0.00
Received By jleahy Date 2023-07-18 Time 08:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-06 Cont ID  
Sent By jgomez Date 2023-04-06 Time 17:11 Rev Time 0.00
Received By jgomez Date 2023-03-31 Time 14:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-07-22 Cont ID  
Sent By cmontell Date 2023-07-22 Time 11:05 Rev Time 0.00
Received By cmontell Date 2023-07-22 Time 10:56 Sent To  
Notes
2023-07-22 11:04:57MECHANICAL PLAN REVIEW FAIL
  
 1 - IS THERE TO ALSO BE A DRYER ADDED WITH THIS WASHING
 MACHINE? IF SO PROVIDE A DRAWING INDICATING THE DRYER
 DUCT SIZE AND TERMINATION LOCATION. FRC M1502
  
 2 - NEED EXHAUST FOR WATER CLOSET COMPARTMENT OR WINDOW
 OF NOT LESS THAN 3 SQ FEET FBC RESIDENTIAL
  
  
 CHRIS MONTELLO
 561-805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-04-04 Cont ID  
Sent By medwards Date 2023-04-04 Time 11:32 Rev Time 0.00
Received By medwards Date 2023-04-04 Time 11:32 Sent To  
Notes
2023-04-04 11:38:29PLEASE PROVIDE A MECHANICAL SCOPE OF WORK FOR THIS
 PROJECT.
 IS THERE TO ALSO BE A DRYER ADDED WITH THIS WASHING
 MACHINE? IF SO PROVIDE A DRAWING INDICATING THE DRYER
 DUCT SIZE AND TERMINATION LOCATION. FRC M1502
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-07-19 Cont ID  
Sent By rwbrown Date 2023-07-19 Time 07:02 Rev Time 0.00
Received By rwbrown Date 2023-07-19 Time 07:02 Sent To  
Notes
2023-07-19 07:05:112ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 THESE DRAWINGS ARE NOT REVIEWABLE. THEY DO NOT SHOW
 DIMENSIONS, PIPE SIZES, OR PROPER CONFIGURATION OF A
 CODE COMPLIANT DWV SYSTEM. THEY DO NOT SHOW A
 DIMENSIONED FLOOR PLAN THAT CLEARY SHOWS THE EXISTING
 AND PROPOSED. THE UPDATED DRAWINGS ARE NOT CLEAR AS TO
 WHAT IS BEING PROPOSED AND DOES NOT APPEAR TO BE
 COMPLIANT.
  
 1. 2017 WPB AMENDS 107.2.1 - THE DESCRIPTION SAYS
 "EXPAND DOWNSTAIRS BATHROOM", HOWEVER, YOUR PLANS DO
 NOT SHOW AN EXISTING VERSUS PROPOSED PLAN THAT WOULD
 ALLOW US TO DO A PROPER REVIEW. PLEASE PROVIDE AN
 EXISTING AND PROPOSED FLOOR PLAN THAT SHOWS THE CHANGES
 FROM THE OLD TO THE NEW.
  
 2. 2017 WPB AMEND 107.3.5.3 (12) - THE PLUMBING
 DRAWINGS ARE TO BE IN ISOMETRIC (RISER) FORM. THESE
 DRAWING DO NOT INDICATE A REVIEWABLE SET OF DRAWINGS.
 PLEASE SHOW A RISER THAT HAS CODE COMPLIANT VENTING AND
 DRAINS. SHOW PIPE SIZES WHERE NEEDED.
  
 3. 2017 WPB AMENDS 107.2.1 - THE TITLE OF PAGE 2 SAYS
 "PLUMBING FOR WASHER" BUT DOES NOT REPRESENT A WASHER.
 IT REPRESENTS A SINK. PLEASE SUBMIT THE PROPER DRAWING
 FOR THE APPLICATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-04-04 Cont ID  
Sent By rwbrown Date 2023-04-04 Time 14:19 Rev Time 0.00
Received By rwbrown Date 2023-04-04 Time 14:17 Sent To  
Notes
2023-04-04 14:23:421ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - THE DESCRIPTION SAYS
 "EXPAND DOWNSTAIRS BATHROOM", HOWEVER, YOUR PLANS DO
 NOT SHOW AN EXISTING VERSUS PROPOSED PLAN THAT WOULD
 ALLOW US TO DO A PROPER REVIEW. PLEASE PROVIDE AN
 EXISTING AND PROPOSED FLOOR PLAN THAT SHOWS THE CHANGES
 FROM THE OLD TO THE NEW.
  
 2. 2017 WPB AMEND 107.3.5.3 (12) - THE PLUMBING
 DRAWINGS ARE TO BE IN ISOMETRIC (RISER) FORM. THESE
 DRAWING DO NOT INDICATE A REVIEWABLE SET OF DRAWINGS.
 PLEASE SHOW A RISER THAT HAS CODE COMPLIANT VENTING AND
 DRAINS. SHOW PIPE SIZES WHERE NEEDED.
  
 3. 2017 WPB AMENDS 107.2.1 - THE TITLE OF PAGE 2 SAYS
 "PLUMBING FOR WASHER" BUT DOES NOT REPRESENT A WASHER.
 IT REPRESENTS A SINK. PLEASE SUBMIT THE PROPER DRAWING
 FOR THE APPLICATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-04-06 Cont ID  
Sent By lbond Date 2023-04-06 Time 10:13 Rev Time 0.00
Received By lbond Date 2023-04-06 Time 10:13 Sent To  
Notes
***NONE***