Plan Review Details - Permit 22080594
Plan Review Stops For Permit 22080594
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-11-08 Cont ID  
Sent By cpuell Date 2022-11-08 Time 08:58 Rev Time 0.00
Received By cpuell Date 2022-11-08 Time 08:58 Sent To  
Notes
2022-11-08 09:00:29HALF ADDRESS READDRESSED AS 239 MONROE DR, PER BUILDING
 COMMENTS A SEPARATE PERMIT IS REQUIRED FOR THE NORTH
 BUILDING WITH THE ADDRESS 239 MONROE DR

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-09-14 Cont ID  
Sent By cpuell Date 2022-09-14 Time 12:29 Rev Time 0.00
Received By cpuell Date 2022-09-14 Time 12:29 Sent To  
Notes
2022-09-14 12:30:16WORK TO BE DONE ON THE NORTH AND THE SOUTH BUILDING.
 THE NORTH BUILDING HAS A HALF ADDRESS WHICH WILL NEED
 TO BE READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO READDRESS
 THE HALF ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-02-01 Cont ID  
Sent By cthroop Date 2023-02-01 Time 13:37 Rev Time 0.00
Received By cthroop Date 2023-02-01 Time 12:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-12-14 Cont ID  
Sent By cthroop Date 2022-12-14 Time 09:34 Rev Time 0.00
Received By cthroop Date 2022-12-13 Time 13:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-07 Cont ID  
Sent By cthroop Date 2022-10-07 Time 15:51 Rev Time 0.00
Received By cthroop Date 2022-10-07 Time 14:23 Sent To  
Notes
2022-10-07 15:55:001ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: A SEPERATE PERMIT IS REQUIRED FOR THE 2-STORY
 GARAGE.
  
 1. PROVIDE AN ENERGY SUBMITTAL RESIDENTIAL (RE)
 R401.2COMPLIANCE.
 PROJECTS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1.SECTIONS R401 THROUGH R404.
 2.SECTION R405 AND THE PROVISIONS OF SECTIONS R401
 THROUGH R404 LABELED MANDATORY.
  
 2. NOA 21-0708.03 HAS EXPIRED.
 PROVIDE CURRENT PRODUCT APPROVALS OR NOA FOR PROPOSED
 FIXED WINDOWS.
 PRODUCT APPROVALS INCLUDE THE COVER SHEET, EVALUATION
 REPORT AND INSTALLATION INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3.PROVIDE THE DESIGN PRESSURES FOR NEW ROOFING PER
 FIGURE R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES
 R301.2.1.1WIND DESIGN REQUIRED.
  
 4.PROVIDE A ROOF SHEATHING FASTENER SCHEDULE PER THE
 CALCULATED DESIGN PRESSURES.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-01-19 Cont ID  
Sent By mpeterso Date 2023-01-19 Time 14:33 Rev Time 0.00
Received By mpeterso Date 2023-01-19 Time 14:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-06 Cont ID  
Sent By mpeterso Date 2022-12-06 Time 10:18 Rev Time 0.00
Received By mpeterso Date 2022-12-06 Time 08:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-09-08 Cont ID  
Sent By mpeterso Date 2022-09-08 Time 11:09 Rev Time 0.00
Received By mpeterso Date 2022-09-08 Time 10:47 Sent To  
Notes
2022-09-08 11:12:13ELECTRIC REVIEW FAILED
 1) PLEASE CLARIFY THE CONFLICTING INSTANCE OF THE AIR
 CONDITIONING IN THE MAIN HOUSE. WILL THIS BE AN AIR
 HANDLER ON THE FIRST FLOOR, SECOND FLOOR OR A ROOF TOP
 UNIT? WILL THERE BE A SEPARATE CONDENSER, IF SO, PLEASE
 LOCATE ON ELECTRICAL PLAN? PLEASE DETAIL ALL UNITS ON
 ELECTRICAL PLAN, PANEL SCHEDULES AND LOAD CALCULATIONS.
 FBC 107.2 AND NEC 215.5
 2) PLEASE DETAIL ALL MINISPLIT AND THEIR ASSOCIATED
 OUTDOOR UNIT LOCATIONS ON ELECTRICAL PLANS. IN ADDITION
 PLEASE PROVIDE THERE SPECIFICATIONS, IE, VOLTAGE AMPS
 AND WHETHER THE ASSOCIATED UNITS ARE POWER FROM THE
 MAIN UNIT.
 3) PLEASE CLARIFY THE WATER HEATER LOCATIONS AND
 SPECIFICATIONS. THERE IS ONLY ONE INSTANCE ON A PANEL
 SCHEDULE INDICATING A WATER HEATER. PLEASE DETAIL ALL
 UNITS ON ELECTRICAL PLAN, PANEL SCHEDULES AND LOAD
 CALCULATIONS. FBC 107.2 AND NEC 215.5
 4) PLEASE DETAIL POOL EQUIPMENT LOCATIONS ON ELECTRIC
 PLAN, PANEL SCHEDULES AND LOAD CALCULATIONS. FBC 107.2
 AND NEC 215.5
 5) PLEASE CORRECT MISLABELED PANEL SCHEDULES. FBC 107.2
 6) PLEASE PROVIDE ACCURATE ELECTRICAL RISER DIAGRAM
 DETAILING ALL ELECTRIC PANELS, DISCONNECTS, METERS,
 CONDUIT AND CONDUCTOR SIZES, OVERCURRENT PROTECTION AND
 GROUNDING ELECTRODE SYSTEMS AS APPLICABLE. NEC 215.5,
 NEC 250.30 AND 250.32 FOR GES REQUIREMENTS AT SEPARATE
 STRUCTURES
 7) PLEASE DETAIL ELECTRIC FEEDER AND SERVICE LOAD
 CALCULATIONS FOR MAIN ELECTRIC SERVICE AND ALL
 APPLICABLE PANELS WITH ACCURATE LABELS FOR EACH. ENSURE
 TO INCLUDE ALL APPLICABLE LOADS AS PER NEC 220 PART III
 OR PART IV FOR OPTIONAL CALCULATIONS IN EACH
 CALCULATION. FBC 107.2 AND NEC 215.5
 8) PLEASE DETAIL OUTSIDE RECEPTACLES AS REQUIRED BY NEC
 210.52(E) AND NEC 210.63
 9) PLEASE CLARIFY CONFLICTING LOCATIONS FOR
 REFRIGERATOR AND RANGE IN MAIN HOUSE. IT IS DIFFERENT
 ON FLOOR PLANS, ELECTRIC PLANS AND OTHERS. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2023-01-30 Cont ID  
Sent By amhamilt Date 2023-01-30 Time 15:16 Rev Time 0.00
Received By amhamilt Date 2023-01-30 Time 15:16 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-11-23 Cont ID  
Sent By fmittner Date 2022-11-23 Time 14:46 Rev Time 0.00
Received By fmittner Date 2022-11-23 Time 14:46 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2022-09-14 Cont ID  
Sent By amhamilt Date 2022-09-14 Time 14:37 Rev Time 0.00
Received By amhamilt Date 2022-09-14 Time 14:37 Sent To  
Notes
2022-09-14 14:39:06THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PLEASE VERIFY ON WINDOW SCHEDULE THAT ALL WINDOWS WILL
 HAVE CLEAR GLASS (LOW E PERMISSIBLE ON SIDES AND REAR
 ELEVATIONS, PLEASE INDICATE IF USED)
  
 PLEASE ALSO VERIFY ON WINDOW SCHEDULE THAT ALL MUNTINS
 WILL BE EXTERNALLY APPLIED WITH EITHER AN OGEE OR
 PYRAMID PROFILE (PLEASE INDICATE WHICH PROFILE USED).
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-01 Cont ID  
Sent By aoliver Date 2023-02-01 Time 14:24 Rev Time 0.00
Received By aoliver Date 2023-01-13 Time 07:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-14 Cont ID  
Sent By cthroop Date 2022-12-14 Time 09:44 Rev Time 0.00
Received By cthroop Date 2022-11-16 Time 09:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-07 Cont ID  
Sent By cthroop Date 2022-10-07 Time 15:58 Rev Time 0.00
Received By cthroop Date 2022-08-17 Time 15:45 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-02-02 Cont ID  
Sent By aoliver Date 2023-02-02 Time 10:58 Rev Time 0.00
Received By aoliver Date 2023-01-30 Time 16:37 Sent To  
Notes
2023-02-02 10:57:46NO IMPACT FEES DUE, SEE EMAIL UPLOADED
2023-01-30 16:37:401/30/23 EMAILED IMPACT OFFICE PER DBATTLES. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-10-07 Cont ID  
Sent By cthroop Date 2022-10-07 Time 15:46 Rev Time 0.00
Received By cthroop Date 2022-10-07 Time 14:23 Sent To  
Notes
2022-10-07 15:47:27IMPACT FEES
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-03-02 Cont ID  
Sent By medwards Date 2023-03-02 Time 16:03 Rev Time 0.00
Received By medwards Date 2023-03-02 Time 16:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-01-17 Cont ID  
Sent By medwards Date 2023-01-17 Time 08:59 Rev Time 0.00
Received By medwards Date 2023-01-17 Time 08:59 Sent To  
Notes
2023-01-17 08:59:54SEE SIGNATURE REVIEW COMMENTS BELOW:
  
 SIGNATURE REVIEW:
  
 1) THE SUBMITTED PAPER DRAWINGS HAVE THE WET SIGNATURE
 OF THE ARCHITECT OF RECORD BUT THEY DON'T HAVE THE
 RAISED OR INK SEAL. ONLY DRAWING CV1 HAS THE
 ARCHITECT'S RAISED SEAL AND WET SIGNATURE. NEED ALL
 DRAWINGS WITH RAISED SEAL AND WET SIGNATURE. FL.
 STATUTE 481.221 AND SEC. 61G1-16.002 FAC.
  
 NOTE:
 THE FOLLOWING ARE THE PAPER DRAWINGS INCLUDED IN THIS
 SUBMITTAL:
 CV1, SP2, A3, A4, A5, S1, E1, E2, M1, P1 AND P2.
 DRAWING LS WAS ALSO SUBMITTED BUT IT WAS DISCARDED
 BECAUSE THIS DRAWING IS SUPPOSED TO BE SUBMITTED WITH
 THE LANDSCAPE PERMIT. JG.
 ************************************************

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-11-21 Cont ID  
Sent By medwards Date 2022-11-21 Time 13:18 Rev Time 0.00
Received By medwards Date 2022-11-21 Time 13:18 Sent To  
Notes
2022-11-21 13:18:252ND REVIEW FMC
 PERMIT: 22080594
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1 IS FOR THE MAIN HOUSE REMODEL ONLY, THE
 GARAGE MECHANICAL DRAWING WAS NOT SUBMITTED WITH THIS
 NEW SUBMITTAL. PROVIDE THE MECHANICAL DESIGN INCLUDING
 CLEARLY LABELING THE ENERGY AND MECHANICAL CALCULATIONS
 AS TO WHICH BUILDING THEY ADDRESS. PROVIDE A SCOPE OF
 WORK AS TO WHAT IS EXISTING AND NOT IN THE SCOPE OF
 WORK AND EXACTLY WHAT IS IN THE SCOPE OF WORK. CASE IN
 POINT, THE MASTER BEDROOM AREA DOES NOT SHOW ANY
 CONDITIONING BUT THERE ARE 2 BATH EXHAUST FANS. FBC
 107.3.5
  
 2) THE ARCHITECT KEITH D CHAMBERS MUST DIGITALLY SIGN
 THE MECHANICAL DRAWINGS. F.S. 471/481
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-08-25 Cont ID  
Sent By medwards Date 2022-08-25 Time 10:56 Rev Time 0.00
Received By medwards Date 2022-08-25 Time 10:56 Sent To  
Notes
2022-08-25 10:56:361ST REVIEW FMC
 PERMIT: 22080594
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THE NEW
 ADDITION. FEC R401.2
  
 2) SHOW THE CONDENSATE PIPING MATERIAL AND TERMINATION
 LOCATION. FRC M1411.3.2
  
 3) PROVIDE THE ENERGY CALCULATIONS FOR THE GARAGE
 APARTMENT. FEC R401.2
  
 4) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THE GARAGE APARTMENT. FEC R403.7
  
 5) PROVIDE A MECHANICAL DRAWING FOR THE MECHANICAL
 SYSTEM OF THE GARAGE APARTMENT. FBC 107.3.5
  
 6) PROVIDE ANCHORAGE DETAILS FOR THE CONDENSING UNITS.
 FRC M1307.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-01-17 Cont ID  
Sent By rwbrown Date 2023-01-17 Time 09:32 Rev Time 0.00
Received By rwbrown Date 2023-01-17 Time 09:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-11-17 Cont ID  
Sent By rwbrown Date 2022-11-17 Time 07:56 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-08-26 Cont ID  
Sent By rwbrown Date 2022-08-26 Time 06:23 Rev Time  
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2023-02-01 Cont ID  
Sent By cthroop Date 2023-02-01 Time 13:38 Rev Time 0.00
Received By cthroop Date 2023-02-01 Time 12:48 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-12-14 Cont ID  
Sent By cthroop Date 2022-12-14 Time 09:42 Rev Time 0.00
Received By cthroop Date 2022-12-13 Time 13:48 Sent To  
Notes
2022-12-14 09:44:392ND ROOFING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: COMMENTS FROM 1ST REVIEW HAVE NOT BEEN
 ADDRESSED. SEE BELOW:
  
 1. PROVIDE PRODUCT APPROVALS FOR SECONDARY WATER
 BARRIER PER FBC R905.1.1.
 UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL
 CONFORM TO THE APPLICABLE STANDARDS??? AND SHALL BE
 APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION
 R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE.
  
 REFERENCE NOA 18-0919.12 FOR THE FOLLOWING COMMENT:
  
 2. DESIGNER SHALL SELECT SYSTEM TO BE INSTALLED.
 INDICATE ON THE COVER PAGE WHAT SYSTEM AND PAGE NUMBER
 IT'S LOCATED ON.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. GENERAL LIMITATION #9 MAY APPLY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-10-07 Cont ID  
Sent By cthroop Date 2022-10-07 Time 15:47 Rev Time 0.00
Received By cthroop Date 2022-10-07 Time 14:23 Sent To  
Notes
2022-10-07 15:51:361ST ROOFING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1. PROVIDE PRODUCT APPROVALS FOR SECONDARY WATER
 BARRIER PER FBC R905.1.1.
 UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL
 CONFORM TO THE APPLICABLE STANDARDS??? AND SHALL BE
 APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION
 R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE.
  
 REFERENCE NOA 18-0919.12 FOR THE FOLLOWING COMMENT:
  
 2. DESIGNER SHALL SELECT SYSTEM TO BE INSTALLED.
 INDICATE ON THE COVER PAGE WHAT SYSTEM AND PAGE NUMBER
 IT'S LOCATED ON.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-01-31 Cont ID  
Sent By dbattles Date 2023-01-31 Time 13:55 Rev Time 0.00
Received By dbattles Date 2023-01-31 Time 13:55 Sent To  
Notes
2023-03-02 16:41:45HARD COPY OF FULL SET SENT TO STORAGE. 2/10/23

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-01-13 Cont ID  
Sent By jgomez Date 2023-01-13 Time 18:10 Rev Time 0.00
Received By jgomez Date 2023-01-13 Time 17:14 Sent To  
Notes
2023-01-13 17:38:21SIGNATURE REVIEW:
  
 1) THE SUBMITTED PAPER DRAWINGS HAVE THE WET SIGNATURE
 OF THE ARCHITECT OF RECORD BUT THEY DON'T HAVE THE
 RAISED OR INK SEAL. ONLY DRAWING CV1 HAS THE
 ARCHITECT'S RAISED SEAL AND WET SIGNATURE. NEED ALL
 DRAWINGS WITH RAISED SEAL AND WET SIGNATURE. FL.
 STATUTE 481.221 AND SEC. 61G1-16.002 FAC.
  
 NOTE:
 THE FOLLOWING ARE THE PAPER DRAWINGS INCLUDED IN THIS
 SUBMITTAL:
 CV1, SP2, A3, A4, A5, S1, E1, E2, M1, P1 AND P2.
 DRAWING LS WAS ALSO SUBMITTED BUT IT WAS DISCARDED
 BECAUSE THIS DRAWING IS SUPPOSED TO BE SUBMITTED WITH
 THE LANDSCAPE PERMIT. JG.
 ************************************************

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-11-16 Cont ID  
Sent By ccole Date 2022-11-16 Time 09:59 Rev Time 0.00
Received By ccole Date 2022-11-16 Time 09:59 Sent To  
Notes
2022-11-16 10:00:371ST REVIEW FBC-2020 SIGNATURE
 PERMIT- 22110594
 11/16/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED PAPER PLANS DO NOT BEAR THE RAISED OR
 INK SEALS AND SIGNATURES OF THE ARCHITECT OF RECORD-
 FL. STATUTE 481.221 AND SEC. 61G1-16.002 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-08-24 Cont ID  
Sent By mpeterso Date 2022-08-24 Time 15:46 Rev Time 0.00
Received By mpeterso Date 2022-08-24 Time 15:46 Sent To  
Notes
2022-08-24 15:46:438/24/22 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS
 PASSED AND ROUTED TO STORAGE.MP

Review Stop Z ZONING
Rev No 4 Status P Date 2023-03-02 Cont ID  
Sent By amhamilt Date 2023-03-02 Time 16:16 Rev Time 0.00
Received By amhamilt Date 2023-03-02 Time 16:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2023-01-30 Cont ID  
Sent By fmittner Date 2023-01-30 Time 15:15 Rev Time 0.00
Received By amhamilt Date 2023-01-30 Time 15:15 Sent To  
Notes
2023-01-30 15:15:39THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 **PREVIOUS COMMENTS STILL NOT ADDRESSED SEE BELOW**
  
 THE VALUE OF THE CONSTRUCTION ($120,000.00) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($212,687.00) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. SUBMIT A SEPARATE LANDSCAPE
 PERMIT WITH PLANS SHOWING MATERIAL EXISTING ON SITE OR
 ANY ADDITION OF TREES OR SHRUBS TO BRING THE SITE INTO
 CONFORMITY.
  
 REASON:
 FOR THE MAJORITY OF PROPERTIES, THE EXISTING LANDSCAPE
 IS NON-CONFORMING. THE MINIMAL CHARGE FOR A PERMIT
 VALUE OF LESS THAN $2500.00 IS $125.00. THIS ALLOWS FOR
 STAFF TO REVIEW THE EXISTING MATERIAL ON SITE TO VERIFY
 THE REQUIREMENTS ARE MET AND ALSO ALLOWS FOR AN
 INSPECTION TO CONFIRM THE SITE IS IN COMPLIANCE AT THE
 CONCLUSION OF THE PROJECT.
  
 NEW SINGLE FAMILY AND ALL OTHER NEW STRUCTURES REQUIRE
 A LANDSCAPE PERMIT BE SUBMITTED OR USE THE CONDITIONAL
 APPROVAL FORM.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-11-23 Cont ID  
Sent By amhamilt Date 2022-11-23 Time 14:47 Rev Time 0.00
Received By fmittner Date 2022-11-23 Time 14:47 Sent To  
Notes
2022-11-23 14:48:05SEE NOTES FROM FIRST REVIEW....STILL NO SEPARATE
 LANDSCAPE PLAN SUBMITTED.

Review Stop Z ZONING
Rev No 1 Status F Date 2022-08-26 Cont ID  
Sent By asangele Date 2022-08-26 Time 14:15 Rev Time 0.00
Received By asangele Date 2022-08-26 Time 14:15 Sent To  
Notes
2022-08-26 14:21:22FAILED
 8/26/2022
  
 NEEDS TO APPLY FOR A LANDSCAPE PERMIT
  
 THE VALUE OF THE CONSTRUCTION ($600,000) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($212,687) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 PLEASE ALSO PROVIDE BUILDING HEIGHT ELEVATION OF THE
 PROPOSED ADDITION HEIGHT IS MEASURED FROM GRADE.
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]