| 2022-08-31 10:27:55 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22080569 |
| | 8/30/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P.219: THE SUBMITTED NARRATIVE OF PLUMBING |
| | CHANGES PROVIDES VERY GENERAL INFORMATION. PLEASE |
| | PROVIDE A DETAILED NARRATIVE THAT ITEMIZES ALL |
| | REVISIONS MADE TO THE PLAN FROM REV-2 (12/14/2020) TO |
| | REV-11 (08/05/2020). PLEASE UPDATE THE REVISION |
| | SCHEDULE ON THE PLAN WITH DELTA SYMBOLS AND DATES THAT |
| | CORRESPOND WITH THE DESIGN CHANGES- SEC. 107.2.1 WPB. |
| | COMPARISONS OF THE APPROVED PLAN (09/15/2021) AND THE |
| | SUBMITTED REVISED PLANS SHOW CHANGES THAT INCLUDE: |
| | A) REMOVAL OF THE MEN'S AND WOMEN'S GANG BATHROOMS, |
| | POOL EQUIPMENT ROOM, & SERVICE BAR. |
| | B) MULTIPLE CHANGES TO BATHROOM LAYOUTS AND PLUMBING |
| | FIXTURES IN THE ROOMS INCLUDING A NEW ADA COMPLIANT |
| | ROOM 1.3. |
| | C) A NEW KITCHEN WHICH WILL REQUIRE A GREASE |
| | INTERCEPTOR AND A GREASE WASTE LINE- SEC. 1003.3.1 FBC |
| | P. |
| | PLEASE REVISE ALL PLUMBING AND ARCHITECTURAL PLANS THAT |
| | ARE AFFECTED BY THE CHANGES IN DESIGN. |
| | |
| | 2) P.219: SUBMIT REVISED SHEET P.509 WHICH IS CALLED |
| | OUT IN THE NOTE AT THE KITCHEN- SEC. 107.2.1 WPB. |
| | |
| | 3) P.219, P.220, P.221, P.222, P.223, P.224: CHANGES TO |
| | ACCESSIBLE BATHROOM FIXTURE LAYOUTS, PLUMBING PIPING |
| | LAYOUTS AND RISERS ARE INDICATED. PLEASE SUBMIT THE |
| | REVISED SHEETS CALLED OUT ON THE PLANS- P.701A, & |
| | P.703- SEC. 107.2.1 WPB. ALTERNATIVELY, IF NEW SHEETS |
| | HAVE BEEN PROVIDED PLEASE REVISE THE TARGET NOTES TO |
| | MATCH. |
| | |
| | 4) P.219, P.220, P.221, P.222, P.223, P.224: PROVIDE |
| | REVISED ENLARGED AND DETAILED ARCHITECTURAL DRAWINGS |
| | FOR THE ACCESSIBLE BATHROOMS- SEC. 213.2 & SECS. 603.1- |
| | 610.1 FBC ACC. |
| | |
| | 5) P.219: REFERENCE NOTE FOR ENLARGED UNIT PIPING |
| | LAYOUT NOT PROVIDED IN ADA ROOM 1.3A- SEC. 107.2.1 WPB. |
| | |
| | 6) P.220: REFERENCE NOTES FOR ENLARGED UNIT PIPING |
| | LAYOUT NOT PROVIDED IN SUITE 4KL, AND ROOM 1.3A- SEC. |
| | 107.2.1 WPB. |
| | |
| | 7) P.221 & P.222: REFERENCE NOTES FOR ENLARGED UNIT |
| | PIPING LAYOUT NOT PROVIDED IN MANY OF THE ROOMS. PLEASE |
| | REVIEW AND REVISE- SEC. 107.2.1 WPB. |
| | |
| | 8) P.501 & P.503A: PLEASE SUBMIT THE REVISED SHEETS |
| | CALLED OUT ON THE PLANS- P.701A, & P.703- SEC. 107.2.1 |
| | WPB. ALTERNATIVELY, IF NEW SHEETS HAVE BEEN PROVIDED, |
| | PLEASE REVISE THE TARGET NOTES TO MATCH. |
| | |
| | 9) P.512: THE NARRATIVE INDICATES NEW BATHROOMS AT THE |
| | 12TH FLOOR. PLEASE PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P. |
| | INDICATE THE REQUIRED AND PROVIDED NUMBER OF FIXTURES |
| | BASED ON THE TABLE. |
| | |
| | 10) P.512: THE NARRATIVE DOES NOT PROVIDE ANY |
| | INFORMATION ABOUT THE NEW LOCKER ROOM BATHS- SEC. |
| | 107.2.1 WPB. PLEASE PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P. |
| | INDICATE THE REQUIRED AND PROVIDED NUMBER OF FIXTURES |
| | BASED ON THE TABLE. |
| | |
| | 11) P.512: PROVIDE REVISED THE MAIN SANITARY RISER |
| | DRAWINGS AND DFU CALCULARTIONS BASED ON THE ADDED |
| | PLUMBING FIXTURES IN THE TOWER- SEC. 107.3.5.1.3 WPB, |
| | AND SEC. 710.1 FBC P. |
| | |
| | 12) P.512: PROVIDE REVISED ENLARGED AND DETAILED |
| | ARCHITECTURAL DRAWINGS FOR THE ACCESSIBLE BATHROOMS ON |
| | THE 7TH AND 12TH FLOORS SEC. 213.2 & SECS. 603.1- 610.1 |
| | FBC ACC. |
| | |
| | 13) P.512: SHOW THE SOURCES OF THE HOT WATER AND |
| | CLARIFY IF NEW WATER HEATERS HAVE BEEN SELECTED AS PART |
| | OF THE REVISION TO SUPPLY THE FIXTURES- SEC. 607.1 FBC |
| | P. PLEASE PROVIDE WATER HEATER EQUIPMENT SCHEDULES IF |
| | APPLICABLE- SEC. 107.2.1 WPB. |
| | |
| | 14) P.512: THE 1/2-INCH FIXTURE SUPPLY PIPES SUPPLYING |
| | HOT WATER TO THE LAVATORIES HAVE EXCEEDED THE MAXIMUM 2 |
| | FT. LENGTHS ALLOWABLE PER TABLE C404.5.1 FBC EC. THE |
| | HWR LINE MUST LOOP DOWN TO THE LAVS, OR POINT OF USE |
| | WATER HEATERS SHALL BE PROVIDED. |
| | |
| | 15) P.512: INDICATE HOW TRAP SEAL PROTECTION IS BEING |
| | PROVIDED FOR THE FLOOR DRAINS- SEC. 1002.4.1 FBC P. |
| | |
| | 16) P.705A: BT-X & SH-X SHOWN IN THE RISER FOR UNITS |
| | 1.3A- 4.2A NEED TO BE VENTED PER SEC. 901.2.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | |