Plan Review Details - Permit 22080569
Plan Review Stops For Permit 22080569
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-04-28 Cont ID  
Sent By rmcdouga Date 2023-04-28 Time 09:46 Rev Time 0.00
Received By rmcdouga Date 2023-04-28 Time 09:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-03-10 Cont ID  
Sent By rmcdouga Date 2023-03-10 Time 15:35 Rev Time 0.00
Received By rmcdouga Date 2023-03-10 Time 11:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-10-04 Cont ID  
Sent By rmcdouga Date 2022-10-04 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2022-10-04 Time 13:59 Sent To  
Notes
2022-10-04 14:10:12THE FIRST REVIEW WAS LOCKED BY ACCIDENT.
  
 PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET 03.033 - A1.214, THERE IS NO DOOR SHOWN TO
 THE BATHRROOM IN ROOM HO408. FBC 107.2.1
  
 2) ON SHEET 03.049 - A1.230 THE REVISED AREA WHERE THE
 MENS AND WOMENS BATHROOMS AND POOL EQUIPMENT ROOM HAVE
 BEEN REPLACED BY THE TWO KITCHENS AND POOL BAR IS NOT
 CLOUDED. FBC 107.2.1
  
 3) PROVIDE A NARRATIVE THAT EXPLAINS THIS CHANGE.
 SPECIFY WHERE THE MENS AND WOMENS BATHROOMS AND POOL
 EQUIPMENT ROOM HAVE BEEN RELOCATED. FBC 107.2.1
  
 4) CLARIFY THE LOCATIONS OF THE RESTROOMS FOR THE POOL
 AREA. FBC 107.2.1
  
 5) I COULD NOT LOCATE SHEET ALS1.114 - THE RESIDENTIAL
 LEVEL 12 LIFE SAFETY PLAN THAT IS LISTED ON THE
 NARRATIVE THAT WAS SUBMITTED. FBC 107.2.1
  
 6) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date   Cont ID  
Sent By rmcdouga Date   Time   Rev Time 0.00
Received By rmcdouga Date 2022-10-03 Time 07:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-07 Cont ID  
Sent By jleahy Date 2023-03-07 Time 13:18 Rev Time 0.00
Received By jleahy Date 2023-03-07 Time 13:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-09-22 Cont ID  
Sent By jleahy Date 2022-09-22 Time 10:49 Rev Time 0.00
Received By jleahy Date 2022-09-22 Time 10:39 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2023-04-21 Cont ID  
Sent By lquinone Date 2023-04-21 Time 15:34 Rev Time 0.00
Received By lquinone Date 2023-04-21 Time 15:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-02-21 Cont ID  
Sent By pleduc Date 2023-02-21 Time   Rev Time 0.00
Received By pleduc Date 2023-02-21 Time 13:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-08-29 Cont ID  
Sent By pleduc Date 2022-08-29 Time   Rev Time 0.00
Received By pleduc Date 2022-08-23 Time 10:17 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2022-09-27 Cont ID  
Sent By ccole Date 2022-09-27 Time 11:40 Rev Time 0.00
Received By ccole Date 2022-09-27 Time 11:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-01 Cont ID  
Sent By medwards Date 2023-05-01 Time 08:16 Rev Time 0.00
Received By aoliver Date 2023-04-13 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-10 Cont ID  
Sent By rmcdouga Date 2023-03-10 Time 15:35 Rev Time 0.00
Received By rmcdouga Date 2023-02-16 Time 06:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-08 Cont ID  
Sent By aoliver Date 2022-11-08 Time 11:47 Rev Time 0.00
Received By aoliver Date 2022-08-22 Time 12:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-05-01 Cont ID  
Sent By medwards Date 2023-05-01 Time 08:14 Rev Time 0.00
Received By medwards Date 2023-05-01 Time 08:14 Sent To  
Notes
2023-05-01 08:15:33THESE COMMENTS ARE BEING ADDRESSED IN THE 22120277
 REVISION FOR THIS PROJECT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-02-24 Cont ID  
Sent By medwards Date 2023-02-24 Time 15:21 Rev Time 0.00
Received By medwards Date 2023-02-24 Time 15:21 Sent To  
Notes
2023-02-24 15:22:032ND REVIEW FMC
 PERMIT: 22080569
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 THERE WERE SEVERAL SHEETS SUBMITTED THAT WERE NOT ON
 THE NARRATIVE. BELOW IS A LIST OF COMMENTS.
  
 1) SHEET M.208A: EXPLAIN EG-10 IN WHAT WAS THE TENNIS
 STORAGE AREA.
  
 2) SHEET M.208A: EXPLAIN THE AREA WHERE THE NEW VAV-7
 IS CONDITIONING. ALSO PROVIDE THE EQUIPMENT SIZING
 CALCULATIONS AND OUTDOOR AIR CALCULATIONS FOR THIS
 SPACE. FEC C402 : FEC C403.2.1
  
 3) SHEET M.208B: PROVIDE THE ENERGY CALCULATIONS FOR
 THE NEW KITCHEN AND DINING SPACES. FEC C402
  
 4) ADD A NOTE TO THESE DRAWINGS STATING THAT THE
 KITCHEN HOOD AND GREASE DUCT WILL REQUIRE A SEPARATE
 PERMIT, DOCUMENT SUBMITTAL AND PLAN REVIEW AS THEY WILL
 NOT BE REVIEWED UNDER THIS REVISION.
  
 5) ADD A NOTE TO THESE DRAWINGS STATING THAT THE
 WALK-IN COOLER WILL REQUIRE A SEPARATE PERMIT, DOCUMENT
 SUBMITTAL AND PLAN REVIEW AS THEY WILL NOT BE REVIEWED
 UNDER THIS REVISION.
  
 6) SHOW HOW THE NEW HOTEL ROOMS MECHANICAL SYSTEMS
 MEET THE ENERGY REQUIREMENTS OF FEC C403.2.4.8
  
 7) SHEET M.252: NEW ENLARGED ROOMS: THE CLOUDED
 DRAWINGS REFERENCE NOTES 5, 6 AND 8 BUT NOTES 5, 6 AND
 8 ARE NOT ON THE DRAWINGS. INCLUDE THE NOTES ON THE
 DRAWINGS. THESE NEW ENLARGED ROOMS WILL REQUIRE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS. FBC 107.3.5
 AND FEC C403.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-08-31 Cont ID  
Sent By medwards Date 2022-08-31 Time 15:29 Rev Time 0.00
Received By medwards Date 2022-08-31 Time 15:29 Sent To  
Notes
2022-08-31 15:30:011ST REVIEW FMC
 PERMIT: 22080569
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THAT THE LAST REVISION THAT WE HAVE
 RECEIVED AND REVIEWED WAS REVISION NUMBER 2 DATED
 12/14/2020. EVIDENTLY THERE HAVE BEEN SEVERAL DESIGN
 CHANGES FROM THE 2ND REVISION TO THIS REVISION 11 THAT
 HAS BEEN SUBMITTED. PROVIDE A COMPLETE LIST OF CHANGES
 AND IDENTIFY THE CHANGES ON THE DRAWINGS AS THERE IS NO
 WAY THIS REVIEWER COULD FOLLOW ALL THE CHANGES THAT
 HAVE BEEN MADE. EXAMPLE: SHEET M.208B HAS THE WOMEN?S
 BATHROOM AND THE POOL EQUIPMENT ROOM BEING REMOVED AND
 A KITCHEN AND BAR ARE NOW TAKING THEIR PLACES. THIS
 ISN?T EVEN CLOUDED TO SHOW AS A CHANGE? THERE ARE
 GENERAL NOTES THAT HAVE CHANGED BUT ARE NOT IDENTIFIED
 AS A CHANGE. I CANNOT COMPLETE THIS REVIEW UNTIL A
 DETAILED NARRATIVE OF CHANGES HAS BEEN SUBMITTED ALONG
 WITH DRAWINGS IDENTIFYING THE CHANGES. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-04-21 Cont ID  
Sent By ccole Date 2023-04-21 Time 13:07 Rev Time 0.00
Received By ccole Date 2023-04-21 Time 07:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-02-24 Cont ID  
Sent By ccole Date 2023-02-24 Time 12:26 Rev Time 0.00
Received By ccole Date 2023-02-23 Time 12:03 Sent To  
Notes
2023-02-24 12:27:122ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22080569
 2/24/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #1, 2, & 4
 FROM THE 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL
 NOTES
  
 1) 2ND REVIEW- SHEET P.219: IN RESPONSE TO MY 1ST
 REVIEW COMMENTS THE MEP NARRATIVE IS DIRECTING ME TO
 PLAN REVISIONS SUBMITTED UNDER PERMIT 22120277 WHICH
 CURRENTLY HAS A FAILED 1ST PLUMBING REVIEW FOR
 INCOMPLETE PLANS. COMMENTS FROM THE REVIEW INDICATE
 MISSING PLAN SHEETS P106A, 106A, P106B, P106C, P107A,
 P107B, & P107C. I RESEARCHED THE PLANS AND NARRATIVE
 UNDER 22120277 AND THE MISSING SHEETS ARE THE NEW 8TH
 FLOOR KITCHEN AND BAR WASTE AND WATER PIPING PLANS AS
 CALLED OUT IN THE 22120277 NARRATIVE. I WAS ABLE TO
 LOCATE THE KITCHEN AND BAR PLUMBING LAYOUT DRAWINGS AND
 ISOMETRICS FOR THE RELOCATED KITCHEN SHOWN ON SHEETS
 P.517 & P.714 AND HAVE THESE COMMENTS- A, B, & C.
  
 A) THE KW DRAIN LINES SHOWN ON SHEETS P.517 & P.714 ARE
 GREASE WASTE (GW)? IF THAT IS CORRECT IT APPEARS THE
 HANDSINKS AND FLOOR SINKS UNDER ICE MAKERS AND ICE BINS
 ARE DRAINING INTO THE GREASE WASTE INTERCEPTOR WHICH IS
 NOT ALLOWED PER SEC. 1003.3.1 FBC P. PLEASE REVISE THE
 DRAWINGS TO INDICATE DRAINAGE FROM THESE FIXTURES
 DISCHARGING TO THE SANITARY SYSTEM.
  
 B) PLEASE PROVIDE A COMPLETE GREASE WASTE RISER DRAWING
 THAT INCLUDES THE GW PIPE FROM THE 8TH FLOOR INTO THE
 INTERCEPTOR AND THE OUTLET PIPE POINT OF CONNECTION TO
 THE SANITARY. PLEASE INCLUDE CLEANOUT LOCATIONS. THE
 CURRENT PLANS DO NOT SHOW THE PIPE CONTINUATION THROUGH
 THE FLOORS TO THE INTERCEPTOR LOCATION- SEC. 1003.3.1.
  
 C) PLEASE PROVIDE GREASE WASTE CALCULATIONS AND AN
 EQUIPMENT SCHEDULE FOR THE INTERCEPTOR- SEC. 1003.3.5.
  
 2) 2ND REVIEW- SHEET P.219: THE RESPONSE NARRATIVE
 PROVIDES A LAUNDRY LIST OF CHANGES THAT INCLUDE MANY
 ITEMS NOT RELATED TO THE PLUMBING PLANS SUCH AS TENNIS
 COURT DOORS, EXTERIOR TERRACE MODIFICATIONS AND
 LIGHTING ETC. I WAS ABLE TO RESEARCH AND FIND SOME OF
 THE REQUIRED PLUMBING DRAWINGS FOR THE RELOCATED 8TH
 FLOOR BATHS AND THE HOTEL ROOM MODIFICATIONS, HOWEVER I
 WAS NOT ABLE TO LOCATE REVISED RISER DRAWINGS FOR THE
 RELOCATED POOL EQUIPMENT ROOM SHOWN ON SHEETS P.107A &
 P.509. PLEASE NOTE THAT POOL WASTE WATER SHALL NOT
 DRAIN INTO THE SANITARY AND THERE ARE SEVERAL FLOOR
 DRAINS IN PROXIMITY OF EQUIPMENT. POOL WASTE WATER
 SHALL BE DECHLORINATED AND DRAIN TO THE STORM SYSTEM IN
 ACCORDANCE WITH SEC. 90-205(1) WPB CODE OF ORDINANCES.
 PLEASE PROVIDE THE REQUIRED DRAWINGS AND DETAILS
 SHOWING CODE COMPLIANT DISPOSAL.
  
 4) 2ND REVIEW- SHEETS P.219, P.220, P.221, P.222,
 P.223, P.224: PROVIDE REVISED ENLARGED AND DETAILED
 ARCHITECTURAL DRAWINGS FOR THE ACCESSIBLE BATHROOMS-
 SEC. 213.2 & SECS. 603.1- 610.1 FBC ACC. THE NARRATIVE
 REFERS TO SHEETS A0.202 & A0.203 WHICH WERE NOT
 PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-08-31 Cont ID  
Sent By ccole Date 2022-08-31 Time 10:27 Rev Time 0.00
Received By ccole Date 2022-08-31 Time 07:14 Sent To  
Notes
2022-08-31 10:27:551ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22080569
 8/30/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P.219: THE SUBMITTED NARRATIVE OF PLUMBING
 CHANGES PROVIDES VERY GENERAL INFORMATION. PLEASE
 PROVIDE A DETAILED NARRATIVE THAT ITEMIZES ALL
 REVISIONS MADE TO THE PLAN FROM REV-2 (12/14/2020) TO
 REV-11 (08/05/2020). PLEASE UPDATE THE REVISION
 SCHEDULE ON THE PLAN WITH DELTA SYMBOLS AND DATES THAT
 CORRESPOND WITH THE DESIGN CHANGES- SEC. 107.2.1 WPB.
 COMPARISONS OF THE APPROVED PLAN (09/15/2021) AND THE
 SUBMITTED REVISED PLANS SHOW CHANGES THAT INCLUDE:
 A) REMOVAL OF THE MEN'S AND WOMEN'S GANG BATHROOMS,
 POOL EQUIPMENT ROOM, & SERVICE BAR.
 B) MULTIPLE CHANGES TO BATHROOM LAYOUTS AND PLUMBING
 FIXTURES IN THE ROOMS INCLUDING A NEW ADA COMPLIANT
 ROOM 1.3.
 C) A NEW KITCHEN WHICH WILL REQUIRE A GREASE
 INTERCEPTOR AND A GREASE WASTE LINE- SEC. 1003.3.1 FBC
 P.
 PLEASE REVISE ALL PLUMBING AND ARCHITECTURAL PLANS THAT
 ARE AFFECTED BY THE CHANGES IN DESIGN.
  
 2) P.219: SUBMIT REVISED SHEET P.509 WHICH IS CALLED
 OUT IN THE NOTE AT THE KITCHEN- SEC. 107.2.1 WPB.
  
 3) P.219, P.220, P.221, P.222, P.223, P.224: CHANGES TO
 ACCESSIBLE BATHROOM FIXTURE LAYOUTS, PLUMBING PIPING
 LAYOUTS AND RISERS ARE INDICATED. PLEASE SUBMIT THE
 REVISED SHEETS CALLED OUT ON THE PLANS- P.701A, &
 P.703- SEC. 107.2.1 WPB. ALTERNATIVELY, IF NEW SHEETS
 HAVE BEEN PROVIDED PLEASE REVISE THE TARGET NOTES TO
 MATCH.
  
 4) P.219, P.220, P.221, P.222, P.223, P.224: PROVIDE
 REVISED ENLARGED AND DETAILED ARCHITECTURAL DRAWINGS
 FOR THE ACCESSIBLE BATHROOMS- SEC. 213.2 & SECS. 603.1-
 610.1 FBC ACC.
  
 5) P.219: REFERENCE NOTE FOR ENLARGED UNIT PIPING
 LAYOUT NOT PROVIDED IN ADA ROOM 1.3A- SEC. 107.2.1 WPB.
  
 6) P.220: REFERENCE NOTES FOR ENLARGED UNIT PIPING
 LAYOUT NOT PROVIDED IN SUITE 4KL, AND ROOM 1.3A- SEC.
 107.2.1 WPB.
  
 7) P.221 & P.222: REFERENCE NOTES FOR ENLARGED UNIT
 PIPING LAYOUT NOT PROVIDED IN MANY OF THE ROOMS. PLEASE
 REVIEW AND REVISE- SEC. 107.2.1 WPB.
  
 8) P.501 & P.503A: PLEASE SUBMIT THE REVISED SHEETS
 CALLED OUT ON THE PLANS- P.701A, & P.703- SEC. 107.2.1
 WPB. ALTERNATIVELY, IF NEW SHEETS HAVE BEEN PROVIDED,
 PLEASE REVISE THE TARGET NOTES TO MATCH.
  
 9) P.512: THE NARRATIVE INDICATES NEW BATHROOMS AT THE
 12TH FLOOR. PLEASE PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P.
 INDICATE THE REQUIRED AND PROVIDED NUMBER OF FIXTURES
 BASED ON THE TABLE.
  
 10) P.512: THE NARRATIVE DOES NOT PROVIDE ANY
 INFORMATION ABOUT THE NEW LOCKER ROOM BATHS- SEC.
 107.2.1 WPB. PLEASE PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P.
 INDICATE THE REQUIRED AND PROVIDED NUMBER OF FIXTURES
 BASED ON THE TABLE.
  
 11) P.512: PROVIDE REVISED THE MAIN SANITARY RISER
 DRAWINGS AND DFU CALCULARTIONS BASED ON THE ADDED
 PLUMBING FIXTURES IN THE TOWER- SEC. 107.3.5.1.3 WPB,
 AND SEC. 710.1 FBC P.
  
 12) P.512: PROVIDE REVISED ENLARGED AND DETAILED
 ARCHITECTURAL DRAWINGS FOR THE ACCESSIBLE BATHROOMS ON
 THE 7TH AND 12TH FLOORS SEC. 213.2 & SECS. 603.1- 610.1
 FBC ACC.
  
 13) P.512: SHOW THE SOURCES OF THE HOT WATER AND
 CLARIFY IF NEW WATER HEATERS HAVE BEEN SELECTED AS PART
 OF THE REVISION TO SUPPLY THE FIXTURES- SEC. 607.1 FBC
 P. PLEASE PROVIDE WATER HEATER EQUIPMENT SCHEDULES IF
 APPLICABLE- SEC. 107.2.1 WPB.
  
 14) P.512: THE 1/2-INCH FIXTURE SUPPLY PIPES SUPPLYING
 HOT WATER TO THE LAVATORIES HAVE EXCEEDED THE MAXIMUM 2
 FT. LENGTHS ALLOWABLE PER TABLE C404.5.1 FBC EC. THE
 HWR LINE MUST LOOP DOWN TO THE LAVS, OR POINT OF USE
 WATER HEATERS SHALL BE PROVIDED.
  
 15) P.512: INDICATE HOW TRAP SEAL PROTECTION IS BEING
 PROVIDED FOR THE FLOOR DRAINS- SEC. 1002.4.1 FBC P.
  
 16) P.705A: BT-X & SH-X SHOWN IN THE RISER FOR UNITS
 1.3A- 4.2A NEED TO BE VENTED PER SEC. 901.2.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-05-01 Cont ID  
Sent By medwards Date 2023-05-01 Time 08:16 Rev Time 0.00
Received By medwards Date 2023-05-01 Time 08:16 Sent To  
Notes
2023-04-28 09:42:38BUILDING PLANS PASSED.
2023-04-21 13:20:27PLUMBING PLANS PASSED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-03-10 Cont ID  
Sent By rmcdouga Date 2023-03-10 Time 15:11 Rev Time 0.00
Received By rmcdouga Date 2023-03-07 Time 13:04 Sent To  
Notes
2023-03-10 15:12:41THE ENGINEER, CHAD WISLER P.E., SELF-CERIFIED HIS
 DIGITAL SIGNATURE ON THE MECHANICAL AND STRUCTURAL
 PLANS. THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 REQUIRES THE ENGINEER'S DIGITAL SIGNATURE TO BE
 CERTIFIED BY AN APPROVED THIRD PARTY CERTIFICATION
 AGENCY.
  
2023-03-07 13:18:07ELECTRICAL PLANS SIGNATURES ARE APPROVED JLEAHY
2023-02-24 15:23:06MECHANICAL DIGITAL SIGNATURES APPROVED ME
2023-02-24 12:43:11PLUMBING (P) PLAN SIGS APPROVED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-03 Cont ID  
Sent By rmcdouga Date 2022-10-03 Time 08:47 Rev Time 0.00
Received By rmcdouga Date 2022-10-03 Time 08:47 Sent To  
Notes
2022-10-03 09:31:19THE ENGINEER, CHAD WISLER P.E., SELF-CERIFIED HIS
 DIGITAL SIGNATURE ON THE MECHANICAL AND PLUMBING PLANS.
 THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS REQUIRES
 THE ENGINEER'S DIGITAL SIGNATURE TO BE CERTIFIED BY AN
 APPROVED THIRD PARTY CERTIFICATION AGENCY.
2022-08-31 15:32:18MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 1 Status P Date 2022-11-07 Cont ID  
Sent By ckimmerl Date 2022-11-07 Time 12:37 Rev Time 0.00
Received By ckimmerl Date 2022-11-07 Time 12:37 Sent To  
Notes
***NONE***