| Plan Review Stops For Permit 22080414 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-05-02 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-05-02 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2023-05-02 16:48:51 | DEFERRAL ON PLAN PAGE A-201: SUBMIT WINDOW AND DOOR | | | PRODUCT APPROVALS FOR REVIEW AND APPROVAL PRIOR TO | | | INSTALLATION. CT | | | APPROVAL OF THE BUILDING REVIEW IS PENDING APPROVAL OF | | | THE SIGNATURE REVIEW, SEE COMMENTS UNDER SIGNATURE | | | REVIEW. CT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-03-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-03-03 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-03-03 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2023-03-03 14:22:52 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 3RD REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1.PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA | | | FOR THE PROPOSED WINDOWS AND DOORS TO BE INSTALLED. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | NOTE: NOA?S DO NOT HAVE COVER SHEETS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-12-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-12-06 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-12-06 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2022-12-06 16:16:51 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: COMMENTS FROM 1ST REVIEW HAVE NOT BEEN | | | ADDRESSED. SEE BELOW, | | | | | | 1. PROVIDE A SITE PLAN.... | | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | | AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE | | | AND INCLUDED BOUNDARY LINE SURVEY. | | | | | | 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | FBC R401.3 SITE DRAINAGE | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. | | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | | INCHES WITHIN THE FIRST 10 FEET. | | | | | | 3.PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA | | | FOR THE PROPOSED WINDOWS AND DOORS TO BE INSTALLED. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | NOTE: NOA?S DO NOT HAVE COVER SHEETS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 4. PROVIDE THE ICC-ES REPORT FOR THE SPRAY FOAM | | | INSULATION. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-31 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-31 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2022-08-31 16:13:48 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: VALUE HAS BEEN INCREASED TO $38,472 PER THE ICC | | | BLDG. VALUATION DATA. | | | | | | 1. PROVIDE A SITE PLAN.... | | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | | AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE | | | AND INCLUDED BOUNDARY LINE SURVEY. | | | | | | 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | FBC R401.3 SITE DRAINAGE | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. | | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | | INCHES WITHIN THE FIRST 10 FEET. | | | | | | 3.PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA | | | FOR THE PROPOSED WINDOWS AND DOORS TO BE INSTALLED. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | NOTE: NOA?S DO NOT HAVE COVER SHEETS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 4. PROVIDE THE ICC-ES REPORT FOR THE SPRAY FOAM | | | INSULATION. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2023-04-19 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-04-19 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-04-19 |
Time |
10:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-02-15 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-02-15 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2023-02-15 12:14:26 | ELECTRIC REVIEW FAILED | | | | | | 1) IT APPEARS THE ELECTRICAL RISER PROVIDED DOES NOT | | | MATCH THE ELECTRICAL RISER DIAGRAM ON FILE FROM A | | | PREVIOUS ELECTRICAL UPGRADE DONE IN 2012. PLEASE | | | PROVIDE A CORRECT ELECTRIC RISER TO COMPLY WITH CODES | | | CITED BELOW. | | | . | | | NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE | | | AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER | | | DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF | | | THE FEEDERS. | | | | | | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-11-29 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-11-29 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-11-29 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2022-11-29 08:33:20 | PREVIOUS COMMENTS NOT ADDRESSED |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-08-29 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-08-29 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2022-08-29 13:20:47 | ELECTRIC REVIEW FAILED | | | 1) SEE SIGNATURE REVIEW | | | 2) PLEASE PROVIDE ELECTRICAL PLANS AS APPLICABLE. FBC | | | 107.2 | | | | | | TO ENSURE CLARITY, ELECTRIC WORK SUBMITTALS SHOULD | | | INCLUDE ELECTRIC DRAWINGS DETAILING EXISTING | | | CONDITIONS, ALL PROPOSED CHANGES AND A DETAILED WORK | | | SCOPE. FLOOR PLANS, SITE PLANS, ELECTRIC RISER | | | DIAGRAMS, LOAD CALCULATIONS, EQUIPMENT SIZES AND | | | SPECIFICATIONS, CONDUCTOR SIZES AND TYPE AND PRODUCT | | | SPECIFICATIONS OR ANY RELEVANT DETAILS, AS APPLICABLE, | | | MAY BE REQUIRED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-05-02 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-04-12 |
Time |
10:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-03-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-03-03 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-02-09 |
Time |
07:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-12-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-12-06 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-11-06 |
Time |
07:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-31 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-10 |
Time |
07:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-31 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-31 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2022-08-31 14:23:24 | IMPACT FEES | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-04-24 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-04-24 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2023-04-24 13:14:10 | PLEASE UNDERSTAND THAT THE ENERGY CALCULATIONS | | | SUBMITTED DOES NOT HAV ETHE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. PLEASE SUBMIT THE MECHANICAL EQUIPMENT | | | SIZING CALCULATIONS AND MECHANICAL DRAWING ASKED FOR 5 | | | CYCLES AGO. | | | | | | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | ALONG WITH A MECHANICAL DRAWING SHOWING THE MINI-SPLIT | | | LOCATION AND CONDENSING UNIT TIE DOWN. FEC R403.7 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2023-02-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-14 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-14 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2023-02-14 14:00:00 | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | THAT HAVE BEEN REQUESTED IN PREVIOUS REVIEWS FOR THIS | | | PROJECT. FEC R403.7 ALSO PROVIDE A MECHANICAL DRAWIG | | | THAT SHOWS THE ENTIRE MECHANICAL DESIGN FOR THIS | | | PROJECT. FBC 107.3.5 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-16 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-16 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2022-11-16 11:17:27 | SEE ORIGINAL REVIEW COMMENT BELOW: | | | | | | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | ALONG WITH A MECHANICAL DRAWING SHOWING THE MINI-SPLIT | | | LOCATION AND CONDENSING UNIT TIE DOWN. FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-08-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-19 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-19 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2022-08-19 10:38:56 | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | ALONG WITH A MECHANICAL DRAWING SHOWING THE MINI-SPLIT | | | LOCATION AND CONDENSING UNIT TIE DOWN. FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2022-08-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-18 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-17 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-31 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-31 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2022-08-31 16:09:04 | PROVISO ON PLAN PAGE S-101: ROOFING SHALL BE BY A | | | SEPERATE PERMIT. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-05-02 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-05-02 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2023-05-02 16:46:56 | 4TH SIGNATURE REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: ALL PLAN PAGES EXCEPT PG. A-201 (VALID DIGITAL | | | SIGNATURE OF KELLY YATES AIA) | | | | | | 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A | | | VALID DIGITAL SIGNATURE. | | | A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE | | | IS NOT CONSIDERED A VALID DIGITAL SIGNATURE. | | | | | | 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S. | | | 668.003 (3); | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS) | | | F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-02-15 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-02-15 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2023-02-15 12:20:58 | SIGNATURE REVIEW FAILED | | | | | | 1) SHEETS S101 S201 AND S202 DO NOT DETAIL THE REQUIRED | | | DIGITAL SIGNATURE FOR THE EOR/AOR AS REQUIRED. PLEASE | | | CORRECT AS NOTED BELOW. | | | | | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | DIGITALLY SEALED AND SIGNED. | | | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-12-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-12-06 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-12-06 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2022-12-06 16:14:58 | 2ND SIGNATURE REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: PLAN PAGES S-101, S-201, S-202 | | | | | | DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A | | | VALID DIGITAL SIGNATURE. | | | A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE | | | IS NOT CONSIDERED A VALID DIGITAL SIGNATURE. | | | | | | SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S. | | | 668.003 (3); | | | FBC 107.2.1 ???ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. (SEE ALSO SECTION 107.3.5). | | | F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS) | | | F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-08-29 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-08-29 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2022-08-29 13:21:29 | SIGNATURE REVIEW FAILED | | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | DIGITALLY SEALED AND SIGNED. | | | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2023-04-24 |
|
|
Cont ID |
|
| Sent By |
VBroglia |
Date |
2023-04-24 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-04-24 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-02-22 |
|
|
Cont ID |
|
| Sent By |
VBroglia |
Date |
2023-02-22 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-02-22 |
Time |
13:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-12-06 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2022-12-06 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2022-12-06 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2022-12-06 15:26:12 | 12/6/22- FAILED- INDICATE ON THE SURVEY WHERE THE | | | ADDITION IS GOING IN RELATIONSHIP TO THE PROPERTY LINE. | | | | | | ANGELLA VANN | | | 561-822-1441 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-08-15 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-08-15 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-08-15 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2022-08-15 16:29:00 | 08/15/22 FAILED - NEED TO SHOW THE PROPOSED EDITION ON | | | A SURVEY OF THE PROPERTY SO I CAN DETERMINE IF THE | | | PROJECT MEETS SETBACK REQUIREMENTS. | | | | | | ALEXANDER FOWLKES | | | [email protected] | | | 5618221431 |
|
|