Plan Review Details - Permit 22080397
Plan Review Stops For Permit 22080397
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-06 Cont ID  
Sent By rmcdouga Date 2022-10-06 Time 10:23 Rev Time 0.00
Received By rmcdouga Date 2022-10-06 Time 08:16 Sent To  
Notes
2022-10-06 10:00:47PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE ARE SEVERAL MISTAKES ON SHEET IF. PLEASE
 CORRECT.
 A) THERE ARE A COUPLE OF REFERENCES TO THE 2020 FRBC.
 NOT SURE WHAT CODE THIS IS. THE RESIDENTIAL CODE DOES
 NOT APPLY TO CONDOMINIUMS. THE 2020 FBC EXISTING
 BUILDING AND 2020 FBC BUILDING ARE THE CODES THAT APPLY
 TO THIS PROJECT. FBC 107.2.1
 B) THE LIFE SAFETY NOTES SPECIFY TYPEV CONSTRUCTION.
 THIS IS A HIGH RISE BUILDING AND WOULD BE A MINIMUM OF
 TYPE II CONSTRUCTION. FBC CHAPTER 5
 C) THE TYPE OF OCCUPANCY FOR THIS BUILDING IS R-2. FBC
 310
  
 2) THERE ARE SEVERAL MISTAKES ON SHEET A-005. PLEASE
 CORRECT.
 A) UNDER STRUCTURAL NOTES THE ULTIMATE WIND SPEED IS
 170 MPH AND THE NOMINAL WIND SPEED IS 132 MPH. FBC
 1609.3
 B) THIS BUILDING IS NOT ALLOWED TO HAVE STRUCTURAL
 TIMBERS. FBC 601
 C) THE TYPICAL SUSPENDED CEILING DETAIL DOESN'T APPLY
 SINCE THERE ARE NO TIMBER TRUSSES IN THIS BUILDING. FBC
 601
  
 3) SUBMIT THE FOLLOWING INFORMATION FOR THE NEW
 FLOORING.
 A) TYPE OF PROPOSED (HARD) FINISH FLOOR COVERING (TILE,
 LAMINATE, WOOD, MARBLE, ETC.).
 B) DESCRIPTION OF EXISTING SITE CONDITIONS: THICKNESS
 OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW (EXPOSED
 CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL).
 C) PROPOSED ACOUSTICAL INSULATION UNDERLAYMENT.
 D) TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 E) TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 - SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE
 SOUND INSULATION INCLUDING FLAME SPREAD AND SMOKE
 DEVELOPED FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
 - FBC 603.1 FLAME SPREAD AND SMOKE DEVELOPED - ASTM E
 84-09
 - FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 - WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
 - FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 -
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4) THE VALUE FOR THIS PROJECT APPEARS TO BE TOO LOW FOR
 THE PROPOSED WORK. SUBMIT AN ITEMIZED COST BREAKDOWN.
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF FBC 109.3 BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-03 Cont ID  
Sent By fgiaquin Date 2022-10-03 Time 23:36 Rev Time 0.00
Received By fgiaquin Date 2022-10-03 Time 22:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-09-14 Cont ID  
Sent By pleduc Date 2022-09-14 Time   Rev Time 0.00
Received By pleduc Date 2022-09-14 Time 13:40 Sent To  
Notes
2022-09-14 13:48:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF "DEMO EXISTING FLLOR AND
 ADD NEW ONE", HOWEVER, THERE IS NO INDICATION OF A SPEC
 SHEET NOR A PRODUCT NAME FOR THE ACTUAL PROPOSED
 FLOORING.
  
 FINISHED FLOORING CAN BE MANUFACTURED AROUND THE WORLD
 AND NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FINISHED FLOORING COULD HAVE DIFFERENT MEANINGS AND IF
 NOT CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE
 VINYL/LAMINATE ETC.
  
 PLEASE PROVIDE THE TILE TYPE I.E. CERAMIC, MARBLE,
 TERRACOTTA, STONE WHICH WOULD NOT REQUIRE A SPEC SHEET
 NOR A FIRE BEHAVIOR RATING.
  
 FOR OTHER TYPE OF TILE PRODUCT TYPE I.E. VINYL, VINYL
 PLANKS, LUXURY VINYL PLANKS, LAMINTE, CORK, WOOD PLEASE
 PROVIDE THE MANUFACTURE PRODUCT FLAME SPREAD/PRODUCT
 SAFETY TEST SHEET
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FINSIHED
 FLOORING TYPE AND/OR NAME AND THE PRODUCT SPEC SHEETS
 OF THE PROPOSED FINISHED
 FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2) THERE IS AN INDICATION OF "NO FIRE SPRINKLER WORK"
 HOEVER, THERE ARE INDICATIONS OF WALLS BEING REMOVED
 AND RECONSTRUCTION.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 SHOULD FIRE SPRINKLER MODIFICATION NOT BE REQUIRED A
 LETTER FROM THE CONTRACTOR SHALL BE PROVIDED TO THE
 FIRE INSPECTION ON INSPECTION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLDGEMENT
  
  
 3) THE EXISTING FIRE ALARM SYSTEM DEVICES SHALL BE
 MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE DEMO AND
 RECONSTRUCTION PERIODS.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER AND FIR ALARM
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED FIRE SPRINKLER AND FIRE ALARM CONTRACTORS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLDGEMENT
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-06 Cont ID  
Sent By rmcdouga Date 2022-10-06 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2022-09-08 Time 08:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-10-06 Cont ID  
Sent By rmcdouga Date 2022-10-06 Time 10:23 Rev Time 0.00
Received By rmcdouga Date 2022-10-06 Time 10:23 Sent To  
Notes
***NONE***