| 2022-10-24 14:43:39 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22080363 |
| | ADD: 330 CLEMATIS ST. # 116 |
| | CONT: BLUE WATER VENTURES OF PALM BEACH |
| | TEL: 561-339-6128 |
| | E-MAIL: |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. OCT. 24TG/2022 |
| | ACTION: DENIED |
| | 1) SHEET A-3 DETAIL H1: |
| | 1A) THIS DETAIL INDICATES THE STAIR RISER TO BE 7 3/8 |
| | INCHES IN HEIGHT. PLEASE REFER TO THE 2020 FBC-BUILDING |
| | CODE SECTION 1011.5.2 RISER HEIGHT MAXIMUM 7 INCHES. |
| | |
| | |
| | 1B) THE SUBMITTED PLAN DOES NOT PROVIDE WHAT MATERIALS |
| | THE STAIR STRINGERS ARE MADE OF, NOR HOW MANY STRINGERS |
| | THERE ARE, DETAIL A8 DOES NOT PROVIDE THE WIDTH OF THE |
| | STAIRS FBC-B 1011.2 & 1011.7. |
| | |
| | 1C) THE SUBMITTED PLANS DOES NOT PROVIDE THE LIVE LOAD |
| | DESIGN IN ACCORDANCE WITH TABLE 1607.1 (30). |
| | |
| | 1D) MISSING HANDRAIL & GUARDRAIL LOADING: |
| | FBC-B 1607.8.1, |
| | FBC-B 1607.8.1.1 CONCENTRATED LOAD |
| | FBC-B 1607.8.1.2 INTERMEDIATE RAILS |
| | |
| | 1E) DETAIL H1 MISSING THE DIMENSION BETWEEN GUARDRAIL |
| | CABLES TO BE IN COMPLIANCE WITH FBC-B SECTION 1015.4. |
| | |
| | 1F) DETAIL H1 THE SIDE ELEVATION OF THE STAIRS DOES NOT |
| | PROVIDE THE TRIANGULAR AREA FORMED BY THE RISER, TREAD |
| | AND BOTTOM GUARDRAIL CABLE, SHALL NOT ALLOW A 6-INCH |
| | SPHERE TO PASS THROUGH. |
| | |
| | 1G) PLEASE NOTE THIS STAIR IS THE ONLY MEANS OF EGRESS |
| | FROM THE MEZZANINE. THE DETAIL H1 SHOWS A COPIER AND |
| | LINEAR FILE UNDER THE STAIR. PLEASE SHOW COMPLIANCE |
| | WITH 2020 FBC-BUILDING CODE SECTION 1011.7.3. |
| | |
| | 1H) DETAIL A1 SHOWS THE BREAK ROOM WITH A MICROWAVE IN |
| | THE UPPER CABINETS. THIS CONFIGURATION DOES NOT COMPLY |
| | WITH 2020 FBC-ACCESSIBILITY CODE FOR: |
| | 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1 |
| | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE |
| | REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH |
| | REACH. |
| | |
| | 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL |
| | BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL |
| | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| | MAXIMUM. |
| | |
| | 1I) ) DETAIL A1 SHOWS THE BREAK ROOM DOES NOT DECLARE |
| | THE HEIGHT OF THE SINK AND COUNTERTOP. 606 LAVATORIES |
| | AND SINKS> 2020 FBC-ACCESSIBILITY CODE SECTION 606.3 |
| | HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. WORK |
| | SURFACES, 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL |
| | BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | |
| | 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |