Plan Review Details - Permit 22080288
Plan Review Stops For Permit 22080288
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2022-10-26 Cont ID  
Sent By rmcphers Date 2022-10-26 Time 11:12 Rev Time 0.00
Received By rmcphers Date 2022-10-26 Time 11:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-12-01 Cont ID  
Sent By rmcphers Date 2022-12-01 Time 08:43 Rev Time 0.00
Received By rmcphers Date 2022-12-01 Time 08:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-10-26 Cont ID  
Sent By rmcphers Date 2022-10-26 Time 11:12 Rev Time 0.00
Received By rmcphers Date 2022-10-26 Time 11:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-01 Cont ID  
Sent By mpeterso Date 2022-12-01 Time 15:25 Rev Time 0.00
Received By mpeterso Date 2022-12-01 Time 14:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-11 Cont ID  
Sent By mpeterso Date 2022-10-11 Time 15:16 Rev Time 0.00
Received By mpeterso Date 2022-10-11 Time 15:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-11-16 Cont ID  
Sent By cwalker Date 2022-11-16 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-11-16 10:38:11FIRE PROVISO COMMENTS:
  
 (1) THE TENANT STORAGE SHALL MAINTAIN 18 INCHES
 CLEARANCE BELOW FIRE SPRINKLER HEADS.
  
 (2) ANY WORK ON ANY LIFE SAFETY SYSTEM (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PERFORMED BY PROPERLY
 LICENSED CONTRACTORS UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS.
  
 (3) PORTABLE FIRE EXTINGUISHERS SHALL BE OF SIZE AND
 TYPE OF THE HAZARD BEING PROTECTED AND LOCATED A
 MAXIMUM DISTANCE OF 75 FEET TRAVEL DISTANCE.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-06 Cont ID  
Sent By cwalker Date 2022-09-06 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-09-06 12:55:01FIRE PROVISO COMMENTS:
  
 (1) THE TENANT STORAGE SHALL MAINTAIN 18? CLEARANCE
 BELOW FIRE SPRINKLER HEADS.
  
 (2) ANY WORK ON ANY LIFE SAFETY SYSTEM (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PERFORMED BY PROPERLY
 LICENSED CONTRACTORS UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS.
  
 (3) FIRE EXTINGUISHERS SHALL BE OF SIZE AND TYPE OF THE
 HAZARD BEING PROTECTED AND LOCATED A MAXIMUM DISTANCE
 OF 75 FEET.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-30 Cont ID  
Sent By medwards Date 2023-01-30 Time 10:32 Rev Time 0.00
Received By medwards Date 2023-01-09 Time 16:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-07 Cont ID  
Sent By cpuell Date 2022-12-07 Time 10:40 Rev Time 0.00
Received By cpuell Date 2022-11-15 Time 07:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-26 Cont ID  
Sent By rmcphers Date 2022-10-26 Time 11:12 Rev Time 0.00
Received By rmcphers Date 2022-09-01 Time 10:47 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-10-26 Cont ID  
Sent By rmcphers Date 2022-10-26 Time 11:12 Rev Time 0.00
Received By rmcphers Date 2022-10-26 Time 11:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-01-30 Cont ID  
Sent By medwards Date 2023-01-30 Time 10:31 Rev Time 0.00
Received By medwards Date 2023-01-30 Time 10:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-11-30 Cont ID  
Sent By medwards Date 2022-11-30 Time 14:36 Rev Time 0.00
Received By medwards Date 2022-11-30 Time 14:36 Sent To  
Notes
2022-11-30 14:36:342ND REVIEW FMC
 PERMIT: 22080288
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISE THE MECHANICAL DRAWING TO SHOW THE OUTDOOR
 AIR DUCT. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-09-21 Cont ID  
Sent By medwards Date 2022-09-21 Time 05:27 Rev Time 0.00
Received By medwards Date 2022-09-21 Time 05:27 Sent To  
Notes
2022-09-21 05:27:551ST REVIEW FMC
 PERMIT: 22080288
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE VALUE OF THIS PROJECT ON THE
 APPLICATION.
  
 2) SHEET C-1 LISTS THIS PROJECT AS S-1/WAREHOUSE. SHEET
 1.1AOF 5 LISTS THIS PROJECT AS WAREHOUSE. SHEET 3.0M IS
 CALLING THIS SPACE A STRETCH ROOM. PLEASE PROVIDE
 CORRECTED INFORMATION FOR THIS REVIEWER TO START THE
 REVIEW. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-01-30 Cont ID  
Sent By medwards Date 2023-01-30 Time 10:31 Rev Time 0.00
Received By medwards Date 2023-01-30 Time 10:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-01 Cont ID  
Sent By rmcphers Date 2022-12-01 Time 08:53 Rev Time 0.00
Received By rmcphers Date 2022-12-01 Time 08:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-09-21 Cont ID  
Sent By medwards Date 2022-09-21 Time 05:28 Rev Time 0.00
Received By medwards Date 2022-09-21 Time 05:28 Sent To  
Notes
2022-09-21 05:30:20THE DIGITAL SIGNATURE IS INVALID AS THE DOCUMENT HAS
 BEEN ALTERED AFTER SIGNATURE. PLEASE PROVIDE DIGITALLY
 SIGNED DOCUMENTS THAT ARE NOT ALTERED AFTER SIGNATURE
 HAS BEEN ADDED. FS 471/481
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-12-07 Cont ID  
Sent By jroach Date 2022-12-07 Time 08:44 Rev Time 0.00
Received By jroach Date 2022-12-07 Time 08:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-10-11 Cont ID  
Sent By jroach Date 2022-10-11 Time 11:38 Rev Time 0.00
Received By jroach Date 2022-10-11 Time 11:23 Sent To  
Notes
2022-10-11 11:38:37ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 10.11.2022
 PERMIT NO.: 22080288
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE CLARIFY THE LOCATION OF THE PROPOSED
 IMPROVEMENTS. THE COVER SHEET APPEARS TO SHOW THE
 IMPROVEMENTS OCCURRING IN RETAIL BAY 3039, BUT THE
 TITLE BLOCK OF THE PLANS INDICATES 3139.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ??? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  