| 2023-01-24 16:03:59 | RESIDENTIAL (R3) FOURTH BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22080253 |
| | 8403 IRONHORSE CT. |
| | |
| | NOTE: |
| | NEED TO ADDRESS THE SIGNATURE REVIEW ALSO. SEE COMENT |
| | AT THE BOTTOM OF THIS PAGE. |
| | |
| | |
| | 2- ACCORDING SHUTTERS: |
| | |
| | PREVIOUS COMMENT: |
| | A) SHUTTERS INSTALLATION SCHEDULE SPECIFY CONCRETE AS |
| | THE SUBSTRATE WHERE SHUTTERS ARE GOING TO BE INSTALLED |
| | (TOP AND BOTTOM). TYPICALLY THE BOTTOM OF WINDOW |
| | OPENINGS IS CONCRETE BLOCK. REVISE INSTALLATION |
| | SCHEDULE USING THE ANCHOR FOR CONCRETE BLOCK SUBSTRATE |
| | AT THE BOTTOM OR PROVIDE PROOF SHOWING BOTTOM OF |
| | OPENINGS HAS POURED CONCRETE WITH THE STRENGTH |
| | SPECIFIED ON ANCHOR SCHEDULE OF PRODUCT APPROVAL |
| | SUBMITTED. |
| | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | NOTE: |
| | ACCORDION SHUTTERS SCHEDULE UPLOADED TO PROJECTDOX ON |
| | 1/6/2023 IS MISMATCHING THE ACCORDIGN SHUTTERS AND THE |
| | ARMOR SCREEN SHUTTERS INFORMATION. THE TOP FORM OF THE |
| | THIS SHUTTER SCHEDULE IS SPECIFYING FOLDING SHUTTER |
| | CORPORATION SHUTTERS BUT THE ACTUAL INSTALLATION |
| | SCHEDULE BELOW IS SHOWING THE 8 OPENINGS TO BE COVERED |
| | WITH THE ARMOR SCREEN SHUTTERS NOT THE 18 OPENINGS WITH |
| | ACCORDING SHUTTERS. |
| | THIS IS WHY THERE IS SO MUCH CONFUSION. |
| | THE ACTUAL REVISED ACCORDION SHUTTERS INSTALLATION |
| | SCHEDULE WAS NEVER UPLOADED. IN ORDER TO AVOID MORE |
| | CONFLICTS AND DEALYS, PLEASE UPLOAD THE REVISED |
| | ACCORDING SHUTTERS INSTALLATION SCHEDULE ADDRESING THE |
| | COMMENTS. |
| | |
| | PREVIOUS COMMENT: |
| | B) REVISE SHUTTER GLASS SEPARATION SPECIFIED ON SHUTTER |
| | INSTALLATION SCHEDULE FOR OPENINGS WITH A SHUTTER SPAN |
| | LONGER THAN 99 INCHES. SEE SHEET 13 OF 13 OF SHUTTERS |
| | PRODUCT APPROVAL AND REVISE AS REQUIRED. NEED 3-1/2 |
| | INCH GLASS SEPARATION. |
| | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | NOTE: |
| | ACCORDION SHUTTERS SCHEDULE UPLOADED TO PROJECTDOX ON |
| | 1/6/2023 IS MISMATCHING THE ACCORDIGN SHUTTERS AND THE |
| | ARMOR SCREEN SHUTTERS INFORMATION. THE TOP FORM OF THE |
| | THIS SHUTTER SCHEDULE IS SPECIFYING FOLDING SHUTTER |
| | CORPORATION SHUTTERS BUT THE ACTUAL INSTALLATION |
| | SCHEDULE BELOW IS SHOWING THE 8 OPENINGS TO BE COVERED |
| | WITH THE ARMOR SCREEN SHUTTERS NOT THE 18 OPENINGS WITH |
| | ACCORDING SHUTTERS. |
| | THIS IS WHY THERE IS SO MUCH CONFUSION. |
| | THE ACTUAL REVISED ACCORDION SHUTTERS INSTALLATION |
| | SCHEDULE WAS NEVER UPLOADED. IN ORDER TO AVOID MORE |
| | CONFLICTS AND DEALYS, PLEASE UPLOAD THE REVISED |
| | ACCORDING SHUTTERS INSTALLATION SCHEDULE ADDRESING THE |
| | COMMENTS. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | SIGNATURE REVIEW: |
| | |
| | THOMAS J. TWOMEY P.E DWG 1 OF 1 SUBMITTED WITH FLORIDA |
| | PRODUCT APPROVAL FL320-R10 NEEDS ORIGINAL |
| | SEAL/SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. WHEN |
| | SUBMITTING FOR PUBLIC RECORDS. |
| | |
| | NOTE: UPLOAD THIS DRAWING IN THE DRAWINGS FOLDER. |
| | |
| | |
| | |