| 2022-08-31 10:55:27 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22080216 5812 S DIXIE HWY |
| | |
| | 1ST REVIEW |
| | 8/31/2022 |
| | PLUMBING COMMENTS: DENIED |
| | |
| | PROVISO: MANUFACTURER'S SPECIFICATION/INSTALLATION |
| | MANUAL FOR THE FOLLOWING SHALL BE ON SITE PRIOR TO |
| | FINAL INSPECTION: |
| | WATER HEATER |
| | BACKFLOW PREVENTER DEVICES |
| | THERMOSTATIC MIXING VALVES |
| | PLUMBING FIXTURES |
| | |
| | 1. PER WPB CCCM C. III. ALL GENERAL SERVICE |
| | (COMMERCIAL) AND MULTI-FAMILY DWELLINGS WATER USERS |
| | WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION |
| | ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW |
| | ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF |
| | HAZARD POSED BY THE WATER USER. |
| | SPECIFY AND FURNISH A BACKFLOW PREVENTION ASSEMBLY FOR |
| | EACH TENANT SPACE POINT OF ENTRY. PROVIDE A DETAIL. |
| | PLEASE NOTE, A CHECK VALVE IS NOT A COMPLIANT DEVICE. |
| | |
| | SEPARATE BACKFLOW PERMITS ARE REQUIRED TO BE SUBMITTED |
| | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS |
| | APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. |
| | |
| | 2. P-101: PER WPB FBC 107.2.1, CONFIRM ON THE PLAN THAT |
| | WATER SERVICE SHALL CONNECT TO EXISTING BACKFLOW |
| | PREVENTER AT METER; INDICATE TYPE. UP TO DATE |
| | CERTIFICATION FOR THE DEVICE SHALL BE ON SITE FOR FINAL |
| | INSPECTION. WPB CCCM C.III, I-2(A) |
| | |
| | 3. P-102: PER FBC 1210.2.2 AND FBC PL 310.3, WALLS AND |
| | PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND |
| | WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT |
| | SURFACE TO A HEIGHT NOT LESS THAN 4 FEET ABOVE THE |
| | FLOOR. SECTION 1210.2.2 STIPULATES THAT THE MATERIAL BE |
| | "HARD." THE INTENT OF THIS SECTION IS THAT THE |
| | SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS |
| | EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME |
| | ABSORBENT AND THUS, NOT READILY CLEANABLE AND |
| | SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH |
| | HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF |
| | SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS |
| | APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED |
| | PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED |
| | PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL. |
| | |
| | 4. P-101/WATER HEATER DETAIL & RISER DIAGRAM: PER WPB |
| | FBC 107.2.1, FBC PL 606.1 AND 503.1, PROVIDE DEDICATED |
| | SHUT OFF VALVE FOR COLD WATER TO FAUCET AND FOR COLD |
| | WATER TO WATER HEATER. |
| | |
| | 5. P-101/WATER HEATER DETAIL: PER WPB FBC 107.2.1 AND |
| | FBC PL 419.5, PROVIDE AND SPECIFY AN ASSE 1070 |
| | COMPLIANT WATER-TEMPERATURE LIMITING DEVICE. PROVIDE |
| | DETAIL. |
| | |
| | 6. P-101: A HOSE BIB IS SHOWN ON FLOOR PLAN BUT NOT ON |
| | RISER DIAGRAM, PER WPB FBC 107.2.1, CLARIFY AND |
| | RECONCILE. |
| | |
| | 7. P-101: PER FBC PL 606.2, PROVIDE A SHUT-OFF VALVE |
| | FOR THE HOSE BIB. |
| | |
| | 8. PER FBC PL 608.1, HOSE BIB SHALL BE PROVIDED WITH A |
| | HOSE CONNECTION VACUUM BREAKER. |
| | |
| | 9. P-101: PER WPB FBC 107.2.1, PLEASE SPECIFY MATERIAL |
| | FOR NEW 1 INCH UNDERGROUND WATER SERVICE. |
| | |
| | 10. P-101: PER WPB FBC 107.2.1, PLEASE SPECIFY MATERIAL |
| | FOR NEW 1 INCH ABOVE GROUND |
| | WATER SERVICE GOING INTO BUILDING. |
| | |
| | 11. P-101/WATER SERVICE RISER GOING INTO BUILDING: THE |
| | PLANS ARE UNCLEAR AS TO WHETHER THE RISER IS ON THE |
| | EXTERIOR FACE OF THE WALL, THE INTERIOR FACE OF THE |
| | WALL OR INSIDE OF THE WALL. PER WPB FBC 107.2.1, |
| | PROVIDE DETAIL OF RISER; PROVIDE SUPPORTS, SLEEVING, |
| | APPLICABLE PROTECTION OF PIPING, ETC. MAINTAIN |
| | INTEGRITY OF THE WALL. |
| | |
| | 12. P-101: A CHECK VALVE IS SHOWN IN THE CEILING OF |
| | EACH SPACE ON THE RISER DIAGRAM; A SERVICE SHUT-OFF |
| | VALVE IS SHOWN IN THE CEILING ON THE FLOOR PLAN. PER |
| | WPB FBC 107.2.1, PLEASE CLARIFY AND RECONCILE THE |
| | DRAWINGS. PLEASE NOTE THAT A CHECK VALVE IS NOT A |
| | COMPLIANT BACKFLOW PREVENTER DEVICE. |
| | |
| | 13. P-101: PROVIDE SIZE OF SERVICE SHUT-OFF VALVE IN |
| | THE CEILING. PER FBC PL 603.1 AND 606.1(2), THE MINIMUM |
| | SIZE SHALL BE 3/4 INCH. |
| | |
| | 14. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL |
| | BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND |
| | 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS |
| | STATING THE SAME. |
| | |
| | 15. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL |
| | WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| | SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 16. PER WPB FBC 107.2.1, PROVIDE ENERGY EFFICIENCY FOR |
| | WATER HEATER; COMPLY WITH FBC EC TABLE C404.2 |
| | |
| | 17. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL |
| | 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING |
| | LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF |
| | 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE |
| | A MINIMUM SLOPE OF 1/8 INCH PER FOOT." |
| | |
| | 18. PER WPB FBC 107.2.1, PROVIDE PLUMBING FIXTURE |
| | SCHEDULE INDICATING FIXTURE TYPE AND DESCRIPTION (I.E. |
| | WC-WATER CLOSET, ELONGATED FLOOR MOUNTED TANK TYPE 1.28 |
| | GPF, ADA COMPLIANT, OPEN FRONT ELONGATED SEAT). INCLUDE |
| | DFU AND DRAIN SIZE/WATER SUPPLY FU AND CONNECTION SIZE |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | |
| | |