| Plan Review Stops For Permit 22080193 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-10-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-18 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-18 |
Time |
10:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-09-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-09-03 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-09-01 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2022-09-03 10:32:52 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE | | | SURVEY. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. PROVIDE A SITE PLAN.... | | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | | AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE | | | AND INCLUDED BOUNDARY LINE SURVEY. | | | NOTE: IDENTIFY THE LOCATION OF THE NEW ADDITIONS WITH | | | GRAYSCALE OR HASHTAG. | | | | | | 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | FBC R401.3 SITE DRAINAGE | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. | | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | | INCHES WITHIN THE FIRST 10 FEET. | | | | | | 3.SMOKE ALARMS | | | R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314. | | | | | | 4. FILE LABELED "PRODUCT APPROVAL-UNDERLAYMENT" IS THE | | | ICC-ES REPORT FOR THE ICYNENE SPRAY FOAM INSULATION. | | | RE-LABEL FILE. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | NOTICE: ROOFING PROVISO ON PG. S-3: A ROOFING SHALL BE | | | BY A SEPERATE PERMIT. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-10-05 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-10-04 |
Time |
14:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-08-31 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-08-29 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2022-08-31 14:19:54 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NO SMOKE DETECTORS SHOWN. R314 FBC 2020 | | | | | | 2) SERVICE SHOWS 2/0 FOR FEEDERS GOING TO THE PANELS. | | | DOES NOT MEET 310.15 (B)(7)(2) | | | | | | 310.15.(B)(7) | | | FOR A FEEDER RATED 100 THROUGH 400 AMPERES, THE FEEDER | | | CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A | | | ONE-FAMILY | | | DWELLING, OR THE FEEDER CONDUCTORS SUPPLYING THE ENTIRE | | | LOAD ASSOCIATED WITH AN INDIVIDUAL DWELLING UNIT IN A | | | TWO-FAMILY OR | | | MULTIFAMILY DWELLING, SHALL BE PERMITTED TO HAVE AN | | | AMPACITY NOT LESS THAN 83 PERCENT OF THE FEEDER RATING. | | | | | | 3) MASTER BATH OUTLETS MAY BE TO CLOSE TO THE SHOWER | | | AND TUB. 210.8(A)(9) | | | | | | 210.8(A)(9) BATHTUBS OR SHOWER STALLS ? WHERE | | | RECEPTACLES ARE INSTAL?LED WITHIN 1.8 M (6 FT) OF THE | | | OUTSIDE EDGE OF THE | | | BATHTUB OR SHOWER STALL | | | | | | 4) OUTLETS REQUIRED AT THE FRONT AND REAR OF RESIDENCE | | | 210/52(E)(1) | | | | | | FOR A ONE-FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY | | | DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE | | | RECEPTACLE OUTLET | | | READILY ACCESSIBLE FROM GRADE AND NOT MORE THAN 2.0 M | | | (6 1?2 FT) ABOVE GRADE LEVEL SHALL BE INSTALLED AT THE | | | FRONT AND | | | BACK OF THE DWELLING. | | | | | | 5) OUTLETS ARE REQUIRED IN THE GARAGE ONE FOR EACH | | | SPACE. 210.52 | | | | | | IN EACH ATTACHED GARAGE AND IN EACH DETACHED GARAGE | | | WITH ELECTRIC POWER, AT LEAST ONE RECEPTACLE OUTLET | | | SHALL BE | | | INSTALLED IN EACH VEHICLE BAY AND NOT MORE THAN 1.7 M | | | (51?2 FT) ABOVE THE FLOOR. | | | | | | 6) BALCONIES REQUIRE OUTLETS TO BE INSTALLED | | | 210.52(E)(3) | | | | | | BALCONIES, DECKS, AND PORCHES THAT ARE ATTACHED TO THE | | | DWELLING UNIT AND ARE ACCESSIBLE FROM INSIDE THE | | | DWELLING | | | UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET | | | ACCESSIBLE FROM THE BALCONY, DECK, OR PORCH. THE | | | RECEPTACLE OUTLET | | | SHALL NOT BE LOCATED MORE THAN 2.0 M (61?2 FT) ABOVE | | | THE BALCONY, DECK, OR PORCH WALKING SURFACE. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2022-09-19 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2022-09-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2022-09-19 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-10-18 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-10-18 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-09-09 |
Time |
07:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-09-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-09-03 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-11 |
Time |
08:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-10-25 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-10-25 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-10-18 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2022-10-25 08:41:45 | MU-2022-048060 - $0.00 DUE | | 2022-10-18 11:43:50 | 10/18/22 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-09-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-09-03 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-09-01 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2022-09-01 09:11:18 | IMPACT FEES | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-09-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-15 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-15 |
Time |
08:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-08-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-19 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-19 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2022-08-19 15:18:45 | 1) WHAT IS THE ID1 AND ID2 IN THE GARAGE? | | | | | | 2) SHEET MEP-3.1 AIR CONDITIONING NOTES: NOTE 1 | | | PROVIDES THE SCOPE OF WORK AS DUCTWORK MODIFICATION. | | | WHY IS THERE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR 3 ZONES FOR THIS PROJECT? | | | | | | 3) THE ZONES ARE NOT IDENTIFIED ON THE MECHANICAL | | | DRAWINGS. IDENTIFY THESE ZONES. FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-09-15 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-15 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-08-22 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-08-22 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-08-22 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2022-08-22 11:12:43 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2ND FLOOR BATHS 2 & 3 - SANITARY RISER DIAGRAM - | | | 2020 FRC P3108.2.1 - THE WATER CLOSET AND THE SHOWER | | | ARE CONNECTED BEFORE THE VENTED FIXTURE CONNECTION. | | | ONLY ONE BATHROOM GROUP FIXTURE IS ALLOWED UPSTREAM OF | | | THE VENTED FIXTURE CONNECTION. | | | | | | 2. 2ND FLOOR BATH 4 SANITARY RISER DIAGRAM - 2020 FRC | | | P3108.2.1 - THE WATER CLOSET AND THE SHOWER ARE | | | CONNECTED BEFORE THE VENTED FIXTURE CONNECTION. ONLY | | | ONE BATHROOM GROUP FIXTURE IS ALLOWED UPSTREAM OF THE | | | VENTED FIXTURE CONNECTION. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-09-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-09-03 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-09-01 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2022-09-03 09:35:20 | PROVISO ON PLAN PAGE S-3: ROOFING SHALL BE BY A | | | SEPERATE PERMIT. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-10-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-18 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-18 |
Time |
10:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-09-03 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-09-03 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-09-01 |
Time |
09:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-10-20 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-10-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-10-20 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-09-19 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-09-19 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-09-19 |
Time |
10:05 |
Sent To |
|
|
| Notes |
| 2022-09-19 10:08:56 | FAILED | | | 9/19/2022 | | | | | | REPEAT COMMENT NEEDS TO HAVE LANDSCAPE PERMIT IN SYSTEM | | | FOR THIS PERMIT TO GET APPROVED | | | | | | THE VALUE OF THE CONSTRUCTION ($825,000) EXCEEDS 50% OF | | | THE STRUCTURE'S VALUE ($814,492) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY | | | | | | SEPARATE PERMIT IS REQUIRED FOR ANY CHANGES MADE TO THE | | | POOL | | | | | | TREE RELOCATION PERMIT IS ADDITION IF ANY TREES ARE | | | BEING REMOVED | | | | | | ALEXIS SANGELEER | | | ASSOCIATE PLANNER | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-08-29 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-08-29 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2022-08-29 12:55:14 | 8/29/2022 | | | FAILED | | | PLEASE PROVIDE ALL NEW ADDITION SETBACKS ON SURVEY | | | SEPARATE PERMIT IS REQUIRED FOR ANY CHANGES MADE TO THE | | | POOL | | | TREE RELOCATION PERMIT IS NEEDED | | | LANDSCAPE PERMIT IS REQUIRED | | | THE VALUE OF THE CONSTRUCTION ($825,000) EXCEEDS 50% OF | | | THE STRUCTURE'S VALUE ($814,492) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY | | | | | | | | | | | | ALEXIS SANGELEER | | | ASSOCIATE PLANNER | | | [email protected] | | | | | | |
|
|