Plan Review Details - Permit 22080193
Plan Review Stops For Permit 22080193
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-10-18 Cont ID  
Sent By cthroop Date 2022-10-18 Time 11:15 Rev Time 0.00
Received By cthroop Date 2022-10-18 Time 10:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-09-03 Cont ID  
Sent By cthroop Date 2022-09-03 Time 10:23 Rev Time 0.00
Received By cthroop Date 2022-09-01 Time 09:10 Sent To  
Notes
2022-09-03 10:32:52PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE
 SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE A SITE PLAN....
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE
 AND INCLUDED BOUNDARY LINE SURVEY.
 NOTE: IDENTIFY THE LOCATION OF THE NEW ADDITIONS WITH
 GRAYSCALE OR HASHTAG.
  
 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 3.SMOKE ALARMS
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314.
  
 4. FILE LABELED "PRODUCT APPROVAL-UNDERLAYMENT" IS THE
 ICC-ES REPORT FOR THE ICYNENE SPRAY FOAM INSULATION.
 RE-LABEL FILE.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 NOTICE: ROOFING PROVISO ON PG. S-3: A ROOFING SHALL BE
 BY A SEPERATE PERMIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-05 Cont ID  
Sent By jleahy Date 2022-10-05 Time 10:40 Rev Time 0.00
Received By jleahy Date 2022-10-04 Time 14:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-31 Cont ID  
Sent By jleahy Date 2022-08-31 Time 13:46 Rev Time 0.00
Received By jleahy Date 2022-08-29 Time 16:20 Sent To  
Notes
2022-08-31 14:19:54FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO SMOKE DETECTORS SHOWN. R314 FBC 2020
  
 2) SERVICE SHOWS 2/0 FOR FEEDERS GOING TO THE PANELS.
 DOES NOT MEET 310.15 (B)(7)(2)
  
 310.15.(B)(7)
 FOR A FEEDER RATED 100 THROUGH 400 AMPERES, THE FEEDER
 CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A
 ONE-FAMILY
 DWELLING, OR THE FEEDER CONDUCTORS SUPPLYING THE ENTIRE
 LOAD ASSOCIATED WITH AN INDIVIDUAL DWELLING UNIT IN A
 TWO-FAMILY OR
 MULTIFAMILY DWELLING, SHALL BE PERMITTED TO HAVE AN
 AMPACITY NOT LESS THAN 83 PERCENT OF THE FEEDER RATING.
  
 3) MASTER BATH OUTLETS MAY BE TO CLOSE TO THE SHOWER
 AND TUB. 210.8(A)(9)
  
 210.8(A)(9) BATHTUBS OR SHOWER STALLS ? WHERE
 RECEPTACLES ARE INSTAL?LED WITHIN 1.8 M (6 FT) OF THE
 OUTSIDE EDGE OF THE
 BATHTUB OR SHOWER STALL
  
 4) OUTLETS REQUIRED AT THE FRONT AND REAR OF RESIDENCE
 210/52(E)(1)
  
 FOR A ONE-FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY
 DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE
 RECEPTACLE OUTLET
 READILY ACCESSIBLE FROM GRADE AND NOT MORE THAN 2.0 M
 (6 1?2 FT) ABOVE GRADE LEVEL SHALL BE INSTALLED AT THE
 FRONT AND
 BACK OF THE DWELLING.
  
 5) OUTLETS ARE REQUIRED IN THE GARAGE ONE FOR EACH
 SPACE. 210.52
  
 IN EACH ATTACHED GARAGE AND IN EACH DETACHED GARAGE
 WITH ELECTRIC POWER, AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE
 INSTALLED IN EACH VEHICLE BAY AND NOT MORE THAN 1.7 M
 (51?2 FT) ABOVE THE FLOOR.
  
 6) BALCONIES REQUIRE OUTLETS TO BE INSTALLED
 210.52(E)(3)
  
 BALCONIES, DECKS, AND PORCHES THAT ARE ATTACHED TO THE
 DWELLING UNIT AND ARE ACCESSIBLE FROM INSIDE THE
 DWELLING
 UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE FROM THE BALCONY, DECK, OR PORCH. THE
 RECEPTACLE OUTLET
 SHALL NOT BE LOCATED MORE THAN 2.0 M (61?2 FT) ABOVE
 THE BALCONY, DECK, OR PORCH WALKING SURFACE.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2022-09-19 Cont ID  
Sent By rrossano Date 2022-09-19 Time   Rev Time 0.00
Received By rrossano Date 2022-09-19 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-18 Cont ID  
Sent By lmarchan Date 2022-10-18 Time 11:42 Rev Time 0.00
Received By lmarchan Date 2022-09-09 Time 07:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-03 Cont ID  
Sent By cthroop Date 2022-09-03 Time 10:32 Rev Time 0.00
Received By cthroop Date 2022-08-11 Time 08:16 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-10-25 Cont ID  
Sent By lmarchan Date 2022-10-25 Time 08:41 Rev Time 0.00
Received By lmarchan Date 2022-10-18 Time 11:43 Sent To  
Notes
2022-10-25 08:41:45MU-2022-048060 - $0.00 DUE
2022-10-18 11:43:5010/18/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-09-03 Cont ID  
Sent By cthroop Date 2022-09-03 Time 09:36 Rev Time 0.00
Received By cthroop Date 2022-09-01 Time 09:10 Sent To  
Notes
2022-09-01 09:11:18IMPACT FEES
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-09-15 Cont ID  
Sent By medwards Date 2022-09-15 Time 08:17 Rev Time 0.00
Received By medwards Date 2022-09-15 Time 08:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-08-19 Cont ID  
Sent By medwards Date 2022-08-19 Time 15:12 Rev Time 0.00
Received By medwards Date 2022-08-19 Time 15:12 Sent To  
Notes
2022-08-19 15:18:451) WHAT IS THE ID1 AND ID2 IN THE GARAGE?
  
 2) SHEET MEP-3.1 AIR CONDITIONING NOTES: NOTE 1
 PROVIDES THE SCOPE OF WORK AS DUCTWORK MODIFICATION.
 WHY IS THERE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR 3 ZONES FOR THIS PROJECT?
  
 3) THE ZONES ARE NOT IDENTIFIED ON THE MECHANICAL
 DRAWINGS. IDENTIFY THESE ZONES. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-09-15 Cont ID  
Sent By rwbrown Date 2022-09-15 Time 07:28 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-08-22 Cont ID  
Sent By rwbrown Date 2022-08-22 Time 11:08 Rev Time 0.00
Received By rwbrown Date 2022-08-22 Time 11:08 Sent To  
Notes
2022-08-22 11:12:431ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2ND FLOOR BATHS 2 & 3 - SANITARY RISER DIAGRAM -
 2020 FRC P3108.2.1 - THE WATER CLOSET AND THE SHOWER
 ARE CONNECTED BEFORE THE VENTED FIXTURE CONNECTION.
 ONLY ONE BATHROOM GROUP FIXTURE IS ALLOWED UPSTREAM OF
 THE VENTED FIXTURE CONNECTION.
  
 2. 2ND FLOOR BATH 4 SANITARY RISER DIAGRAM - 2020 FRC
 P3108.2.1 - THE WATER CLOSET AND THE SHOWER ARE
 CONNECTED BEFORE THE VENTED FIXTURE CONNECTION. ONLY
 ONE BATHROOM GROUP FIXTURE IS ALLOWED UPSTREAM OF THE
 VENTED FIXTURE CONNECTION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2022-09-03 Cont ID  
Sent By cthroop Date 2022-09-03 Time 09:34 Rev Time 0.00
Received By cthroop Date 2022-09-01 Time 09:10 Sent To  
Notes
2022-09-03 09:35:20PROVISO ON PLAN PAGE S-3: ROOFING SHALL BE BY A
 SEPERATE PERMIT. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-10-18 Cont ID  
Sent By cthroop Date 2022-10-18 Time 11:14 Rev Time 0.00
Received By cthroop Date 2022-10-18 Time 10:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-09-03 Cont ID  
Sent By cthroop Date 2022-09-03 Time 09:35 Rev Time 0.00
Received By cthroop Date 2022-09-01 Time 09:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-10-20 Cont ID  
Sent By asangele Date 2022-10-20 Time   Rev Time 0.00
Received By asangele Date 2022-10-20 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-09-19 Cont ID  
Sent By asangele Date 2022-09-19 Time 10:05 Rev Time 0.00
Received By asangele Date 2022-09-19 Time 10:05 Sent To  
Notes
2022-09-19 10:08:56FAILED
 9/19/2022
  
 REPEAT COMMENT NEEDS TO HAVE LANDSCAPE PERMIT IN SYSTEM
 FOR THIS PERMIT TO GET APPROVED
  
 THE VALUE OF THE CONSTRUCTION ($825,000) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($814,492) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY
  
 SEPARATE PERMIT IS REQUIRED FOR ANY CHANGES MADE TO THE
 POOL
  
 TREE RELOCATION PERMIT IS ADDITION IF ANY TREES ARE
 BEING REMOVED
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-08-29 Cont ID  
Sent By asangele Date 2022-08-29 Time 12:38 Rev Time 0.00
Received By asangele Date 2022-08-29 Time 12:38 Sent To  
Notes
2022-08-29 12:55:148/29/2022
 FAILED
 PLEASE PROVIDE ALL NEW ADDITION SETBACKS ON SURVEY
 SEPARATE PERMIT IS REQUIRED FOR ANY CHANGES MADE TO THE
 POOL
 TREE RELOCATION PERMIT IS NEEDED
 LANDSCAPE PERMIT IS REQUIRED
 THE VALUE OF THE CONSTRUCTION ($825,000) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($814,492) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]
  
  