Plan Review Details - Permit 22080183
Plan Review Stops For Permit 22080183
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-09-26 Cont ID  
Sent By cpuell Date 2022-09-26 Time 13:13 Rev Time 0.00
Received By cpuell Date 2022-09-26 Time 13:13 Sent To  
Notes
2022-09-26 13:15:514065 N HAVERHILL RD # B7 IS THE CORRECT ADDRESS FOR THE
 INTERIOR REMODEL, UPDATED PERMIT

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-08-30 Cont ID  
Sent By cpuell Date 2022-08-30 Time 16:53 Rev Time 0.00
Received By cpuell Date 2022-08-30 Time 16:53 Sent To  
Notes
2022-08-30 16:58:30INCORRECT ADDRESS THE SOUTH SECTION ON THE WEST
 BUILDING HAS THE ADDRESS OF 4065 N HAVERHILL RD (4075 N
 HAVERHILL RD IS EXCLUSIVELY FOR PUBLIX. THE PLANS
 INDICATE THAT YOU WILL BE MERGING SUITES B6 AND B8, ONE
 OF THESE SUITES WILL NEED TO BE RETIRE SO THAT ONLY ONE
 SUITE ADDRESS REMAINS, PLEASE HAVE THE OWNER CONTACT ME
 SO THAT ONE OF THE ADDRESSES CAN BE RETIRED.
 [email protected] OR CALL 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2023-01-17 Cont ID  
Sent By jwitmer Date 2023-01-17 Time 07:24 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-10-31 Cont ID  
Sent By jwitmer Date 2022-10-31 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2022-10-31 Time 07:33 Sent To  
Notes
2022-10-31 07:45:41COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-09-28 Cont ID  
Sent By jwitmer Date 2022-09-28 Time 13:19 Rev Time 0.00
Received By jwitmer Date 2022-09-28 Time 13:19 Sent To  
Notes
2022-09-28 13:19:40COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-01-17 Cont ID  
Sent By jwitmer Date 2023-01-17 Time 07:28 Rev Time 0.00
Received By jwitmer Date 2023-01-17 Time 07:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-10-31 Cont ID  
Sent By jwitmer Date 2022-10-31 Time 07:50 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-09-28 Cont ID  
Sent By jwitmer Date 2022-09-28 Time 13:54 Rev Time 0.00
Received By jwitmer Date 2022-09-28 Time 13:20 Sent To  
Notes
2022-09-28 13:54:00WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22080183
 ADD: 4065 N HAVERHILL RD # B7
 CONT: NORTHSTAR GENERAL CONTRACTING
 TEL: 561-239-9873
 E-MAIL: KEN@[email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 28TH/2022
 ACTION: DENIED
  
 1) SHEET A-1 THE ROOM FINISH SCHEDULE INDICATES FOR THE
 2 ACCESSIBLE RESTROOMS THE WALLS ARE TO BE EPOXY PAINT.
 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINKS AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE
 SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS
 THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2) SHEET M-1 INDICATES THE ROOF DECK IS GOING TO BE
 PENETRATED WITH 4 20-INCH DIA. GAS FLUES UP THROUGH THE
 ROOF. THERE ARE NO DETAILS ON SHEET M-2 ROOF MECHANICAL
 SHEET FOR THE NEW ROOF FRAMING AROUND EACH PENETRATION,
 NOR IS THERE A HEIGHT GIVEN FOR THE GAS FLUE, NOR GAUGE
 OF DUCT NOR TYPE OF WEATHER SHIELD/CAP. THE SAME IS
 TRUE FOR THE FRESH AIR INTAKE DETAIL. THERE IS A NOTE:
 ATTACHMENT BY STRUCTURAL ENGINEER AND OR ARCHITECT.
  
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 2020 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-02-21 Cont ID  
Sent By jleahy Date 2023-02-21 Time 15:08 Rev Time 0.00
Received By jleahy Date 2023-02-21 Time 14:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2023-01-20 Cont ID  
Sent By jleahy Date 2023-01-20 Time 13:29 Rev Time 0.00
Received By jleahy Date 2023-01-20 Time 13:29 Sent To  
Notes
2023-01-20 13:30:10PLAN IS NOT DIGITALLY SIGNED JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-11-13 Cont ID  
Sent By jleahy Date 2022-11-13 Time 17:06 Rev Time 0.00
Received By jleahy Date 2022-11-13 Time 16:59 Sent To  
Notes
2022-11-13 17:09:03PLAN IS NOT DIGITALLY SIGNED JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-09-22 Cont ID  
Sent By jleahy Date 2022-09-22 Time 01:33 Rev Time 0.00
Received By jleahy Date 2022-09-22 Time 01:20 Sent To  
Notes
2022-09-22 01:55:00FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) CIRCUITS 13,15,17,19,21,23 TO BE GFCI PROTECTED PER
 422.5 , 210.8(B)
  
 APPLIANCES IDENTIFIED IN 422.5(A)(1) THROUGH (5) RATED
 250 VOLTS OR LESS AND 60 AMPERES OR LESS, SINGLE- OR
 3-???PHASE, SHALL BE PROVIDED WITH GFCI PROTECTION FOR
 PERSONNEL. MULTIPLE GFCI PROTECTIVE DEVICES SHALL BE
 PERMITTED BUT SHALL NOT BE REQUIRED.
 (1) AUTOMOTIVE VACUUM MACHINES PROVIDED FOR PUBLIC USE
  
 (2) DRINKING WATER COOLERS
  
 (3) HIGH-PRESSURE SPRAY WASHING MACHINES ???
 CORD-AND-PLUG-CONNECTED
  
 (4) TIRE INFLATION MACHINES PROVIDED FOR PUBLIC USE
  
 (5) VENDING MACHINE

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-10-28 Cont ID  
Sent By cwalker Date 2022-10-28 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-10-28 11:20:30FIRE PROVISO COMMENTS:
  
 (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (2) ANY MODIFICATIONS, ALTERATIONS, ADDITIONS, ETC. TO
 ANY LIFE SAFETY SYSTEM (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL BE CONDUCTED BY PROPERLY LICENSED
 CONTRACTORS AND PERFORMED UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS.
  
 (3) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION SHALL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (4) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE
 INCLUDING PAINTING.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-08-26 Cont ID  
Sent By cwalker Date 2022-08-26 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-08-26 11:46:43FIRE PROVISO COMMENTS:
  
 (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (2) ANY MODIFICATIONS, ALTERATIONS, ADDITIONS, ETC. TO
 ANY LIFE SAFETY SYSTEM (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL BE CONDUCTED BY PROPERLY LICENSED
 CONTRACTORS AND PERFORMED UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS.
  
 (3) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION SHALL REQUIRE THE IMPLEMENTATION OF A
 FIRE WATCH.
  
 (4) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE
 INCLUDING PAINTING.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2023-02-09 Cont ID  
Sent By rwbrown Date 2023-02-09 Time 11:33 Rev Time 0.00
Received By rwbrown Date 2023-02-09 Time 11:28 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2023-01-18 Cont ID  
Sent By jesmith Date 2023-01-17 Time 13:43 Rev Time 0.00
Received By jesmith Date 2023-01-17 Time 13:36 Sent To  
Notes
2023-01-17 13:43:25APPROVED

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-10-31 Cont ID  
Sent By jesmith Date 2022-10-31 Time 15:47 Rev Time 0.00
Received By jesmith Date 2022-10-31 Time 15:46 Sent To  
Notes
2022-10-31 15:47:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22080183 4075 N HAVERHILL RD
  
 GAS COMMENTS: DENIED
  
 1. COMPLIED
  
 2. COMPLIED
  
 3. SECOND REQUEST: P-3/GAS RISER: REGULATOR AT METER
 REDUCES PRESSURE TO 7 INCHES WATER COLUMN; SIZING
 CALCULATIONS ARE BASED ON FBC FG TABLE 402.4(5) 2
 PSI/1PD/6SG. PER WPB FBC 107.2.1, PLEASE CLARIFY AND
 RECONCILE.
 NEW COMMENT: NOTE FOR REGULATOR AT METER REDUCES
 PRESSURE TO 7 INCHES WATER COLUMN HAS BEEN ELIMINATED;
 SIZING CALCULATIONS ARE STILL BASED ON FBC FG TABLE
 402.4(5) 2 PSI/1PD/6SG INDICATING A 2 PSI SYSTEM.
 ***CONFIRM ON THE PLAN 2 PSI SYSTEM OR LESS THAN 2PSI
 SYSTEM
 ***IF LESS THAN 2 PSI SYSTEM, PROVIDE A SIZING TABLE
 SELECTED FROM FBC FG 402.4
 ***IF A 2PSI SYSTEM IS REQUIRED FOR DISTRIBUTION, THEN
 SPECIFY AND PROVIDE MP REGULATORS FOR FINAL
 CONNECTIONS. PROVIDE SIZING TABLE (FROM FBC FG 402.4)
 FOR REDUCED PRESSURE PIPING AND MAXIMUM DEVELOPED
 LENGTH OF REDUCED PRESSURE SYSTEM(S) FROM MP REGULATOR
 TO FINAL CONNECTIONS. SHOW LOCATIONS OF MP REGULATORS.
  
 4. COMPLIED
  
 5. COMPLIED
  
 6. COMPLIED
  
 7. COMPLIED
  
 8. SECOND REQUEST:P-1/TANKLESS GAS WATER HEATER DETAIL
 INDICATES A CONCENTRIC VENT WITH SINGLE POINT
 CONNECTION FOR SINGLE HEATER. SCHEDULED NAVIEN NPE-240A
 AND P-1/HIGH TEMP DOMESTIC WATER HEATER DETAIL REQUIRES
 DEDICATED COMBUSTION AIR INLET AND EXHAUST OUTLET.
 REFER TO NAVIEN COMMON VENT SYSTEM INSTALLATION MANUAL.
 UPDATED DETAIL SHOWS A CONCENTRIC VENT MANIFOLD WITH
 SINGLE POINT CONNECTION FOR EACH OF THE THREE WATER
 HEATERS.
 NAVIEN COMMON VENT SYSTEM INSTALLATION MANUAL FOR
 SCHEDULED WATER HEATERS REQUIRES A DEDICATED INTAKE
 MANIFOLD AND A DEDICATED EXHAUST MANIFOLD. PER FBC FG
 503.4, PROVIDE VENT SYSTEM IN ACCORDANCE WITH
 MANUFACTURER DIRECTIONS.
  
 PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE THE
 FOLLOWING:
 ***A) A DETAIL THAT PROPERLY ADDRESSES THE VENTING OF
 THE THREE UNITS.
 ***B) SIZE(S) AND MATERIAL SPECIFICATION FOR VENTS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-09-07 Cont ID  
Sent By jesmith Date 2022-09-07 Time 17:17 Rev Time 0.00
Received By jesmith Date 2022-09-06 Time 17:16 Sent To  
Notes
2022-09-07 17:15:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22080183 4075 N HAVERHILL RD
  
 GAS COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE
 MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR
 THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***WATER HEATERS
 ***DRYERS (EACH MODEL UNIT)
 ***INLET/EXHAUST VENTS FOR WATER HEATERS
 ***REGULATORS
 ALL SUBMITTALS SHALL BE APPROVED AND STAMPED BY THE
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE PER WPB FBC
 107.2.1, 107.3.4. SUBMITTALS MAY BE DEFERRED IN
 ACCORDANCE WITH SECTION WPB FBC 107.3.4.1. DEFERRED
 SUBMITTALS SHALL BE LISTED ON THE PLANS. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER FBC FG
 305.1.
  
 2. PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE ON THE GAS
 RISER DIAGRAM, ALL PIPE SIZES.
  
 3. P-3/GAS RISER: REGULATOR AT METER REDUCES PRESSURE
 TO 7 INCHES WATER COLUMN; SIZING CALCULATIONS ARE BASED
 ON FBC FG TABLE 402.4(5) 2 PSI/1PD/6SG. PER WPB FBC
 107.2.1, PLEASE CLARIFY AND RECONCILE.
 IF A 2PSI SYSTEM IS REQUIRED FOR DISTRIBUTION, THEN
 SPECIFY AND PROVIDE MP REGULATORS AT APPLIANCES.
 PROVIDE SIZING TABLE (FROM FBC FG 402.4) FOR REDUCED
 PRESSURE PIPING AND MAXIMUM DEVELOPED LENGTH OF REDUCED
 PRESSURE SYSTEM(S). PROVIDE DETAIL FOR MP REGULATOR
 CONNECTION TO APPLIANCE. COMPLY WITH FBC FG 409.4 AND
 410.2.
  
 4. PER WPB FBC 107.2.1, 107.2.1.2 AND 107.3.5.1.5,
 PROVIDE ON THE GAS RISER DIAGRAM, ITEM NUMBER AT EACH
 DRYER POC TO MATCH GAS SCHEDULE.
  
 5. P-3/GAS SCHEDULE: PER WPB FBC 107.2.1, 107.3.5.1.5,
 PROVIDE BTU RATING PER UNIT FOR EACH DRYER MODEL AND
 FOR THE WATER HEATER.
  
 6. P-3/GAS SCHEDULE INDICATES QUANTITY OF ONE (1) EACH
 WATER HEATER; P-1/HIGH TEMP DOMESTIC WATER HEATER
 DETAIL, P-2 PLAN AND P-3 RISER DIAGRAM INDICATE THREE
 (3) EACH. PER WPB FBC 107.2.1, PLEASE CLARIFY AND
 RECONCILE.
  
 7. PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE COMBUSTION
 AIR CALCULATIONS FOR THE DRYERS PER FBC FG 304.1.
  
 8. P-1/TANKLESS GAS WATER HEATER DETAIL INDICATES A
 CONCENTRIC VENT WITH SINGLE POINT CONNECTION FOR SINGLE
 HEATER. SCHEDULED NAVIEN NPE-240A AND P-1/HIGH TEMP
 DOMESTIC WATER HEATER DETAIL REQUIRES DEDICATED
 COMBUSTION AIR INLET AND EXHAUST OUTLET. REFER TO
 NAVIEN COMMON VENT SYSTEM INSTALLATION MANUAL.
 PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE THE
 FOLLOWING:
 ***A) A DETAIL THAT PROPERLY ADDRESSES THE VENTING OF
 THE THREE UNITS.
 ***B) SIZE(S) AND MATERIAL SPECIFICATION FOR VENTS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-03-06 Cont ID  
Sent By medwards Date 2023-03-06 Time 13:41 Rev Time 0.00
Received By medwards Date 2023-03-02 Time 08:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-02-24 Cont ID  
Sent By jleahy Date 2023-02-24 Time 11:00 Rev Time 0.00
Received By jleahy Date 2023-02-08 Time 10:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-23 Cont ID  
Sent By lmarchan Date 2023-01-23 Time 07:39 Rev Time 0.00
Received By lmarchan Date 2023-01-12 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-13 Cont ID  
Sent By jleahy Date 2022-11-13 Time 17:10 Rev Time 0.00
Received By jleahy Date 2022-10-27 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-09-28 Time   Rev Time 0.00
Received By cdecoeur Date 2022-08-26 Time 05:47 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-09-28 Cont ID  
Sent By jwitmer Date 2022-09-28 Time 13:19 Rev Time 0.00
Received By jwitmer Date 2022-09-28 Time 13:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2023-03-06 Cont ID  
Sent By medwards Date 2023-03-06 Time 13:41 Rev Time 0.00
Received By medwards Date 2023-03-06 Time 13:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2023-02-14 Cont ID  
Sent By medwards Date 2023-02-14 Time 11:49 Rev Time 0.00
Received By medwards Date 2023-02-14 Time 11:49 Sent To  
Notes
2023-02-14 11:51:234TH ATTEMPT AT FINDING THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS, SEE PREVIOUS COMMENT BELOW.
  
 1) THIS REVIEWER DOES NOT SEE THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS ASKED FOR IN THE PREVIOUS REVIEW
 CYCLES. PLEASE PROVIDE THEM.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-01-13 Cont ID  
Sent By medwards Date 2023-01-13 Time 15:10 Rev Time 0.00
Received By medwards Date 2023-01-13 Time 15:10 Sent To  
Notes
2023-01-13 15:10:393RD REVIEW FMC
 PERMIT: 22080183
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS REVIEWER DOES NOT SEE THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS ASKED FOR IN THE PREVIOUS REVIEW
 CYCLES. PLEASE PROVIDE THEM.
  
 2) PLEASE UNDERSTAND, YOU ARE REQUIRED TO PROVIDE THE
 OUTDOOR AIR CALCULATIONS BASED ON THE OCCUPANCY
 CLASSIFICATION FOR EACH USE OF SPACE AND THIS IS
 CALCULATED BY OCCUPANT DENSITY. ALL FROM TABLE
 403.3.1.1. THERE ARE NO HOUSE LIMIT RULES. PROVIDE A
 CALCULATION FOR EACH USE OF SPACE BASED ON THE MOST
 SIMILAR OCCUPANCY CLASSIFICATION AND THE OCCUPANT
 DENSITY IN THE TABLE 403.3.1.1.FMC 403.3.1.1 AND TABLE
 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By medwards Date 2022-11-08 Time 13:35 Sent To  
Notes
2022-11-08 13:36:261ST REVIEW FMC
 PERMIT: 22080183
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS ASKED
 FOR IN THE 1ST REVIEW CYCLE WAS NOT SUBMITTED THIS
 CYCLE. PLEASE SUBMIT THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS.
  
 2) PROVIDE THE CORRECT OUTDOOR AIR CALCULATIONS FOR A
 COMMERCIAL LAUNDRY. TABLE 403.3.1.1 CLEARLY PROVIDES
 THE OCCUPANT LOAD AND THE CFM???S PER PERSON BASED ON
 THAT OCCUPANT COUNT. THE ENTIRE SPACE IS A COMMERCIAL
 LAUNDRY. PLEASE USE THE ENTIRE NET SQUARE FOOTAGE FOR
 THE COMMERCIAL LAUNDRY REQUIRED OUTDOOR AIR
 CALCULATIONS. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 3) PLEASE SHOW THE REQUIRED DUCT DETECTORS IN THE
 SUPPLY SIDE OF THE MECHANICAL DUCT SYSTEMS. FMC 606.2.2
  
 1ST REVIEW FMC
 PERMIT: 22080183
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS ASKED
 FOR IN THE 1ST REVIEW CYCLE WAS NOT SUBMITTED THIS
 CYCLE. PLEASE SUBMIT THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS.
  
 2) PROVIDE THE CORRECT OUTDOOR AIR CALCULATIONS FOR A
 COMMERCIAL LAUNDRY. TABLE 403.3.1.1 CLEARLY PROVIDES
 THE OCCUPANT LOAD AND THE CFM???S PER PERSON BASED ON
 THAT OCCUPANT COUNT. THE ENTIRE SPACE IS A COMMERCIAL
 LAUNDRY. PLEASE USE THE ENTIRE NET SQUARE FOOTAGE FOR
 THE COMMERCIAL LAUNDRY REQUIRED OUTDOOR AIR
 CALCULATIONS. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 3) PLEASE SHOW THE REQUIRED DUCT DETECTORS IN THE
 SUPPLY SIDE OF THE MECHANICAL DUCT SYSTEMS. FMC 606.2.2
  
 4) PLEASE SUBMIT A DRYER EXHAUST DUCT DRAWING THAT WILL
 INCLUDE THE SUBMITTED DRYER SPECS INCLUDING THE MAX.
 AIR FLOW AND MAKE-UP AIR. THE DRYER MANUALS SUBMITTED
 DO NOT REFERENCE THE HTT30, HYY45 OR HT075. PLEASE
 PROVIDE DOCUMENTS WITH THESE MODELS IDENTIFIED. THE M-2
 SHEET SPECS OUT A 4INCH DRYER DUCT FOR A SINGLE DRYER
 WITH A FLEX DUCT FOR THE TRANSITION DUCT. PAGE 35 OF
 THE DRYER SPECS. SUBMITTED INDICATES A SINGLE EXHAUST
 DUCT FOR THE DRYERS WOULD BE AN 8 INCH DUCT. PLEASE USE
 THE SPECS FOR THE DRYERS INCLUDING THE MAX. DISTANCE
 AND PROVIDE A DRYER EXHAUST DRAWING FOR THIS LAUNDRY.
 FMC 504.9
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-09-02 Cont ID  
Sent By medwards Date 2022-09-02 Time 09:56 Rev Time 0.00
Received By medwards Date 2022-09-02 Time 09:56 Sent To  
Notes
2022-09-02 09:56:511ST REVIEW FMC
 PERMIT: 22080183
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS NEW LAUNDRY MAT.
  
 2) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS
 COMMERCIAL LAUNDRY INCLUDING ALL OF THE AREAS IN THIS
 TENANT SPACE. THE COIN OPERATED LAUNDRY WOULD NEED 711
 CFM?S OF OUTDOOR AIR. THE OFFICE AREA WOULD NEED 43
 CFM?S OF OUTDOOR AIR FOR A TOTAL OUTDOOR AIR REQUIRED
 OF 754 CFM?S. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 3) PROVIDE THE SPECS FOR THE DRYERS, INCLUDING THE
 EXHAUST DUCT INSTALLATION AND AN EXHAUST DUCT DRAWING
 FOR THESE DRYERS FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2023-02-09 Cont ID  
Sent By rwbrown Date 2023-02-09 Time 11:34 Rev Time 0.00
Received By rwbrown Date 2023-02-09 Time 11:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-01-17 Cont ID  
Sent By jesmith Date 2023-01-17 Time 14:20 Rev Time 0.00
Received By jesmith Date 2023-01-17 Time 12:16 Sent To  
Notes
2023-01-17 14:20:31FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22080183 4065 N HAVERHILL RD #B7
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 PLEASE PROVIDE A RESPONSE CONCERNING A SEPARATE PERMIT
 FOR THE SOLIDS INTERCEPTOR
 A SEPARATE PERMIT FOR THE SOLIDS INTERCEPTOR IS
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. A
 SEPARATE PERMIT IS REQUIRED HOWEVER A REVIEW OF THE
 SYSTEM UNDER THE MAIN PERMIT IS ALSO REQUIRED.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY
 ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS
 EXAMINER AT [email protected] AND RYAN BROWN, CHIEF
 PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH
 THE PERMIT NUMBER(S).
  
 1. SECOND REQUEST: THE TMV HAS BEEN REMOVED FROM
 REVISED P-1/HIGH TEMP DOMESTIC WATER HEATER DETAIL.
 PROVIDE A TEMPERATURE ACTUATED MIXING VALVE COMPLYING
 WITH ASSE 1017 BETWEEN THE WATER HEATERS AND THE HOT
 WATER DISTRIBUTION SYSTEM AS REQUIRED BY FBC PL 607.1.1
 AND 613.1.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-11-02 Cont ID  
Sent By jesmith Date 2022-11-02 Time 09:36 Rev Time 0.00
Received By jesmith Date 2022-10-31 Time 16:45 Sent To  
Notes
2022-11-02 09:33:34FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22080183 4065 N HAVERHILL RD #B7
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A SEPARATE PERMIT FOR THE SOLIDS INTERCEPTOR IS
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. A
 SEPARATE PERMIT IS REQUIRED HOWEVER A REVIEW OF THE
 SYSTEM UNDER THE MAIN PERMIT IS ALSO REQUIRED.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY
 ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS
 EXAMINER AT [email protected] AND RYAN BROWN, CHIEF
 PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH
 THE PERMIT NUMBER(S).
  
 1. THE TMV HAS BEEN REMOVED FROM REVISED P-1/HIGH TEMP
 DOMESTIC WATER HEATER DETAIL. PROVIDE A TEMPERATURE
 ACTUATED MIXING VALVE COMPLYING WITH ASSE 1017 BETWEEN
 THE WATER HEATERS AND THE HOT WATER DISTRIBUTION SYSTEM
 AS REQUIRED BY FBC PL 607.1.1 AND 613.1.
  
 2. SOLIDS INTERCEPTOR: THE PLANS ARE UNCLEAR AS TO
 WHETHER THE UNIT IS IN AN AREA SUBJECT TO
 AUTOMOTIVE/HEAVY TRAFFIC. PER WPB FBC 107.2.1, CLARIFY.
 PER FBC PL 305.7 & 1003.10, PLEASE INDICATE ON THE
 P-1/SOLIDS INTERCEPTOR SPECIFICATION OPTION C24-HP FOR
 H20 LIDS IF APPLICABLE.
 DESIGNER RESPONSE IS THE UNIT IS NOT SUBJECT TO
 AUTOMOTIVE/HEAVY TRAFFIC
 NEW COMMENT: PLEASE INDICATE ON THE PLANS
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-09-07 Cont ID  
Sent By jesmith Date 2022-09-07 Time 17:09 Rev Time 0.00
Received By jesmith Date 2022-09-06 Time 11:51 Sent To  
Notes
2022-09-07 17:05:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22080183 4075 N HAVERHILL RD
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. P-2: CONFIRM LOCATION OF EXISTING BACKFLOW PREVENTER
 ON THE PLAN. IF A NEW BACKFLOW PREVENTER IS REQUIRED, A
 SEPARATE PERMIT IS REQUIRED AND IS REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS
 REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN
 PERMIT IS ALSO REQUIRED.
 ***PROVIDE DETAIL AND SCHEDULE FOR NEW BACKFLOW
 PREVENTER IF APPLICABLE.
  
 2. A SEPARATE PERMIT FOR THE SOLIDS INTERCEPTOR IS
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. A
 SEPARATE PERMIT IS REQUIRED HOWEVER A REVIEW OF THE
 SYSTEM UNDER THE MAIN PERMIT IS ALSO REQUIRED.
  
 3. PER WPB FBC 107.2.1, PLEASE PROVIDE THE
 MANUFACTURER'S INSTALLATION MANUAL FOR THE SCHEDULED
 SOLIDS INTERCEPTOR
  
 4. THE BUILDING DRAIN/SEWER PIPING TO THE INTERCEPTOR
 IS 6 INCH. PER WPB FBC 107.2.1, PLEASE INDICATE ON THE
 P-1/SOLIDS INTERCEPTOR SPECIFICATION OPTION 6P FOR 6
 INCH INLET/OUTLET
  
 5. PER WPB FBC 107.2.1, PLEASE INDICATE ON THE
 P-1/SOLIDS INTERCEPTOR SPECIFICATION THE FILTER OPTION
 TO BE INCORPORATED.
  
 6. P-2/KEYNOTE AND P-3/KEYNOTE 2 INDICATE SOLIDS
 INTERCEPTOR EFFLUENT SHALL CONNECT TO EXISTING 4 INCH
 SANITARY; INFLUENT SIZE IS 6 INCH. PER WPB FBC 107.2.1,
 PLEASE CLARIFY.
  
 7. P-2 AND P-3 SHOWS A P-TRAP AHEAD OF THE SOLIDS
 INTERCEPTOR. PER FBC PL 901.2.1, A VENT IS REQUIRED
 DOWNSTREAM OF THE TRAP.
  
 8. THE VENT FOR THE 6 INCH COMBINATION WASTE AND VENT
 SYSTEM FOR THE CLOTHES WASHERS IS NOTED ON P-2/KEY NOTE
 1 AND P-3/KEY NOTE 1 AS A 3 INCH VENT THROUGH THE ROOF.
 P-3 SANITARY RISER DIAGRAM INDICATES A 2 INCH VENT
 CONNECTING TO 3 INCH VTR BY MEANS OF BRANCH VENT. PER
 FBC 906.2, THE VENT SHALL BE 3 INCH. PLEASE CLARIFY AND
 RECONCILE.
  
 9. SOLIDS INTERCEPTOR: PER WPB FBC 107.2.1, PROVIDE AN
 ENLARGED PIPING DIAGRAM SHOWING
 ***A) THE LOCATIONS OF CLEANOUTS AND VENTS AS REQUIRED
 BY THE MANUFACTURER AND FBC PL 1003.9.
 ***B) SIZE OF INFLUENT AND EFFLUENT PIPING
  
 10. SOLIDS INTERCEPTOR: PER WPB FBC 107.2.1, PROVIDE A
 SITE SPECIFIC, DIMENSIONED INSTALLATION DIAGRAM
 (ELEVATION) SHOWING THE BURIAL DEPTH AND INLET AND
 OUTLET LOCATIONS, CLEAN OUTS AND SIZES. INCLUDE SURFACE
 CONDITIONS (I.E. WALKWAY, TRAFFIC AREA, GRASSY AREA).
 COMPLY WITH MANUFACTURER'S INSTALLATION MANUAL. FBC PL
 301.7, 303.2.
  
 11. SOLIDS INTERCEPTOR: THE PLANS ARE UNCLEAR AS TO
 WHETHER THE UNIT IS IN AN AREA SUBJECT TO
 AUTOMOTIVE/HEAVY TRAFFIC. PER WPB FBC 107.2.1, CLARIFY.
 PER FBC PL 305.7 & 1003.10, PLEASE INDICATE ON THE
 P-1/SOLIDS INTERCEPTOR SPECIFICATION OPTION C24-HP FOR
 H20 LIDS IF APPLICABLE.
  
 12. MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL
 FOR THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***WATER HEATERS
 ***CLOTHES WASHERS
 ***SOLIDS INTERCEPTOR
 ***HEAVY DUTY TRAFFIC LIDS
 ALL SUBMITTALS SHALL BE APPROVED AND STAMPED BY THE
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC
 107.2.1, 107.3.4. SUBMITTALS MAY BE DEFERRED IN
 ACCORDANCE WITH SECTION WPB FBC 107.3.4.1. DEFERRED
 SUBMITTALS SHALL BE LISTED ON THE PLANS. SUBMITTALS
 SHALL BE ON SITE PRIOR TO FIRST INSPECTION. PROCEED AT
 YOUR OWN RISK.
  
 13. A-1/ROOM FINISH SCHEDULE FOR BATHROOM WALLS: PER
 FBC 1210.2.2, FBC PL 310.3, WALLS WITHIN 2 FEET OF
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE TO A HEIGHT NOT LESS THAN 4 FEET ABOVE THE
 FLOOR. SECTION 1210.2.2 STIPULATES THAT THE MATERIAL BE
 "HARD." THE INTENT OF THIS SECTION IS THAT THE
 SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS
 EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME
 ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 14. A-1/ROOM FINISH SCHEDULE FOR JANITORS ROOM: AMEND
 NOTE TO STATE *FRP TO 4 FEET MINIMUM AFF. FBC 1210.2.2,
 FBC PL 310.3
  
 15. P-1/PLUMBING NOTE 15: PER WPB FBC 107.2.1 AND FBC
 PL 604.9, REPLACE THE WORDS "APPROVED AIR CHAMBERS"
 WITH THE WORDS "WATER HAMMER ARRESTORS CONFORMING TO
 ASSE 1010"
  
 16. P-3: PER WPB FBC 107.2.1, PROVIDE WATER PIPE SIZES
 FOR CLOTHES WASHER BATTERY WATER PIPING.
  
 17. 18. P-3: PER WPB FBC 107.2.1, PROVIDE SIZE(S) FOR
 CLOTHES WASHER BATTERY SANITARY PIPING.
  
 19. P-3: PER WPB FBC 107.2.1, IDENTIFY THE FLOOR SINKS
 ON THE PLAN, PROVIDE SIZE.
  
 20. PER FBC EC C404.5.1 AND TABLE C404.5.1, THE 1/2
 -INCH HOT WATER PIPE TO THE LAVATORIES SHALL NOT EXCEED
 2 FEET FROM THE HOT WATER SOURCE.
  
 21. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
  
 22. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 23. PROVIDE ENERGY EFFICIENCY FOR WATER HEATERS; COMPLY
 WITH FBC EC TABLE C404.2
  
 24. A THERMOSTATIC MIXING VALVE IS SHOWN ON P-1/HIGH
 TEMP DOMESTIC WATER HEATER DETAIL BUT NOT ON THE WATER
 DISTRIBUTION RISER AND PLAN VIEWS. PER WPB FBC 107.2.1,
 PLEASE CLARIFY AND RECONCILE.
  
 25. P-1/HIGH TEMP DOMESTIC WATER HEATER DETAIL: PER WPB
 FBC 107.2.1, PROVIDE A SCHEDULE AND SPECIFICATION FOR
 THE TMV.
  
 26. P-1/TANKLESS GAS WATER HEATER DETAIL: PER WPB FBC
 107.2.1, PROVIDE MEANS AND POINT OF TERMINATION FOR
 CONDENSATE DRAIN.
  
 27. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING
 LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF
 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE
 A MINIMUM SLOPE OF 1/8 INCH PER FOOT."
  
 28. M-1/MECHANICAL PLAN NOTE H CALLS FOR A/C CONDENSATE
 TO NEAREST ROOF DRAIN OR INDIRECT WASTE. PER WPB CODE
 OF ORDINANCE CHAPTER 90, ARTICLE 3, SECTION 90-12B5,
 A/C CONDENSATE (INTERPRET THIS AS ANY CONDENSATION FROM
 EVAPORATOR COILS) SHALL NOT DISCHARGE TO THE CITY
 UTILITIES SANITARY SEWAGE INFRASTRUCTURE WITHOUT
 PERMISSION FROM THE UTILITIES DEPARTMENT. YOU MAY
 CONTACT MR. RICK ROSSANO IN ENGINEERING AT 561-494-1098
 FOR ADDITIONAL INFORMATION. MOVING FORWARD, REMOVE
 INDIRECT WASTE FROM THE NOTE. FBC PL 314.2.1.
  
 29. PER WPB FBC 107.2.1, PROVIDE RECIRCULATING PUMP
 SCHEDULE & DETAIL. INTEGRATE WITH P-1/HIGH TEMP
 DOMESTIC WATER HEATER DETAIL.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-02-24 Cont ID  
Sent By jleahy Date 2023-02-24 Time 11:00 Rev Time 0.00
Received By jleahy Date 2023-02-24 Time 11:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-01-17 Cont ID  
Sent By jwitmer Date 2023-01-17 Time 07:46 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2023-01-17 14:25:17DIGITAL SIGNATURES FOR PLUMBING PLANS ARE VALID. JS
2023-01-17 07:46:13ELECTRICAL SHEETS. FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) PLANS IN THE FILE FOLDER, SCANNED,
 FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE OF THE
 LICENSEE???S SIGNATURE SHALL NOT BE USED ON
 ELECTRONIC/DIGITALLY SIGNED AND SEALED ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 61G15-23.004 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS, REQUIRE 3RD
 PARTY VERIFICATION.
  
2023-01-13 15:12:07ORIGINAL DIGITALLY SIGNED DRAWINGS REQUIRED FOR THE
 MECHANICAL DRAWINGS. FS 471/481 ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-11-13 Cont ID  
Sent By jleahy Date 2022-11-13 Time 17:09 Rev Time 0.00
Received By jleahy Date 2022-11-13 Time 17:09 Sent To  
Notes
2022-11-13 17:09:55PLANS ARE NOT DIGITALLY SIGNED JLEAHY
2022-11-08 14:04:47MECHANICAL DRAWINGS ARE NOT DIGITALLY SIGNED. PLEASE
 SUBMIT THE ORIGINALLY DIGITALLY SIGNED DRAWINGS. ME
2022-11-02 09:48:11PLUMBING AND GAS PLANS ARE NOT DIGITALLY SIGNED. PLEASE
 PROVIDE DIGITALLY SIGNED PLANS. JS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-09-02 Cont ID  
Sent By medwards Date 2022-09-02 Time 09:59 Rev Time 0.00
Received By medwards Date 2022-09-02 Time 09:59 Sent To  
Notes
2022-09-06 11:59:33PLUMBING AND GAS PLANS ARE NOT DIGITALLY SIGNED. PLEASE
 PROVIDE DIGITALLY SIGNED PLANS. JS
2022-09-02 10:00:36DIGITALLY SUBMITTED DOCUMENTS MUST BE DIGITALLY SIGNED
 BY THE DESIGNER. PROVIDE DIGITALLY SIGN DOCUMENTS. FS
 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-09-08 Cont ID  
Sent By asangele Date 2022-09-08 Time 10:31 Rev Time 0.00
Received By asangele Date 2022-09-08 Time 10:31 Sent To  
Notes
***NONE***