Plan Review Details - Permit 22080171
Plan Review Stops For Permit 22080171
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-10-04 Cont ID  
Sent By cpuell Date 2022-10-04 Time 09:38 Rev Time 0.00
Received By cpuell Date 2022-10-04 Time 09:38 Sent To  
Notes
2022-10-04 09:38:30ADDRESS APPROPRIATE FOR PROJECT.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-09-14 Cont ID  
Sent By cpuell Date 2022-09-14 Time 12:51 Rev Time 0.00
Received By cpuell Date 2022-09-14 Time 12:51 Sent To  
Notes
2022-09-14 12:52:22PLEASE PROVIDE A SURVEY OF SITE PLAN SHOWING THE
 LOCATION OF THE WORK TO BE DONE. A SECONDARY ADDRESS
 WILL NEED TO BE ASSIGNED IF ZONING APPROVES A SECONDARY
 UNIT. PLEASE CONTACT [email protected] OR CALL
 561-805-6659 ONCE ZONING APPROVES THEIR REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-11-17 Cont ID  
Sent By rmcdouga Date 2022-11-17 Time 09:02 Rev Time 0.00
Received By rmcdouga Date 2022-11-17 Time 08:32 Sent To  
Notes
2022-11-17 09:02:41BUILDING AUDIT ONLY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-10-13 Cont ID  
Sent By rmcdouga Date 2022-10-13 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2022-10-12 Time 17:36 Sent To  
Notes
2022-10-13 08:02:41BUILDING AUDIT ONLY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-11-16 Cont ID  
Sent By mpeterso Date 2022-11-16 Time 15:53 Rev Time 0.00
Received By mpeterso Date 2022-11-16 Time 15:53 Sent To  
Notes
2022-11-16 15:57:47ELECTRICAL AUDIT PASSED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-10-11 Cont ID  
Sent By mpeterso Date 2022-10-11 Time 08:41 Rev Time 0.00
Received By mpeterso Date 2022-10-11 Time 08:22 Sent To  
Notes
2022-10-11 08:43:30AUDIT OF ELECTRICAL PLANS FAILED
  
 1) PLEASE DETAIL THE REQUIRED GROUNDING ELECTRODE
 SYSTEM FOR THE CABANA ELECTRIC PANEL AS REQUIRED PER
 NEC 250.32
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-11-03 Cont ID  
Sent By rwbrown Date 2022-11-03 Time 16:00 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-10-12 Cont ID  
Sent By ccole Date 2022-10-12 Time 12:46 Rev Time 0.00
Received By rwbrown Date 2022-10-12 Time 12:46 Sent To  
Notes
2022-10-12 13:01:461ST GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FGC 402.3 - USING THE LONGEST RUN METHOD, AT
 175 FEET FOR PE ON 2 PSI INLET WITH 1 PSI DROP, YOU
 ONLY HAVE 1,170K BTU AVAILABLE ON 1" PE, AND NEED
 1,194K BTU. PLEASE CHECK THE SIZING AND RECONFIGURE.
 YOU'VE ALSO DETAILED THE PRESSURE AT THE SPLIT TO THE
 RANGE AS 8" W.C., WHICH IS LESS THAN THE 1 PSI ON THE
 ORIGINAL SIZE CHART SHOWN TO SUPPLY ALL THE WAY TO THE
 GENERATOR. WHEN USING THE LONGEST RUN METHOD, YOU CAN
 USE ONLY ONE SIZE CHART PER PRESSURE ZONE.
  
 2. 2020 FRC G2415.14 - SHOW BETTER DETAILS FOR SLEEVING
 TO SHOW COMPLIANCE WITH THIS SECTION. YOUR DRAWING
 INDICATE THE SLEEVES TERMINATE BELOW GRADE. THE SLEEVES
 THAT TERMINATE INDOORS MUST TERMINATE IN "AN OCCUPIABLE
 PORTION OF THE BUILDING". IF THE RANGE IS FIXED IN
 PLACE, IT CANNOT TERMINATE BEHIND IT. THE SLEEVE CANNOT
 TERMINATE BEHIND THE FIREPLACE.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-11-21 Cont ID  
Sent By jleahy Date 2022-11-21 Time 13:11 Rev Time 0.00
Received By jleahy Date 2022-11-18 Time 09:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-11-17 Cont ID  
Sent By rmcdouga Date 2022-11-17 Time 09:03 Rev Time 0.00
Received By rmcdouga Date 2022-10-24 Time 15:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-13 Cont ID  
Sent By rmcdouga Date 2022-10-13 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2022-10-07 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-10-07 Time   Rev Time 0.00
Received By aoliver Date 2022-09-29 Time 09:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-19 Cont ID  
Sent By shill Date 2022-09-19 Time 09:29 Rev Time 0.00
Received By shill Date 2022-09-08 Time 05:40 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-10-12 Cont ID  
Sent By rmcdouga Date 2022-10-12 Time 17:18 Rev Time 0.00
Received By rmcdouga Date 2022-10-12 Time 17:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-10-03 Cont ID  
Sent By medwards Date 2022-10-03 Time 16:45 Rev Time 0.00
Received By medwards Date 2022-10-03 Time 16:45 Sent To  
Notes
2022-10-03 16:45:58MECHANICAL AUDIT ONLY. ME

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-11-21 Cont ID  
Sent By rwbrown Date 2022-11-21 Time 08:52 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-11-03 Cont ID  
Sent By rwbrown Date 2022-11-03 Time 15:57 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-11-03 15:58:042ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. COMMENT NOT ADDRESSED -
 2020 FRC P3108.1 - THE SHOWER IS NOT VENTED TO CODE.
 THE BAR/GRILL AREA SINK IS NOT A BATHROOM GROUP FIXTURE
 AND WOULD NEED TO DISCHARGE DOWNSTREAM OF THE WET VENT
 SYSTEM. CURRENTLY, IT RUNS PAST THE SHOWER WHICH
 APPEARS TO BE PART OF THE WET VENT SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-10-12 Cont ID  
Sent By ccole Date 2022-10-12 Time 13:02 Rev Time 0.00
Received By rwbrown Date 2022-10-12 Time 12:45 Sent To  
Notes
2022-10-12 13:04:011ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC P3108.1 - THE SHOWER IS NOT VENTED TO CODE.
 THE BAR/GRILL AREA SINK IS NOT A BATHROOM GROUP FIXTURE
 AND WOULD NEED TO DISCHARGE DOWNSTREAM OF THE WET VENT
 SYSTEM. CURRENTLY, IT RUNS PAST THE SHOWER WHICH
 APPEARS TO BE PART OF THE WET VENT SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status P Date 2022-11-21 Cont ID  
Sent By jleahy Date 2022-11-21 Time 13:11 Rev Time 0.00
Received By jleahy Date 2022-11-21 Time 13:11 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status P Date 2022-11-16 Cont ID  
Sent By mpeterso Date 2022-11-16 Time 15:50 Rev Time 0.00
Received By mpeterso Date 2022-11-16 Time 15:50 Sent To  
Notes
2022-11-16 15:50:46AUDIT OF AFFIDAVIT PASSED

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2022-10-03 Cont ID  
Sent By medwards Date 2022-10-03 Time 16:33 Rev Time 0.00
Received By medwards Date 2022-10-03 Time 16:33 Sent To  
Notes
2022-09-19 09:26:08AFFIDAVIT REVIEW REQUIRED
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-08-04 Cont ID  
Sent By dbattles Date 2022-08-04 Time 10:28 Rev Time 0.00
Received By dbattles Date 2022-08-04 Time 10:28 Sent To  
Notes
2022-09-19 09:36:23***NEED AFFIDAVIT REVIEW AFTER ZONING***
2022-08-04 10:29:26PRIVATE PROVIDER DOCUMENTS APPROVED UNDER MASTER PERMIT
 21100601
 PLAN REVIEW AND INSPECTIONS

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2022-10-12 Cont ID  
Sent By rmcdouga Date 2022-10-12 Time 17:09 Rev Time 0.00
Received By rmcdouga Date 2022-10-12 Time 17:09 Sent To  
Notes
2022-10-12 17:10:40BERMUDA CONCRETE FLAT ROOF TILE NOA NO. 21-0323.04
 POLYGLASS TU PLUS NOA NO. 21-0602.14
 POLYSET AH-160 NOA NO. 22-0411.02
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-11-21 Cont ID  
Sent By jleahy Date 2022-11-21 Time 13:11 Rev Time 0.00
Received By jleahy Date 2022-11-21 Time 13:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-16 Cont ID  
Sent By mpeterso Date 2022-11-16 Time 15:51 Rev Time 0.00
Received By mpeterso Date 2022-11-16 Time 15:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-10-03 Cont ID  
Sent By medwards Date 2022-10-03 Time 16:46 Rev Time 0.00
Received By medwards Date 2022-10-03 Time 16:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-10-07 Cont ID  
Sent By asangele Date 2022-10-07 Time 11:37 Rev Time 0.00
Received By asangele Date 2022-10-07 Time 11:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-09-13 Cont ID  
Sent By asangele Date 2022-09-13 Time 12:35 Rev Time 0.00
Received By asangele Date 2022-09-13 Time 12:35 Sent To  
Notes
2022-09-13 12:37:33FAILED
 9/13/2022
 PLEASE PROVIDE A PROPERTY SURVEY WITH APPLICATION AND
 LABEL THE SETBACKS OF THE PROPOSED POOL CABANA.
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]