| 2022-08-17 12:49:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION ON THE FLLOR PLAN: "UNDER NEW |
| | TILE", HOWEVER, THERE IS NO INDICATION OF THE |
| | REPLACEMENT FLOOR/"TILE"PRODUCT/MATERIAL. |
| | |
| | THERE IS ALSO A SPEC SHEET FOR THE FLOOR UNDERLAYMENT, |
| | BUT NO "TILE" SPEC SHEET NOR A PRODUCT NAME FOR THE |
| | ACTUAL PROPOSED REPLACEMENT FLOORING. |
| | |
| | THE WORD "TILE" CAN HAVE DIFFERENT DEFINITIONS TO |
| | DIFFERENT PEOPLE AND CAN BE MANUFACTURED AROUND THE |
| | WORLD AND NOT ALL ARE TESTED AND MEETING LISTED AND |
| | NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE "TILE" |
| | PRODUCT NAME AND THE PRODUCT SPEC SHEETS OF THE |
| | PROPOSED "TILE" FLOORING INDICATING THE FIRE BEHAVIOR |
| | RATING. |
| | |
| | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| | WOULD NOT BE REQUIRED. |
| | |
| | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| | FLOORING, WOOD/VINYL LAMINATES, ETC. |
| | |
| | |
| | 2) SHEET A 2 - THERE IS AN INDICATION OF SECURING A |
| | KITCHEN DOOR; HOWEVER, THE DOOR WILL REMIAN ON THE |
| | EXTERIOR. |
| | |
| | FOR FIRE GROUND OPERATIONS AND GAINING ACCESS FOR LIFE |
| | SAFETY , FF'S NEED TO KNOW THAT THEY CANNOT ENTER THAT |
| | DOOR. |
| | |
| | 4.6.1.2 ANY REQUIREMENTS THAT ARE ESSENTIAL FOR THE |
| | SAFETY OF BUILDING |
| | OCCUPANTS AND THAT ARE NOT SPECIFICALLY PROVIDED FOR BY |
| | THIS CODE SHALL |
| | BE DETERMINED BY THE AUTHORITY HAVING JURISDICTION |
| | A SIGN IS REQUIRED WITH THE WORDING(OR SIMILAR) NO |
| | ENTRY THIS DOOR. |
| | |
| | 4.6.1.3 WHERE IT IS EVIDENT THAT A REASONABLE DEGREE OF |
| | SAFETY IS PROVIDED, |
| | ANY REQUIREMENT SHALL BE PERMITTED TO BE MODIFIED IF, |
| | IN THE JUDGMENT |
| | OF THE AUTHORITY HAVING JURISDICTION, ITS APPLICATION |
| | WOULD BE HAZARDOUS |
| | UNDER NORMAL OCCUPANCY CONDITIONS |
| | |
| | PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE ANOTE OF |
| | ACKNOWLEDGMENT ON THE PLAN SHEET. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |