| Plan Review Stops For Permit 22080128 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-20 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-03-20 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-03-20 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2023-03-20 10:50:56 | PLEASE PROVIDE A SITE PLAN OR AERIAL MAP SHOWING THE | | | EXACT BUILDING TO BE WORKED ON. THE MAIN BUILDING HAS | | | THE ADDRESS OF 400 33RD ST # 1 AND THE SOUTH WEST | | | BUILDING HAS THE ADDRESS OF 400 33RD ST # 2 AND THERE | | | IS ANOTHER BUILDING THAT DOESN'T CURRENTLY HAVE AN | | | ADDRESS, TRYING TO ESTABLISH WHICH BUILDING OF THE 3 | | | THIS PERMIT IS FOR, PLEASE EMAIL RESPONSE TO | | | [email protected] OR CALL 561-805-6659. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-21 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-21 |
Time |
09:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
rperdomo |
Date |
2023-03-21 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
rperdomo |
Date |
2023-03-21 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2023-03-21 08:21:37 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE ELECTRICAL SCOPE OF WORK AND DRAWINGS | | | SHOWING THE ELECTRICAL WIRING AND PROTECTIONS. FBC | | | 107.2.1 | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2023-04-07 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-04-07 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-04-07 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2023-04-07 12:17:14 | SEE ZONING COMMENTS. | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-04-07 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-04-07 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-08-02 |
Time |
08:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-21 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-21 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2023-03-21 15:46:30 | SHOW THE EXHAUST FOR THIS NEWLY ADDED BATH ROOM. FRC | | | 303.3 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-03-21 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-03-21 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2023-03-21 08:06:48 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22080128 | | | 3/21/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A SANITARY DRAINAGE AND VENT ISOMETRIC | | | DRAWING FOR THE NEW BATHROOM PLUMBING- SEC. 107.3.5.3 | | | WPB. | | | | | | 2) PLEASE NOTE THE FOLLOWING CONCERNING ANY FUTURE | | | PLANS TO CREATE A SECOND DWELLING UNIT ON THE LOT. TWO | | | DWELLINGS ON THE SAME LOT WILL REQUIRE WATER USERS TO | | | INSTALL A BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF | | | DELIVERY. A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL | | | BE REQUIRED AT THE WATER METER PER THE CITY OF WEST | | | PALM CROSS UTILITIES DEPARTMENT AND THEIR CONNECTION | | | CONTROL PROGRAM. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
lbond |
Date |
2023-03-21 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
lbond |
Date |
2023-03-21 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2023-03-21 09:43:34 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 22080128 | | | | | | REVIEWED: MARCH 21, 2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | 1)THE PLANS SHALL BEAR THE PRINTED NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE REMODEL. | | | SECTION 107.2.1 WPB | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2023-04-07 |
|
|
Cont ID |
|
| Sent By |
AMHamil |
Date |
2023-04-07 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-04-07 |
Time |
12:12 |
Sent To |
|
|
| Notes |
| 2023-04-07 12:16:35 | 4/7/2023 FAILED | | | | | | SURVEY IS REQUIRED TO SHOW WHERE THE GARAGE IS LOCATED | | | ON THE PROPERTY | | | | | | SURVEY SHALL BE NO OLDER THAN 2 YEARS | | | | | | SITE PLAN SHALL BE PROVIDED TO SHOW THE PROPOSED FLOOR | | | PLANS | | | | | | IF EXTENDIGN THE FOOT PRINT, PLEASE SHOW SETBACKS AND | | | SQUARE FEET OF PROPOSED BAHTROOM. | | | | | | **** REVIEWD BY **** | | | VALENTINA BROGLIA | | | PLANNER | | | [email protected] | | | |
|
|