| Plan Review Stops For Permit 22080039 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2023-02-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-02-14 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-02-13 |
Time |
16:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-10-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-27 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-10-26 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2022-10-27 07:39:50 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | FBC R401.3 SITE DRAINAGE | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. | | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | | INCHES WITHIN THE FIRST 10 FEET. | | | | | | 2. GOVERNING CODES REFERENCED UNDER DESIGN PARAMETERS | | | ON PLAN PAGE 3.1 ARE INCORRECT. DESIGN SHALL BE UNDER | | | THE 2020 FBC 7TH ED AND ASCE 7-16. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2. | | | | | | 3.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT | | | APPROVAL, APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED | | | WINDOWS. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-08-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-27 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-27 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2022-08-27 09:08:47 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE A SITE PLAN.... | | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | | AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE | | | AND INCLUDED BOUNDARY LINE SURVEY. | | | | | | 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 | | | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | | INCLUDED BOUNDARY LINE SURVEY. | | | FBC R401.3 SITE DRAINAGE | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. | | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | | INCHES WITHIN THE FIRST 10 FEET. | | | | | | 3. GOVERNING CODES REFERENCED UNDER DESIGN PARAMETERS | | | ARE INCORRECT. DESIGN SHALL BE UNDER THE 2020 FBC 7TH | | | ED AND ASCE 7-16. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 4.PROVIDE THE ENERGY CALCULATIONS FOR THE ADDITION | | | FBC EC R101.5.1.1. | | | R101.5.1.1RESIDENTIAL ? 3 STORIES. | | | | | | 5. SMOKE ALARMS | | | R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-10-12 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-12 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-12 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-08-24 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-08-24 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-08-24 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2022-08-24 10:48:35 | SEE SIGNATURE REVIEW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-02-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-02-14 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-01-24 |
Time |
12:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-10-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-10-27 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-09-22 |
Time |
08:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-08-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-27 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-02 |
Time |
06:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-03-01 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-03-01 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-02-21 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2023-02-28 11:09:40 | RECEIPT MU-2023-007740 - $1897.60 PAID | | 2023-02-21 08:49:36 | EMAILED IMPACT FOR REVIEW-AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-08-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-27 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-27 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2022-08-27 08:59:32 | PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT | | | LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO | | | THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF. | | | THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ | | | B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE | | | RECEIPT TO PROJECT DOX OR EMAIL IT TO | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-10-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-26 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-26 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2022-09-26 13:56:12 | MINI-SPLIT FOR THE MASTER AREA APPROVED .ME | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-12 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-12 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2022-08-12 12:54:43 | PROVIDE A SCOPE OF WORK FOR THE MECHANICAL SYSTEM, THE | | | DRAWING INDICATES THE EXISTING SYSTEM WILL CONDITION | | | THE NEW ADDITION BUT THE DETAILS SHOW A NEW AHU AND | | | CONDENSING UNIT. PLEASE PROVIDE THE ENERGY | | | CALCULATIONS, THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS SHOWING EITHER THE EXISTING UNIT IS SIZED | | | TO HANDLE THE NEW LOAD OR CALCULATIONS SHOWING THE | | | SIZING FOR THE NEW MECHANICAL SYSTEM. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-09-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-26 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-26 |
Time |
17:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-08-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-11 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-11 |
Time |
13:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-08-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-27 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-27 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2022-08-27 08:58:49 | PROVISO ON PLAN PAGE 4.1: A SEPERATE PERMIT IS REQUIRED | | | FOR ROOFING. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-02-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-02-14 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-02-13 |
Time |
16:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-10-12 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-12 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-12 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2022-10-12 13:51:45 | SEE DRAWINGS IN SIGNATURE FOLDER |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-08-24 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-08-24 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-08-24 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2022-08-24 10:49:10 | SIGNATURE REVIEW FAILED | | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | DIGITALLY SEALED AND SIGNED. | | | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-01-31 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-01-31 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-01-31 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-10-04 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-10-04 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-10-04 |
Time |
15:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-08-10 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-08-10 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-08-10 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2022-08-10 16:17:57 | 8/10/2022 FAILED | | | | | | 1. PLEASE SHOW THE SETBACKS OF THE NEW ADDITION WITH | | | THE PROPERTY LINE BOUNDRY: | | | | | | MINIMUM SETBACKS FOR PRINCIPAL BUILDING. | | | FRONT: 25 FEET; | | | CORNER: 12.5 FEET; | | | REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER IS | | | LESS; | | | SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL. | | | MAXIMUM BUILDING HEIGHT: 30 FEET. | | | | | | 2 PLEASE APPLY FOR A LANDSCAPE PERMIT TO ALLOW STAFF TO | | | MOVE FORWARD | | | | | | THE VALUE OF THE CONSTRUCTION ($65,000) EXCEEDS 50% OF | | | THE STRUCTURE'S VALUE ($110,279) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | | | | VALENTINA BROGLIA | | | ASSOCIATE PLANNER | | | [email protected] | | | |
|
|