Plan Review Details - Permit 22071422
Plan Review Stops For Permit 22071422
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-08-18 Cont ID  
Sent By cpuell Date 2022-08-18 Time 13:37 Rev Time 0.00
Received By cpuell Date 2022-08-18 Time 13:37 Sent To  
Notes
2022-08-18 13:38:31ADDRESS IS CORRECTFOR THIS PROJECT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-10-06 Cont ID  
Sent By jgomez Date 2022-10-06 Time 10:42 Rev Time 0.00
Received By jgomez Date 2022-10-06 Time 10:03 Sent To  
Notes
2022-10-06 10:04:4810/06/22 RECEIVED EMAIL FROM ELIZABETH TUKE (OWNER) TO
 APPROVE BUILDING WITH PROVISO. JG.
  
 BUILDING REVIEW APPROVED WITH PROVISO
 (NOTE; PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS):
 1- REVISE BEDROOM EGRESS WINDOW SIZE TO COMPLY WITH
 SEC. R310.2.1 FBC-RESIDENTIAL.
  
 2- PROVIDE PRODUCT APPROVAL FOR:
 A)INSWING ENTRY DOOR AS SHOWN ON PLANS.
 B)SINGLE HUNG WINDOWS.
 C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 D)OVERHEAD GARAGE DOOR AS SHOWN ON PLANS.
  
 3- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-10-04 Cont ID  
Sent By jgomez Date 2022-10-04 Time 18:16 Rev Time 0.00
Received By jgomez Date 2022-10-04 Time 17:45 Sent To  
Notes
2022-10-04 18:16:47RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22071422
 236 EDGEWOOD DR (GARAGE/APARTMENT).
  
  
 NOTE:
 RESPONSE LETTER SUBMITTED IS FOR THE MAIN HOUSE
 COMMENTS NOT FOR THE GARAGE/APARTMENT.
  
  
 ORIGINAL COMMENT:
 1- BEDROOM EGRESS WINDOWS DON'T COMPLY WITH THE MINIMUM
 CLEAR OPENING REQUIREMENTS OF SEC. R310.2.1
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 RESPONSE:
 1-SINGLE HUNG BEDROOM EGRESS WINDOWS SIZE (3'-0" X
 5'-0")DOESN'T SEEM TO COMPLY WITH THE MINIMUM CLEAR
 HEIGHT OPENING REQUIREMENTS OF SEC. R310.2.1
 FBC-RESIDENTIAL. REVISE AS REQUIRED OR PROVIDE
 MANUFACTURER'S SPECIFICATIONS SHOWING COMPLIANCE ALL
 THE EGRESS REQUIREMENTS.
 NOTE: TYPICALLY, 63" HIGH SINGLE HUNG WINDOWS ARE THE
 ONES THAT PROVIDE THE 24" CLEAR HEIGHT OPENING.
  
 2- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)INSWING ENTRY DOOR AS SHOWN ON PLANS.
 B)SINGLE HUNG WINDOWS.
 C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 D)OVERHEAD GARAGE DOOR AS SHOWN ON PLANS.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-19 Cont ID  
Sent By jgomez Date 2022-08-19 Time 17:44 Rev Time 0.00
Received By jgomez Date 2022-08-19 Time 17:05 Sent To  
Notes
2022-08-19 17:44:37RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22071422
 236 EDGEWOOD DR (GARAGE/APARTMENT)
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- BEDROOM EGRESS WINDOWS DON'T COMPLY WITH THE MINIMUM
 CLEAR OPENING REQUIREMENTS OF SEC. R310.2.1
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 2- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)INSWING ENTRY DOOR AS SHOWN ON PLANS.
 B)SINGLE HUNG WINDOWS.
 C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 D)OVERHEAD GARAGE DOOR AS SHOWN ON PLANS.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- ARCHITECT TO CLARIFY WHY THE EXTERIOR ELEVATIONS
 SHOW A SECOND FLOOR AT +9'-6" IF THIS IS ONLY ONE STORY
 BUILDING. SEC. 107.2.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-03 Cont ID  
Sent By mpeterso Date 2022-10-03 Time 15:00 Rev Time 0.00
Received By mpeterso Date 2022-10-03 Time 15:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By mpeterso Date 2022-08-05 Time 16:18 Rev Time 0.00
Received By mpeterso Date 2022-08-05 Time 16:18 Sent To  
Notes
2022-08-05 16:19:43ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL AN OUTDOOR RECEPTACLE(S) TO COMPLY
 WITH NEC 210.52 (E)(1) AND NEC 210. 63
 2) PLEASE DETAIL THE REQUIRED RECEPTACLE IN THE LIVING
 ROOM WITHIN 6 FEET OF THE FRONT DOOR TO COMPLY WITH NEC
 210.52 RECEPTACLE SPACING
 3) PLEASE DETAIL GROUNDING ELECTRODE SYSTEM FOR MAIN
 HOUSE ELECTRIC PANEL TO COMPLY WITH NEC 250.32
 4) PLEASE REMOVE CONFUSING NOTE ON PLANS DETAILING,
 PROPOSED ADDITION, TO MAIN HOUSE, AND HIGHLIGHT NOTE
 STATING, THIS CONSTRUCTION DOCUMENT SET IS FOR GUEST
 HOUSE. FBC 107.2
  
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-10-06 Cont ID  
Sent By amhamilt Date 2022-10-06 Time 14:53 Rev Time 0.00
Received By amhamilt Date 2022-10-06 Time 14:53 Sent To  
Notes
2022-10-06 14:53:30CONDITIONS SATISFIED PER ATTACHED EMAIL.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2022-08-17 Cont ID  
Sent By amhamilt Date 2022-08-17 Time 09:43 Rev Time 0.00
Received By amhamilt Date 2022-08-17 Time 09:43 Sent To  
Notes
2022-08-17 09:44:58THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PLEASE INDICATE THAT GUEST HOUSE DOOR WILL BE RETAINED
 AND USED SOMEWHERE ON PROPERTY PER HPB DECISION
 CONDITIONS. PLEASE ALSO INDICATE THAT ALL GRIDS ON
 WINDOWS WILL BE EXTERNALLY APPLIED AND HAVE A
 DIMENSIONAL PROFILE (EITHER PYRAMID OR OGEE)
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-11 Cont ID  
Sent By aoliver Date 2022-10-11 Time 09:21 Rev Time 0.00
Received By aoliver Date 2022-09-19 Time 06:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-19 Cont ID  
Sent By jgomez Date 2022-08-19 Time 17:48 Rev Time 0.00
Received By jgomez Date 2022-08-01 Time 05:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-09-20 Cont ID  
Sent By medwards Date 2022-09-20 Time 09:23 Rev Time 0.00
Received By medwards Date 2022-09-20 Time 09:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-08-08 Cont ID  
Sent By medwards Date 2022-08-08 Time 11:38 Rev Time 0.00
Received By medwards Date 2022-08-08 Time 11:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-09-20 Cont ID  
Sent By rwbrown Date 2022-09-20 Time 07:18 Rev Time 0.00
Received By rwbrown Date 2022-09-20 Time 07:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-08-01 Cont ID  
Sent By rwbrown Date 2022-08-01 Time 08:16 Rev Time 0.00
Received By rwbrown Date 2022-08-01 Time 08:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-20 Cont ID  
Sent By medwards Date 2022-09-20 Time 09:36 Rev Time 0.00
Received By medwards Date 2022-09-20 Time 09:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-08-05 Cont ID  
Sent By mpeterso Date 2022-08-05 Time 16:21 Rev Time 0.00
Received By mpeterso Date 2022-08-05 Time 16:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-10-06 Cont ID  
Sent By amhamilt Date 2022-10-06 Time 14:52 Rev Time 0.00
Received By amhamilt Date 2022-10-06 Time 14:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-08-17 Cont ID  
Sent By amhamilt Date 2022-08-17 Time 09:40 Rev Time 0.00
Received By amhamilt Date 2022-08-17 Time 09:40 Sent To  
Notes
2022-08-17 09:43:47GARAGE APARTMENT PERMITTED PER GREEN CARD
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  