Plan Review Details - Permit 22071418
Plan Review Stops For Permit 22071418
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-11-23 Cont ID  
Sent By cthroop Date 2022-11-23 Time 15:46 Rev Time 0.00
Received By cthroop Date 2022-11-23 Time 11:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-10-18 Cont ID  
Sent By cthroop Date 2022-10-18 Time 16:46 Rev Time 0.00
Received By cthroop Date 2022-10-18 Time 16:32 Sent To  
Notes
2022-10-18 16:48:45PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. SEE
 BELOW:
  
 1. PROVIDE AN EXISTING FLOOR PLAN. NOTE ON FLOOR PLAN
 PG. 1 OF 3 STATES "WALLS ADDED OR REMOVED AS SHOWN" BUT
 THERE IS NO LEGEND PROVIDED.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2.PROVIDE AN ENERGY SUBMITTAL
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
 FBC EC-R101.5.1.1.2 BUILDING THERMAL ENVELOPE
 ALTERNATIVE.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 3. NOA 21-0728.01 FOR THE SGD HAS EXPIRED.
 PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA FOR
 THE PROPOSED SGD.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 NOTE: NOA?S DO NOT HAVE COVER SHEETS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4.
  
 5.
  
 6.
  
 7. EXTERIOR DOORS/LANDINGS
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-09-03 Cont ID  
Sent By cthroop Date 2022-09-03 Time 08:30 Rev Time 0.00
Received By cthroop Date 2022-09-02 Time 16:56 Sent To  
Notes
2022-09-03 08:55:08PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE AN EXISTING FLOOR PLAN. NOTE ON FLOOR PLAN
 PG. 1 OF 3 STATES "WALLS ADDED OR REMOVED AS SHOWN" BUT
 THERE IS NO LEGEND PROVIDED.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2.PROVIDE AN ENERGY SUBMITTAL
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
 FBC EC-R101.5.1.1.2 BUILDING THERMAL ENVELOPE
 ALTERNATIVE.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 3. NOA 21-0728.01 FOR THE SGD HAS EXPIRED.
 PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA FOR
 THE PROPOSED SGD.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 NOTE: NOA?S DO NOT HAVE COVER SHEETS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4.SMOKE ALARMS
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314.
  
 5.HOT WATER
 PLEASE PROVIDE THE SOURCE OF HOT WATER PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS. SECTION P2801.1 FBC RES.
 P2801.1REQUIRED.
 HOT WATER SHALL BE SUPPLIED TO PLUMBING FIXTURES AND
 PLUMBING APPLIANCES INTENDED FOR BATHING, WASHING OR
 CULINARY PURPOSES.
  
 6. PROVIDE A SITE PLAN....
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
  
 7. EXTERIOR DOORS/LANDINGS
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-12-08 Cont ID  
Sent By mpeterso Date 2022-12-08 Time 16:08 Rev Time 0.00
Received By mpeterso Date 2022-12-08 Time 15:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-11-07 Cont ID  
Sent By mpeterso Date 2022-11-07 Time 10:31 Rev Time 0.00
Received By mpeterso Date 2022-11-07 Time 14:13 Sent To  
Notes
2022-11-07 10:35:04ELECTRIC REVIEW FAILED
  
 1) ELECTRICAL PLAN IS STILL NOT SIGNED BY THE DESIGN
 PROFFESIONAL. WPB 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-09-30 Cont ID  
Sent By jleahy Date 2022-09-30 Time 13:13 Rev Time 0.00
Received By jleahy Date 2022-09-30 Time 13:08 Sent To  
Notes
2022-09-30 13:16:11PAGE NOT DIGITALLY SIGNED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-29 Cont ID  
Sent By mpeterso Date 2022-08-29 Time 13:37 Rev Time 0.00
Received By mpeterso Date 2022-08-29 Time 13:24 Sent To  
Notes
2022-08-29 13:44:10ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE ELECTRICAL RISER DIAGRAM, ELECTRIC
 SITE PLAN DETAILING ALL ELECTRICAL AND MECHANICHAL
 EQUIPMENT (AIR CONDITIONING EQUIPMENT MAY NOT BE
 REFLECTED AS TO BE DETERMINED) PLEASE REFLECT ALL
 EQUIPMENT IN PANEL SCHEDULES AND LOAD CALCULATIONS
 (RANGE,DRYER,MINI SPLITS AND WATERHEATER LOADS APPEAR
 TO BE INCORRECT AS PER NEC 220) FBC 107.2 NEC 215.5 220
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2022-11-28 Cont ID  
Sent By amhamilt Date 2022-11-28 Time 12:38 Rev Time 0.00
Received By amhamilt Date 2022-11-28 Time 12:38 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2022-10-14 Cont ID  
Sent By amhamilt Date 2022-10-14 Time 10:37 Rev Time 0.00
Received By amhamilt Date 2022-10-14 Time 10:37 Sent To  
Notes
2022-10-14 10:39:19THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 WINDOWS APPROPRIATE FOR PROJECT, HOWEVER, EXTERNAL
 MUNTINS NEED TO BE DIMENSIONAL. LISTED AS ES-1014
 (FLAT), NEEDS TO BE ES- 1015 (OGEE). PLEASE REVISE.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2022-08-25 Cont ID  
Sent By amhamilt Date 2022-08-25 Time 11:14 Rev Time 0.00
Received By amhamilt Date 2022-08-25 Time 11:14 Sent To  
Notes
2022-08-25 11:15:34THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 NOT ENOUGH INFORMATION PROVIDED ABOUT PROPOSED WINDOWS.
 PLEASE SUBMIT ELEVATIONS AND A CONTRACT OR WINDOW
 SCHEDULE FOR WINDOWS, PLEASE ALSO INDICATE GLASS COLOR,
 FRAME COLOR, AND MUNTIN PROFILE
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-12-08 Cont ID  
Sent By mpeterso Date 2022-12-08 Time 16:09 Rev Time 0.00
Received By mpeterso Date 2022-11-29 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-11-28 Cont ID  
Sent By lmarchan Date 2022-11-28 Time 16:15 Rev Time 0.00
Received By lmarchan Date 2022-10-27 Time 15:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-18 Cont ID  
Sent By cthroop Date 2022-10-18 Time 16:48 Rev Time 0.00
Received By cthroop Date 2022-09-22 Time 08:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-03 Cont ID  
Sent By cthroop Date 2022-09-03 Time 08:55 Rev Time 0.00
Received By cthroop Date 2022-08-17 Time 06:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-11-04 Cont ID  
Sent By medwards Date 2022-11-04 Time 10:38 Rev Time 0.00
Received By medwards Date 2022-11-04 Time 10:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-09-23 Cont ID  
Sent By medwards Date 2022-09-23 Time 11:52 Rev Time 0.00
Received By medwards Date 2022-09-23 Time 11:52 Sent To  
Notes
2022-09-23 11:53:26PLEASE ADDRESS PREVIOUS REVIEW COMMENTS BELOW:
  
 SHEET 1 OF 3 INDICATES IN THE GENERAL SCOPE OF WORK
 NOTES THAT THE MECHANICAL SCOPE OF WORK IS TO ADD 5
 ZONE MINI SPLIT SYSTEM AS SHOWN. SHEET M-1 IS A DRAWING
 OF AN AHU WITH DUCTWORK GOING THROUGHOUT THE RESIDENCE
 TO EACH ROOM. WE HAVE NO RECORDS OF A MECHANICAL SYSTEM
 PREVIOUSLY BEING PERMITTED FOR THIS HOME. PROVIDE A
 CORRECTED SCOPE OF WORK FOR THIS MECHANICAL SYSTEM
 INCLUDING THE ENERGY CALCULATIONS, THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS AND AN ACCURATE
 MECHANICAL DRAWING INDICATING WHAT IS BEING INSTALLED
 AT THE RESIDENCE. THE DOCUMENTS SUBMITTED MUST BE
 SIGNED BY THE DESIGNER. FBC 107.3.5
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-08-19 Cont ID  
Sent By medwards Date 2022-08-19 Time 05:23 Rev Time 0.00
Received By medwards Date 2022-08-19 Time 05:23 Sent To  
Notes
2022-08-19 05:33:38SHEET 1 OF 3 INDICATES IN THE GENERAL SCOPE OF WORK
 NOTES THAT THE MECHANICAL SCOPE OF WORK IS TO ADD 5
 ZONE MINI SPLIT SYSTEM AS SHOWN. SHEET M-1 IS A DRAWING
 OF AN AHU WITH DUCTWORK GOING THROUGHOUT THE RESIDENCE
 TO EACH ROOM. WE HAVE NO RECORDS OF A MECHANICAL SYSTEM
 PREVIOUSLY BEING PERMITTED FOR THIS HOME. PROVIDE A
 CORRECTED SCOPE OF WORK FOR THIS MECHANICAL SYSTEM
 INCLUDING THE ENERGY CALCULATIONS, THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS AND AN ACCURATE
 MECHANICAL DRAWING INDICATING WHAT IS BEING INSTALLED
 AT THE RESIDENCE. THE DOCUMENTS SUBMITTED MUST BE
 SIGNED BY THE DESIGNER. FBC 107.3.5
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-11-30 Cont ID  
Sent By ccole Date 2022-11-30 Time 14:39 Rev Time 0.00
Received By ccole Date 2022-11-30 Time 12:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-10-31 Cont ID  
Sent By ccole Date 2022-10-31 Time 11:04 Rev Time 0.00
Received By ccole Date 2022-10-31 Time 10:17 Sent To  
Notes
2022-10-31 11:06:553RD REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22071418
 10/31/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED
  
 1) THE PREVIOUS SHEET 2 PLUMBING PLAN HAS BEEN
 ABANDONED. THE NEW SANITARY ISOMETRICS ON NEW SHEET 3
 ARE MISLABELED AS SUPPLY ISOMETRICS AND HAVE THE
 FOLLOWING DEFICIENCIES-
  
 A) THERE IS ONLY ONE EXISTING VENT SHOWN FOR BOTH THE
 MASTER BATHROOM AND KITCHEN FIXTURES- SEC. P3101.2.1
 FBC RES. PROVIDE A HORIZONTAL WET VENT FOR THE BATHROOM
 FIXTURES IN ACCORDANCE WITH SEC. P3108.1. THE LAVATORY
 VENT CAN SERVE AS THE VENT FOR ALL THE BATHROOM
 FIXTURES PROVIDING THAT THE LAVATORY FIXTURE DRAIN
 CONNECTS AT A POINT UPSTREAM OF THE OTHER FIXTURE DRAIN
 CONNECTIONS, WITH THE EXCEPTION OF ONE FIXTURE
 PERMITTED TO BE CONNECTED UPSTREAM OF THE LAV DRAIN
 CONNECTION- SEC. P3108.2.1. THE CURRENT PLAN SHOWS TWO
 FIXTURES LABELED AS TOILETS CONNECTING UPSTREAM. ONE OF
 THE FIXTURES SHOULD BE LABELED SHOWER.
  
 B) THE DRAIN FROM THE DISHWASHER TYPICALLY CONNECTS TO
 THE SINK DRAIN VIA AN AIR GAP AND ONE SINGLE VENT SHALL
 BE PROVIDED FOR BOTH OF THE FIXTURES. THE SINK FIXTURE
 DRAIN SHALL CONNECT TO THE EXISTING BUILDING DRAIN
 DOWNSTREAM OF THE BATHROOM WET VENT- SECS. P2717.1,
 P2717.2, P3107.1 & P3108.2.1.
  
 C) NO VENTING IS SHOWN FOR THE FIXTURES IN THE HALL
 BATHROOM. REFER TO COMMENT 1A ABOVE FOR CODE SECTIONS
 TO REVIEW AND REVISE THE RISER ACCORDINGLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-09-23 Cont ID  
Sent By ccole Date 2022-09-23 Time 15:57 Rev Time 0.00
Received By ccole Date 2022-09-23 Time 15:27 Sent To  
Notes
2022-09-23 15:59:252ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22071418
 9/23/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW ARE LISTED BELOW. NO CORRECTED PLUMBING PLANS
 WERE UPLOADED FOR REVIEW.
  
 1) SHEET 3: PROVIDE PLUMBING RISER DRAWINGS- SEC.
 107.3.5.3 WPB.
  
 2) SHEET 3: SHOW THE REQUIRED SHOWER PAN LINER AND
 LINER SLOPE IN THE DETAIL- SEC. P2801.1 FBC RES.
  
 3) SHEET 3: SHOW THE SOURCE OF THE HOT WATER- EXISTING
 OR REPLACED WATER HEATER- SEC. P2709.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-08-19 Cont ID  
Sent By ccole Date 2022-08-19 Time 10:01 Rev Time 0.00
Received By ccole Date 2022-08-19 Time 09:46 Sent To  
Notes
2022-08-19 10:02:312ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22071418
 8/19/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3: PROVIDE PLUMBING RISER DRAWINGS- SEC.
 107.3.5.3 WPB.
  
 2) SHEET 3: SHOW THE REQUIRED SHOWER PAN LINER AND
 LINER SLOPE IN THE DETAIL- SEC. P2801.1 FBC RES.
  
 3) SHEET 3: SHOW THE SOURCE OF THE HOT WATER- EXISTING
 OR REPLACED WATER HEATER- SEC. P2709.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status N Date 2022-12-08 Cont ID  
Sent By mpeterso Date 2022-12-08 Time 16:08 Rev Time 0.00
Received By mpeterso Date 2022-12-08 Time 16:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-11-23 Cont ID  
Sent By cthroop Date 2022-11-23 Time 15:45 Rev Time 0.00
Received By cthroop Date 2022-11-23 Time 11:03 Sent To  
Notes
2022-11-23 15:46:03ALL PLAN PAGES SIGNED BY CONTRACTORS. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-10-18 Cont ID  
Sent By cthroop Date 2022-10-18 Time 16:44 Rev Time 0.00
Received By cthroop Date 2022-10-18 Time 16:32 Sent To  
Notes
2022-10-18 16:46:502ND SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
2022-09-30 13:17:12ELECTRICAL PLAN NOT SIGNED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-19 Cont ID  
Sent By medwards Date 2022-08-19 Time 05:33 Rev Time 0.00
Received By medwards Date 2022-08-19 Time 05:33 Sent To  
Notes
2022-08-19 05:34:40THE DRAWINGS MUST BE DIGITALLY SIGNED BY THE DESIGNER.
 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2022-11-28 Cont ID  
Sent By amhamilt Date 2022-11-28 Time 12:56 Rev Time 0.00
Received By amhamilt Date 2022-11-28 Time 12:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-10-14 Cont ID  
Sent By amhamilt Date 2022-10-14 Time 10:39 Rev Time 0.00
Received By amhamilt Date 2022-10-14 Time 10:39 Sent To  
Notes
2022-10-14 10:39:46NO LANDSCAPE PERMIT IN REVIEW SYSTEM, SEE PREVIOUS
 COMMENT.

Review Stop Z ZONING
Rev No 1 Status F Date 2022-08-25 Cont ID  
Sent By ahamilto Date 2022-08-25 Time 11:17 Rev Time 0.00
Received By amhamilt Date 2022-08-25 Time 11:17 Sent To  
Notes
2022-08-25 11:17:48THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 THE VALUE OF CONSTRUCTION EXCEEDS 50% OF THE
 IMPROVEMENT VALUE OF THE STRUCTURE, THEREFORE A
 SEPERATE LANDSCAPE PERMIT IS REQUIRED AND MUST BE
 SUBMITTED FOR ZONING APPROVAL TO MOVE FORWARD
  
 SEC 94-441 (B)
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  