| Plan Review Stops For Permit 22071347 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2023-01-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-13 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-13 |
Time |
10:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-05 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-05 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2022-10-05 10:16:30 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2023-02-02 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-02 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-02 |
Time |
10:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-01-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-13 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-13 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2023-01-13 11:17:01 | REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE FRONT PAGE FOR THE FL23301 | | | PRODUCT APPROVAL (FLORIDA STATE FRONT PAGE) | | | | | | 2) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | | APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED | | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | | ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE | | | THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-82.5) | | | - SEE NOTE NUMBER 9 ON THE PRODUCT APPROVAL. | | | | | | 3) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE LIGHT | | | WEIGHT CONCRETE - FBC 1917.2.1 | | | APPLICATION OF ALL LIGHTWEIGHT INSULATING CONCRETE ROOF | | | DECKS SHALL BE BY APPLICATORS APPROVED BY THE | | | LIGHT-WEIGHT INSULATING CONCRETE DECK MANUFACTURER. | | | PRODUCT APPROVAL SHALL BE REQUIRED FOR ALL LIGHTWEIGHT | | | INSULATING CONCRETE SYSTEMS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-05 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-05 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2022-10-05 10:14:44 | RENOVATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) OUTSIDE PORTABLE VAULT IS SUBJECT TO WIND LOADS - | | | PLEASE PROVIDE SIGNED AND SEALED VAULT DRAWINGS FROM A | | | DESIGN PROFESSIONAL OR PROVIDE STATE APPROVED PRODUCT | | | APPROVAL FOR THE VAULT FBC 1609 SEE FBC 107.3 | | | | | | 2) PLEASE SHOW THE WIND DESIGN CRITERIA USED FOR THE | | | WIND DESIGN FBC 1603.1.4 | | | | | | 3) DRAWING A-402 - WIND DESIGN SHOWN RISK CAT. II WIND | | | SPEED 168 MPH - WIND SPEED FOR A RISK CAT. II IS 170 | | | MPH SEE FBC WPB SECTION 120 | | | | | | 4) SHOULD THE WIND DESIGN CRITERIA BE - FBC TABLE | | | 1604.5 RISK CAT. IV WITH WIND SPEED 180 MPH :BUILDINGS | | | AND OTHER STRUCTURES HAVING CRITICAL NATIONAL DEFENSE | | | FUNCTIONS. | | | | | | 5) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE - FBC | | | 602.1 | | | | | | 6) PLEASE SHOW IF THE BUILDING IS - NON SPRINKLERED OR | | | SPRINKLERED. | | | | | | 7) PLEASE SHOW THE PROPOSED RAMP SLOPES - HAND RAILS | | | MAY BE REQUIRED - FBC 405.8 HANDRAILS. | | | RAMP RUNS WITH A RISE GREATER THAN 6 INCHES (150 MM) | | | SHALL HAVE HANDRAILS COMPLYING WITH 505. | | | | | | 8) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVAL FOR THE ROOFING SYSTEMS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-09-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-09-27 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-09-27 |
Time |
14:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2023-02-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2023-02-13 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-12-30 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-12-30 |
Time |
|
Rev Time |
|
| Received By |
bdolan |
Date |
2022-12-30 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2022-12-30 14:32:38 | THIS PLAN WAS REVIEWED AND APPROVED BY CAPT. BRIAN | | | DOLAN, DIVISION OF FIRE PREVENTION, WITH THE FOLLOWING | | | COMMENTS: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL | | | AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR | | | CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS. | | | | | | ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND | | | SHOP DRAWINGS BY CERTIFIED CONTRACTORS. | | | | | | THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL REMAIN | | | ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION PERIODS. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | CAPT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-08-25 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-08-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
bdolan |
Date |
2022-08-19 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2022-08-25 10:48:12 | THIS PLAN WAS REVIEWED AND APPROVED BY LT. BRIAN DOLAN, | | | DIVISION OF FIRE PREVENTION, WITH THE FOLLOWING | | | COMMENTS: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL | | | AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR | | | CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS. | | | | | | ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND | | | SHOP DRAWINGS BY CERTIFIED CONTRACTORS. | | | | | | THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL REMAIN | | | ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION PERIODS. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-02-14 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-02-14 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-02-01 |
Time |
15:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-01-26 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-01-26 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-01-26 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-05 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-17 |
Time |
08:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-05 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-05 |
Time |
10:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2023-02-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-07 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-07 |
Time |
13:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2023-01-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-01-11 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-01-11 |
Time |
17:12 |
Sent To |
|
|
| Notes |
| 2023-01-11 17:14:52 | PROVIDE THE AIR PURIFICATION DEVICE CALCULATIONS. FOR | | | EACH UNIT, ALSO LABEL THEM ON THE DRAWINGS. FMC 403.2 | | | EXCEPTION | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-09-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-14 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-14 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2022-09-14 12:37:20 | 1ST REVIEW FMC | | | PERMIT: 22071347 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE SHOW HOW YOU WILL BE PROTECTING THE CORRIDOR | | | FROM SMOKE. FMC 601.2.1 | | | | | | 2) SHEETS M-202 AND M-203: PLEASE SHOW THE REQUIRED | | | DUCT SMOKE DETECTORS FOR THE REPLACED AHU???S. FMC | | | 606.2.1 | | | | | | 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS AND THE | | | AIR PURIFICATION REDUCTION CALCULATIONS FOR THIS | | | PROJECT. FBC 107.3.5 | | | | | | 4) SHEET M-203: THE FIRE DAMPER FOR VAV-9-02 IS IN THE | | | WRONG LOCATION, IT IS IN THE CORRIDOR AND NOT AT THE | | | WALL. PLEASE SHOW THIS FIRE DAMPER IN THE CORRECT | | | LOCATION. | | | | | | 5) SHEET M-203: PLEASE SHOW THE FIRE DAMPER FOR THE 10 | | | INCH DUCT SUPPLYING AIR TO THE VAV-9-08 AND VAV-9-05 | | | | | | 6) PLEASE SHOW THE FIRE DAMPERS WHERE THE MAIN TRUNK | | | LINES, SUPPLY AND RETURN, FOR AHU-8 AND AHU-9 PENETRATE | | | THE RATED WALLS AT THE MECHANICAL ROOMS AND CORRIDOR. | | | FBC 607 | | | | | | 7) PLEASE IDENTIFY THE EF-3-1 AND EF-7-1 ON THE | | | DRAWINGS. FBC 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-09-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-14 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-14 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2023-02-02 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-02 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-02 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2023-02-02 10:12:50 | A SEPARATE ROOFING PERMIT - 23010590 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2023-01-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-13 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-13 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2023-01-13 11:17:41 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-05 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-05 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2022-10-05 10:15:31 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-02-02 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-02 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-02 |
Time |
10:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-01-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-13 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-13 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2023-01-11 17:16:12 | MECHANICAL DIGITAL SIGNATURES APPROVED ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-05 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-05 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2022-09-27 15:01:49 | ELECTRICAL SIGNATURES APPROVED JLEAHY | | 2022-09-14 12:38:11 | MECHANICAL DIGITAL SIGNATURES APPROVED ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-02-10 |
|
|
Cont ID |
|
| Sent By |
VBroglia |
Date |
2023-02-10 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-02-10 |
Time |
16:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-01-26 |
|
|
Cont ID |
|
| Sent By |
ASangele |
Date |
2023-01-26 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-01-26 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2022-08-22 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-08-22 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-10-26 |
Time |
10:22 |
Sent To |
|
|
| Notes |
| 2022-10-26 10:23:29 | APPLICANT PROVIDED AN APPRIASAL SHOWING THAT THE | | | RENOVATIONS DO NOT EXCEED THE 50% THRESHOLD. | | | | | | ALEXANDER FOWLKES | | | [email protected] | | | 5618221431 | | 2022-08-22 11:24:06 | THE EXTERIOR IMPROVEMENTS (FENCES ETC.) REQUIRE | | | SEPERATE PERMITS | | | | | | THE VALUE OF THE CONSTRUCTION ($3,468,920) EXCEEDS 50% | | | OF THE STRUCTURE'S VALUE ($$3,812,893) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | | | | ALEXANDER FOWLKES | | | [email protected] | | | 5618221431 |
|
|