Plan Review Details - Permit 22071337
Plan Review Stops For Permit 22071337
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-09-26 Cont ID  
Sent By cthroop Date 2022-09-26 Time 17:23 Rev Time 0.00
Received By cthroop Date 2022-09-26 Time 15:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-09-02 Cont ID  
Sent By shill Date 2022-09-02 Time 12:33 Rev Time 0.00
Received By shill Date 2022-09-02 Time 12:33 Sent To  
Notes
2022-09-02 12:36:18[email protected]
 [email protected]
  
 1. PLEASE SUBMIT FLOOR PLAN SKETCH WITH LOCATION OF
 PROPOSED WORK. FBC 107.2
 2. PLEASE SUBMIT COMPLETE PRODUCT APPROVAL FOR DOORS
 WITH DESIGN PRESSURES NOTED. FBC 107.2
 3. SUBMIT A FLASHING DETAIL FBC BUILDING 1404.5.
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2022-09-27 Cont ID  
Sent By rrossano Date 2022-09-27 Time   Rev Time 0.00
Received By rrossano Date 2022-09-27 Time   Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-09-15 Cont ID  
Sent By pleduc Date 2022-09-15 Time   Rev Time 0.00
Received By pleduc Date 2022-09-15 Time 10:03 Sent To  
Notes
2022-09-15 10:07:31FIRE PROVISO:
  
 ENSURE EXIT SIGN IS OVER THE NEW EXIT DOOR.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-09-06 Cont ID  
Sent By pleduc Date 2022-09-06 Time   Rev Time 0.00
Received By pleduc Date 2022-09-06 Time 15:01 Sent To  
Notes
2022-09-06 15:08:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO FLOOR PLAN/SITE PLAN THAT INDICATES
 WHERE THE PRPOSED WILL BE INSTALLED.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 SHOULD THE PROPOSED RESTRICT EGRESS OF A REQUIRED EXIT
 DOOR WHEN NOT INSTALLED FOR HURRICANE WEATHER, PLEASE
 PROVIDE FOR THE REQUIRED EXIT HARDWARE AND SIGNAGE.
  
 IF THIS WORK IS TO BE DONE BY OTHERS PLEASE PROVIDE AA
 APPLICABLE NOTE.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-27 Cont ID  
Sent By lmarchan Date 2022-09-27 Time 15:07 Rev Time 0.00
Received By lmarchan Date 2022-09-09 Time 08:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-06 Cont ID  
Sent By lmarchan Date 2022-09-06 Time 15:33 Rev Time 0.00
Received By lmarchan Date 2022-08-18 Time 05:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-26 Cont ID  
Sent By cthroop Date 2022-09-26 Time 17:19 Rev Time 0.00
Received By cthroop Date 2022-09-26 Time 15:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-09-02 Cont ID  
Sent By shill Date 2022-09-02 Time 12:36 Rev Time 0.00
Received By shill Date 2022-09-02 Time 12:36 Sent To  
Notes
***NONE***