| 2022-08-10 11:27:21 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22071308 |
| | 8/10/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-2.0A: THE PLAN IS UNACCEPTABLE FOR REVIEW |
| | BECAUSE IT A MARKED UP, ILLEGIBLE COPY OF THE |
| | ENGINEER'S SIGNED AND SEALED PLAN SEC. 107.2.1 WPB. THE |
| | PLAN ALSO SHOWS THE LOCATIONS OF THE G1 & G2 |
| | INTERCEPTORS HAVE BEEN CHANGED FROM THEIR ORIGINAL |
| | LOCATIONS AT THE SOUTH SIDE OF THE BUILDING AS SHOWN IN |
| | THE MOST RECENT PLAN REVISION- 3A DATED 6/24/22. THE |
| | ENGINEER OF RECORD SHALL PROVIDE A DIGITALLY SIGNED AND |
| | SEALED REVISED PLAN SHOWING THE NEW INTERCEPTOR |
| | LOCATIONS- SEC. 107.2.1 WPB AND FL. STATUTE 471.025 & |
| | FAC 61G15-23.005. |
| | |
| | 2) THE FLORIDA SEPTIC PRODUCT SPECIFICATIONS INDICATING |
| | COMPLIANCE WITH 2001 FL. PLUMBING CODE AND FAC RULE |
| | 64E-6.013 MARCH 22, 2001 ARE OUTDATED. PLEASE NOTE THE |
| | ENGINEER OF RECORD HAS SPECIFIED OLD CASTLE |
| | INTERCEPTORS TO BE INSTALLED AS SHOWN ON SHEET P-0.1 |
| | APPROVED UNDER THE MASTER PERMIT 20120712. PLEASE |
| | SUBMIT UP-TO-DATE SPECIFICATIONS BEARING THE APPROVAL |
| | STAMP OF THE ENGINEER OF RECORD- SEC. 107.3.4.1 WPB. |
| | PLEASE NOTE IN ACCORDANCE WITH SEC.1003.3.7 FBC P- THE |
| | INTERCEPTOR PRODUCT SPECIFICATIONS SHALL INDICATE THEY |
| | HAVE BEEN DESIGNED AND TESTED IN ACCORDANCE WITH |
| | IAPMO/ANSI Z1001. |
| | |
| | 3) THE ENGINEER OF RECORD SHALL PROVIDE A PIPING |
| | DIAGRAM FOR THE INTERCEPTORS CONSISTENT WITH SEC. 301.3 |
| | FBC PLUMBING -2020 CODE.THE MARKED UP, OUTDATED |
| | SPECIFICATIONS SHOWING PIPING INLETS, OUTLETS, AND |
| | CLEANOUTS ARE UNACCEPTABLE FOR REVIEW- SEC.107.2.1 WPB. |
| | IN LIEU OF ENGINEERING, THE CONTRACTOR OF RECORD MAY |
| | SUBMIT A SUPPLEMENTAL PIPING DIAGRAM CLEARLY DRAWN TO |
| | MINIMUM 1/8-INCH SCALE. THE PLAN SHALL BEAR THE PRINTED |
| | NAME, LICENSE NUMBER AND SIGNATURE OF THE CONTRACTOR |
| | AND ALSO THE ADDRESS OF THE PROJECT. |
| | |
| | 4) SUBMIT ADDITIONAL SPECIFICATIONS FOR THE TRAFFIC |
| | LIDS THAT BEAR THE NAME OF THE MANUFACTURER AND MODEL |
| | NUMBER OF THE LIDS. THE SPECS SHALL SHOW THE LIDS FOR |
| | BOTH THE MANHOLES AND THE SAMPLING PORTS ARE H-20 HEAVY |
| | DUTY TRAFFIC RATED- SEC. 107.2.1 WPB. THE SPECS SHALL |
| | BEAR THE APPROVAL STAMP OF THE ENGINEER OF RECORD- SEC. |
| | 107.3.4.1 WPB. |
| | |
| | 5) PROVIDE SIZING CALCULATIONS FOR THE INTERCEPTORS- |
| | SEC. 1003.3.7 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |