Plan Review Details - Permit 22071259
Plan Review Stops For Permit 22071259
Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-12-16 Cont ID  
Sent By cwalker Date 2022-12-16 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-10-17 Cont ID  
Sent By cwalker Date 2022-10-17 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-09-02 Cont ID  
Sent By cwalker Date 2022-09-02 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-08-09 Cont ID  
Sent By cwalker Date 2022-08-09 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-12-21 Cont ID  
Sent By medwards Date 2022-12-21 Time 11:29 Rev Time 0.00
Received By medwards Date 2022-12-15 Time 09:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-12-02 Cont ID  
Sent By medwards Date 2022-12-02 Time 14:22 Rev Time 0.00
Received By medwards Date 2022-11-29 Time 16:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-11-03 Cont ID  
Sent By medwards Date 2022-11-03 Time 16:10 Rev Time 0.00
Received By medwards Date 2022-10-19 Time 07:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-18 Cont ID  
Sent By medwards Date 2022-10-18 Time 14:51 Rev Time 0.00
Received By medwards Date 2022-10-14 Time 08:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-07 Cont ID  
Sent By medwards Date 2022-09-07 Time 13:01 Rev Time 0.00
Received By medwards Date 2022-09-01 Time 14:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-18 Cont ID  
Sent By medwards Date 2022-08-18 Time 11:36 Rev Time 0.00
Received By medwards Date 2022-08-08 Time 07:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2022-12-21 Cont ID  
Sent By medwards Date 2022-12-21 Time 11:29 Rev Time 0.00
Received By medwards Date 2022-12-21 Time 11:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2022-12-02 Cont ID  
Sent By medwards Date 2022-12-02 Time 14:21 Rev Time 0.00
Received By medwards Date 2022-12-02 Time 14:21 Sent To  
Notes
2022-12-02 14:22:195TH REVIEW FMC
 PERMIT: 22071259
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) I AM STILL TRYING TO GET THE ANSWER TO COMMENT 1 OF
 PREVIOUS REVIEW CYCLE. THE PERMIT NUMBER THAT WAS GIVEN
 IN REFERENCE TO SHEET A8.0.1 IS THIS PERMIT NUMBER.
 THERE ARE NO A SHEETS IN THIS SUBMITTAL AND THERE ARE A
 LOT OF A SHEETS FOR THIS BUILDING, A LOT FOR EACH
 PERMIT FOR THIS BUILDING AND BUILDOUTS. I AM ASKING FOR
 YOU TO EITHER SUBMIT SHEET A8.0.1 AS A REFERENCE ONLY
 SHEET OR TELL ME THE PERMIT NUMBER OF THE A.8.0.1 THAT
 YOU ARE REFERENCING SO I CAN FIND IT MYSELF.
  
 2) THE LETTER SUBMITTED FROM MR. ERIC CHAPA FROM
 CAPTIVEAIRE ONLY STATES WHAT THE FMC STATES: SUCH ROOM
 OR SPACES SHALL BE VENTILATED IN ACCORDANCE WITH THE
 FAN MANUFACTURERS INSTALLATION INSTRUCTIONS. PLEASE
 PROVIDE THIS INFORMATION FROM THE FAN MANUFACTURER. THE
 REVISED DRAWING REFERENCES NOTE 10 (COOLING TUBE TO
 MOTOR COMPARTMENT, BOTH SIDES) PLEASE PROVIDE A DETAIL
 DRAWING OF THIS. PLEASE PROVIDE THE INSTALLATION
 INSTRUCTIONS FOR THE GREASE DUCT IN-LINE FAN. FMC
 506.5.1.2
  
 3) PLEASE SUBMIT A REVISION FOR THE NEW PIZZA OVENS AND
 THE DUCTWORK THAT IS NOW ON THE NEW SHEETS ADDED TO
 THIS SUBMITTAL; MKH-502 AND MKH-503, INCLUDE THE ADDED
 VALUE TO THIS REVISION.
  
 4) PROVIDE A DESIGN FOR THE PIZZA OVENS DUCTWORK. IS
 THE DUCTWORK FOR THESE PIZZA OVEN TO BE FIRE WRAPPED?
 FBC 107.3.5
  
 5) PROVIDE SPECS FOR THE PIZZA OVENS THAT ARE SHOWN ON
 THE NEW SHEETS MKH-502 AND MKH-503 ALSO PROVIDE
 INFORMATION FOR THE DUCT WORK FOR THESE 2 PIZZA OVENS.
 THE KITCHEN FAN SCHEDULE LISTED ON MKH-503 INDICATES
 THE DUCT SIZE CONNECTION AS 6 INCH BUT THE DUCTWORK
 SHOWN ON MKH-502 INDICATES THE DUCTWORK TO BE 8 INCH.
 PLEASE EXPLAIN?
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2022-11-03 Cont ID  
Sent By medwards Date 2022-11-03 Time 16:09 Rev Time 0.00
Received By medwards Date 2022-11-03 Time 16:09 Sent To  
Notes
2022-11-03 16:09:451ST REVIEW FMC
 PERMIT: 22071259
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE PERMIT NUMBER FOR THIS A8.0.1
 THAT IS REFERENCED IN THE RESPONSE LETTER. IF THIS
 ENCLOSURE IS LOCATED IN A PLENUM IT CANNOT BE ALLOWED
 TO ???BREATHE WITH THE PLENUM AIR.??? THE IN LINE FAN
 WILL NEED TO MEET THE REQUIREMENTS OF FMC 506.5.1.2
  
 506.5.1.2 IN-LINE FAN LOCATION. WHERE ENCLOSED DUCT
 SYSTEMS ARE CONNECTED TO IN-LINE FANS NOT LOCATED
 OUTDOORS,
 THE FAN SHALL BE LOCATED IN A ROOM OR SPACE HAVING THE
 SAME FIRE-RESISTANCE RATING AS THE DUCT ENCLOSURE.
 ACCESS SHALL BE PROVIDED FOR SERVICING AND CLEANING OF
 FAN COMPONENTS. SUCH ROOMS OR SPACES SHALL BE
 VENTILATED
 IN ACCORDANCE WITH THE FAN MANUFACTURER???S
 INSTALLATION INSTRUCTIONS.
  
 2) PROVIDE THE DOCUMENT THAT SHOWS THE TENANT ACCESS
 AGREEMENT FMC 306.1
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-10-18 Cont ID  
Sent By medwards Date 2022-10-18 Time 14:39 Rev Time 0.00
Received By medwards Date 2022-10-18 Time 14:39 Sent To  
Notes
2022-10-18 14:42:53PLEASE ADDRESS THE COMMENTS FROM THE PREVIOUS REVIEWS
 LISTED BELOW:
  
 1) PROVIDE THE ARCHITECTURAL SHEETS CALLED OUT IN NOTE
 1. NOTE 2, PROVIDE A DETAIL DRAWING OF THIS ACCESS
 DOOR. OR REFERENCE WHICH A SHEET THE DETAIL IS LOCATED.
  
 2) ACCORDING TO THIS DESIGN FOR THE HOOD EXHAUST AND
 DISHWASHER EXHAUST, THE DUCTWORK IS TRAVELING THROUGH A
 FUTURE TENANT SPACE, MEDICAL OFFICE, PLEASE EXPLAIN HOW
 THIS GREASE DUCT WILL BE ACCESSIBLE FOR CLEANING AND
 MAINTAINING. FBC 107.3.5
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-09-07 Cont ID  
Sent By medwards Date 2022-09-07 Time 12:55 Rev Time 0.00
Received By medwards Date 2022-09-07 Time 12:55 Sent To  
Notes
2022-09-07 12:55:552ND REVIEW FMC
 PERMIT: 22071259
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 DRAWING 3 OF 4: KITCHEN HOOD EXHAUST FAN 2 HOUR RATED
 SHAFT DETAIL:
  
 1) PLEASE PROVIDE A MORE DETAILED DRAWING OF THIS RATED
 BOX THAT WILL ENCLOSE THE KEF-1. EXPLAIN WHY THE FIRE
 DAMPERS ARE IN THIS DESIGN. PROVIDE THE ARCHITECTURAL
 SHEETS CALLED OUT IN NOTE 1. NOTE 2, PROVIDE A DETAIL
 DRAWING OF THIS ACCESS DOOR. NOTE 8 STATES THE 2-HOUR
 FIRE WRAP SHALL TERMINATE TO 2- HOUR GYPSUM BOARD
 ENCLOSURE BUT THE INSTALLATION DETAIL FOR TRANSITION TO
 RATED SHAFT DETAIL DOES NOT SHOW THIS. PLEASE PRESENT
 CONSISTENT DETAILS. THE INSTALLATION DETAIL FOR
 TRANSITION TO RATED SHAFT DETAIL DOES NOT SHOW THAT
 NOTE 5 IS BEING USED, SHOW THE BANDING OR REMOVE THIS
 NOTE 5. THERE IS A 6 ON THE DESIGN DRAWING BUT THIS
 NUMBER 6 IS NOT LISTED, EXPLAIN WHAT THIS 6 IS
 REFERENCING. FBC107.3.5
  
 2) ACCORDING TO THIS DESIGN FOR THE HOOD EXHAUST AND
 DISHWASHER EXHAUST, THE DUCTWORK IS TRAVELING THROUGH A
 FUTURE TENANT SPACE, MEDICAL OFFICE, PLEASE EXPLAIN HOW
 THIS GREASE DUCT WILL BE ACCESSIBLE FOR CLEANING AND
 MAINTAINING. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-08-18 Cont ID  
Sent By medwards Date 2022-08-18 Time 11:10 Rev Time 0.00
Received By medwards Date 2022-08-18 Time 11:10 Sent To  
Notes
2022-08-18 11:35:161) PROVIDE THE FIELD APPLIED GREASE DUCT ENCLOSURE
 SPECIFICATIONS. FMC 506.3.11.2
  
 2) PROVIDE DETAILS FOR THE KEF-1 HOOD EXHAUST FAN AND
 HOW THIS INSTALLATION WILL MEET THE PROTECTION
 REQUIREMENTS OF FMC 506.5.1.2
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-09-07 Cont ID  
Sent By medwards Date 2022-09-07 Time 13:01 Rev Time 0.00
Received By medwards Date 2022-09-07 Time 13:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-12-21 Cont ID  
Sent By medwards Date 2022-12-21 Time 11:29 Rev Time 0.00
Received By medwards Date 2022-12-21 Time 11:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-12-02 Cont ID  
Sent By medwards Date 2022-12-02 Time 14:22 Rev Time 0.00
Received By medwards Date 2022-12-02 Time 14:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-10-18 Cont ID  
Sent By medwards Date 2022-10-18 Time 14:51 Rev Time 0.00
Received By medwards Date 2022-10-18 Time 14:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-07 Cont ID  
Sent By medwards Date 2022-09-07 Time 12:58 Rev Time 0.00
Received By medwards Date 2022-09-07 Time 12:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-08-18 Cont ID  
Sent By medwards Date 2022-08-18 Time 11:36 Rev Time 0.00
Received By medwards Date 2022-08-18 Time 11:36 Sent To  
Notes
***NONE***