Plan Review Details - Permit 22071250
Plan Review Stops For Permit 22071250
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-10-21 Cont ID  
Sent By rmcdouga Date 2022-10-21 Time 13:26 Rev Time 0.00
Received By rmcdouga Date 2022-10-21 Time 13:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-10-14 Cont ID  
Sent By rmcdouga Date 2022-10-14 Time 16:12 Rev Time 0.00
Received By rmcdouga Date 2022-10-14 Time 15:30 Sent To  
Notes
2022-10-14 16:12:35PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [ THE PREVIOUS 2 COMMENTS HAVE NOT BEEN RESOLVED.
 THE ANCHOR SIZES AND EMBED DEPTHS FOR THE POOL HEATER
 HAVE NOT BEEN PROVIDED. THE HEATER DOCUMENTS THAT WERE
 SUBMITTED REFER TO A BOLT DOWN KIT, BUT DOES NOT
 SPECIFY THE SIZE, NUMBER, LOCATIONS AND EMBED DEPTHS OF
 THE ANCHORS. ] THE POOL EQUIPMENT IS REQUIRED TO BE
 ANCHORED TO RESIST WINDLOADS AND FLOOD WATER FORCES.
 SPECIFY THE FASTNER TYPE, SIZE, LOCATIONS AND EMBED
 DEPTHS. FBC-R301
  
 2) [ THE PREVIOUS 2 COMMENTS HAVE NOT BEEN RESOLVED.
 THE POOL EQUIPMENT PAD IS SPECIFIED AS 7.0' NAVD. I
 COULD NOT CLEARLY READ THE ELEVATION OF THE RESIDENCE
 BUT IT APPEARED TO BE MORE THAT 7-0' NAVD. THE POOL
 EQUIPMENT IS REQUIRED TO BE AT OR ABOVE THE ELEVATION
 OF THE HABITABLE ARE OF THE RESIDENCE.] THE PROJECT IS
 LOCATED IN A SPECIAL FLOOD HAZARD AREA. THE POOL
 EQUIPMENT IS REQUIRED TO COMPLY WITH FBC-R 322.1.6.
 EQUIPMENT FOR POOLS, SPAS AND WATER FEATURES SHALL BE
 PERMITTED BELOW THE ELEVATION REQUIRED IN SECTION
 R322.2 OR R322.3 PROVIDED IT IS ELEVATED TO THE EXTENT
 PRACTICAL, IS ANCHORED TO PREVENT FLOTATION AND RESIST
 FLOOD FORCES, AND IS SUPPLIED BY BRANCH CIRCUITS THAT
 HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-09-21 Cont ID  
Sent By rmcdouga Date 2022-09-21 Time 14:10 Rev Time 0.00
Received By rmcdouga Date 2022-09-21 Time 14:10 Sent To  
Notes
2022-09-21 14:26:00PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [ THE PREVIOUS COMMENT WAS NOT RESOLVED.] THE POOL
 EQUIPMENT IS REQUIRED TO BE ANCHORED TO RESIST
 WINDLOADS AND FLOOD WATER FORCES. SPECIFY THE FASTNER
 TYPE, SIZE, LOCATIONS AND EMBED DEPTHS. FBC-R301
  
 2) [ THE PREVIOUS COMMENT WAS NOT RESOLVED.]THE PROJECT
 IS LOCATED IN A SPECIAL FLOOD HAZARD AREA. THE POOL
 EQUIPMENT IS REQUIRED TO COMPLY WITH FBC-R 322.1.6.
 EQUIPMENT FOR POOLS, SPAS AND WATER FEATURES SHALL BE
 PERMITTED BELOW THE ELEVATION REQUIRED IN SECTION
 R322.2 OR R322.3 PROVIDED IT IS ELEVATED TO THE EXTENT
 PRACTICAL, IS ANCHORED TO PREVENT FLOTATION AND RESIST
 FLOOD FORCES, AND IS SUPPLIED BY BRANCH CIRCUITS THAT
 HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-31 Cont ID  
Sent By rmcdouga Date 2022-08-31 Time 09:34 Rev Time 0.00
Received By rmcdouga Date 2022-08-31 Time 09:34 Sent To  
Notes
2022-08-31 09:24:52PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE POOL EQUIPMENT IS REQUIRED TO BE ANCHORED TO
 RESIST WINDLOADS AND FLOOD WATER FORCES. SPECIFY THE
 FASTNER TYPE, SIZE, LOCATIONS AND EMBED DEPTHS.
 FBC-R301
  
 2) THE PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA. THE POOL EQUIPMENT IS REQUIRED TO COMPLY WITH
 FBC-R 322.1.6. EQUIPMENT FOR POOLS, SPAS AND WATER
 FEATURES SHALL BE PERMITTED BELOW THE ELEVATION
 REQUIRED IN SECTION R322.2 OR R322.3 PROVIDED IT IS
 ELEVATED TO THE EXTENT PRACTICAL, IS ANCHORED TO
 PREVENT FLOTATION AND RESIST FLOOD FORCES, AND IS
 SUPPLIED BY BRANCH CIRCUITS THAT HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By ppetty Date 2022-09-21 Time 12:48 Rev Time 0.00
Received By ppetty Date 2022-09-21 Time 11:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-07 Cont ID  
Sent By jleahy Date 2022-08-07 Time 19:18 Rev Time 0.00
Received By jleahy Date 2022-08-07 Time 19:18 Sent To  
Notes
2022-08-07 19:19:45FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE LOAD CALCULATION FOR 100A POOL PANEL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-21 Cont ID  
Sent By rmcdouga Date 2022-10-21 Time 13:26 Rev Time 0.00
Received By rmcdouga Date 2022-10-21 Time 12:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-14 Cont ID  
Sent By rmcdouga Date 2022-10-14 Time 16:12 Rev Time 0.00
Received By rmcdouga Date 2022-10-07 Time 08:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-21 Cont ID  
Sent By asangele Date 2022-09-21 Time 16:18 Rev Time 0.00
Received By asangele Date 2022-09-21 Time 16:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-31 Cont ID  
Sent By rmcdouga Date 2022-08-31 Time 09:35 Rev Time 0.00
Received By rmcdouga Date 2022-07-29 Time 08:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-10-21 Cont ID  
Sent By rwbrown Date 2022-10-21 Time 12:54 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-10-11 Cont ID  
Sent By rwbrown Date 2022-10-11 Time 08:23 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-09-19 Cont ID  
Sent By ccole Date 2022-09-19 Time 14:03 Rev Time 0.00
Received By ccole Date 2022-09-19 Time 13:40 Sent To  
Notes
2022-09-19 14:10:452ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22071250
 9/19/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS #1 & 3 FROM THE
 1ST REVIEW BELOW WERE NOT ADDRESSED.
  
 1) SHEET 4: THE 15.9 HR. POOL WATER TURNOVER RATE AT
 LOW SPEED EXCEEDS THE MAXIMUM 12 HR. RATE SPECIFIED IN
 SEC. 9.1.3 ANSI/APSP/ICC-5 2011.
  
 3) SHEET 4: CORRECT THE EQUIPMENT ANCHORING NOTE
 SPECIFYING MFGR?S NOA. THE NOA DOES NOT EXIST. PLEASE
 PROVIDE ANCHORING METHOD BY MFGR?S SPECIFICATIONS AND
 SHOW THE TYPE AND SIZE OF ANCHOR BOLT OR TAPCON
 INCLUDING DEPTH OF EMBEDMENT AND ANCHOR EDGE DISTANCE
 FROM SLAB END- SEC. R4501.22 FBC RES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-08-01 Cont ID  
Sent By ccole Date 2022-08-01 Time 09:56 Rev Time 0.00
Received By ccole Date 2022-08-01 Time 09:06 Sent To  
Notes
2022-08-01 09:58:071ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22071250
 8/1/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4: THE 15.9 HR. POOL WATER TURNOVER RATE AT
 LOW SPEED EXCEEDS THE MAXIMUM 12 HR. RATE SPECIFIED IN
 SEC. 9.1.3 ANSI/APSP/ICC-5 2011.
  
 2) SHEET 4: PROVIDE THE PUMP CURVE ON THE SHEET MARKED
 UP TO SHOW THE TDH AND FLOW RATES OF THE SYSTEM- SECS.
 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & R4501.7.3
 FBC RES.
  
 3) SHEET 4: CORRECT THE EQUIPMENT ANCHORING NOTE
 SPECIFYING MFGR?S NOA. THE NOA DOES NOT EXIST. PLEASE
 PROVIDE ANCHORING METHOD BY MFGR?S SPECIFICATIONS AND
 SHOW THE TYPE AND SIZE OF ANCHOR BOLT OR TAPCON
 INCLUDING DEPTH OF EMBEDMENT AND ANCHOR EDGE DISTANCE
 FROM SLAB END- SEC. R4501.22 FBC RES.
  
 4) SHEET 1: PLEASE NOTE THE POOL AND SPA ARE BEING
 CONSTRUCTED IN A FLOOD HAZARD AREA. BASED ON THE NOTE
 FOR THE CONCRETE EQUIPMENT PAD, PLEASE PROVIDE THE SITE
 PLAN, AND THE EQUIPMENT PAD ELEVATION HEIGHT- SEC.
 P2601.3 FBC RES.
  
 5) SHEET 4: PLEASE NOTE THAT THE GAS HEATER SHALL BE
 INSTALLED UNDER A SEPARATE PERMIT- SECS. 105.1,
 107.2.1, 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-10-21 Cont ID  
Sent By rmcdouga Date 2022-10-21 Time 13:26 Rev Time 0.00
Received By rmcdouga Date 2022-10-21 Time 13:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-10-14 Cont ID  
Sent By rmcdouga Date 2022-10-14 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2022-10-14 Time 15:30 Sent To  
Notes
2022-10-14 15:41:29DIGITAL SIGNATURES ON PLANS COULD NOT BE VERIFIED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By rmcdouga Date 2022-09-21 Time 14:26 Rev Time 0.00
Received By rmcdouga Date 2022-09-21 Time 14:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-01 Cont ID  
Sent By ccole Date 2022-08-01 Time 10:00 Rev Time 0.00
Received By ccole Date 2022-08-01 Time 09:58 Sent To  
Notes
2022-08-01 10:02:45SIGNATURE REVIEW
 22071250
 8/1/22
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE POOL PLAN SHEETS 1-4 ARE NOT DIGITALLY SIGNED
 AND SEALED BY THE ENGINEER OF RECORD- FL. STATUTE
 471.025, AND SECTION 61G15-23.005 FAC.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By asangele Date 2022-09-21 Time 16:18 Rev Time 0.00
Received By asangele Date 2022-09-21 Time 16:17 Sent To  
Notes
2022-09-21 16:19:11SEPARTE PERMIT REQUIRED FOR POOL EQUIPMENT
  
  
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR
 FEET INTO A SETBACK.

Review Stop Z ZONING
Rev No 1 Status P Date 2022-08-08 Cont ID  
Sent By asangele Date 2022-08-08 Time 16:38 Rev Time 0.00
Received By asangele Date 2022-08-08 Time 16:38 Sent To  
Notes
***NONE***