| 2022-08-25 12:40:15 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22071245 |
| | |
| | 1- RESUBMIT SHUTTERS FLORIDA PRODUCT APPROVAL. |
| | INFORMATION IS NOT LEGIBLE. THE SPAN SCHEDULES AND |
| | ANCHOR SCHEDULES ARE VERY BLURRY AND ARE NOT LEGIBLE. |
| | SUBMIT CLEAR AND LEGIBLE INFORMATION. AND PLEASE UPLOAD |
| | DRAWINGS ON LANDSCAPE ORIENTATION NOT ON VERTICAL |
| | ORIENTATION. SEC. 107.2.1.3 CITY AMENDMENTS. |
| | |
| | 2- REVISE SHUTTERS INSTALLATION SCHEDULE: |
| | A)SHUTTERS MOUNTING CONDITIONS AND ANCHOR CONNECTION |
| | TYPE IS NOT CLEAR. NONE OF THE MOUNTING CONDITIONS |
| | CIRCLED ON SHEETS 5 AND 6 SHOW CONNECTION TYPE C5 AS |
| | SPECIFIED ON THE SHUTTERS INSTALLATION SCHEDULE. REVISE |
| | AS REQUIRED TO REFLECT PROPOSED MOUNTING INSTALLATION |
| | AND ANCHOR CONNECTION TYPE. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | NOTE: TRENCH INSTALLATION DOESN'T INCLUDE ANCHOR |
| | CONNECTION TYPE C5. |
| | |
| | B)SHUTTER MOUNTING INSTALLATION AND ANCHOR CONNECTION |
| | TYPE COLUMN ONLY SPECIFY C5 FOR ALL PROPOSED MOUNTING |
| | CONDITIONS. CONNECTION TYPE C5 DOESN'T APPLY TO ALL |
| | PROPOSED MOUNTING CONDITION. REVISE AS REQUIRED AND |
| | CLEARLY IDENTIFY THE PROPOSED MOUNTING CONDITION. |
| | COORDINATE WITH ITEM #2 ABOVE. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C) SHUTTER SPAN IS INCORRECT. SHUTTER SPAN IS THE |
| | OPENING HEIGHT NOT THE WIDTH. REVISE AS REQUIRED. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | D) EDGE DISTANCE IS INCORRECT. SEE HIGHLIGHTED ANCHOR |
| | SCHEDULE AND REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | NOTE: COORDINATE WITH ITEM #1(F) BELOW. |
| | |
| | E) ANCHOR SPACING NEEDS TO BE COORDINATED WITH ANCHOR |
| | SCHEDULE TABLE USED DEPENDING ON THE SUBSTRATE TYPE |
| | (CONCRETE OR HOLLOW CONCRETE BLOCK). REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | NOTE: COORDINATE WITH ITEM #3(F) BELOW. |
| | |
| | F)REVISE INFORMATION SUBSTRATE COLUMN. TYPICALLY THE |
| | BOTTOM OF WINDOW OPENINGS IS CONCRETE BLOCK. REVISE |
| | INSTALLATION SCHEDULE USING THE ANCHOR FOR CONCRETE |
| | BLOCK SUBSTRATE OR PROVIDE PROOF SHOWING BOTTOM OF |
| | OPENINGS HAS POURED CONCRETE WITH THE STRENGTH |
| | SPECIFIED ON ANCHOR SCHEDULE. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |