| 2022-07-28 12:29:47 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22071210 733 NEW YORK ST |
| | MASTER PERMIT 21100899 |
| | |
| | 1ST REVIEW |
| | GAS COMMENTS: DENIED |
| | |
| | SEPARATE PERMITS SHALL BE REQUIRED FOR CONNECTION TO |
| | GAS APPLIANCES LISTED AS FUTURE. |
| | |
| | 1.MASTER PERMIT 21100899 DOES NOT INDICATE ANY OF THE |
| | APPLIANCES OR EQUIPMENT NOTED IN THIS PERMIT |
| | APPLICATION. PER WPB FBC 107.2.1, PROVIDE BACKUP FROM |
| | MASTER PERMIT. |
| | |
| | 2.PER WPB FBC 107.2.1, PROVIDE, ON THE RISER DIAGRAM, |
| | LOCATIONS OF ALL SHUTOFF VALVES. |
| | |
| | 3. PER WPB FBC 107.2.1, PROVIDE SITE PLAN WITH |
| | LOCATIONS OF SERVICE METER/REGULATOR, FUTURE GENERATOR |
| | AND FUTURE POOL HEATER. |
| | |
| | 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL (FBC |
| | FG402.2, 301.3 /FBC RES G2404.3) FOR ALL GAS EQUIPMENT |
| | AS FOLLOWS: |
| | ***A) TANKLESS WATER HEATER |
| | ***B) DRYER(S) |
| | ***C) RANGE |
| | |
| | 5. THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES / |
| | EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION. |
| | FBC FG 305.1, FBC RES G2408.1. |
| | |
| | 6.PER WPB FBC 107.2.1, PROVIDE SIZES, LENGTHS AND |
| | MATERIAL FOR EACH PIPE SEGMENT BETWEEN THE SERVICE |
| | METER/REGULATOR AND THE BRANCH SERVING THE FUTURE |
| | FIREPLACE. |
| | |
| | 7.PER WPB FBC 107.2.1, PROVIDE SIZING TABLE FOR |
| | SCHEDULE 40 STEEL PIPING BETWEEN THE SERVICE |
| | METER/REGULATOR AND THE 11 INCH WC REGULATOR. |
| | |
| | 8. PLEASE RECALCULATE THE LONGEST RUN FROM THE 11 INCH |
| | WC REGULATOR TO MOST REMOTE APPLIANCE IN THE LESS THAN |
| | 2 PSI SYSTEM. PLEASE NOTE, THERE CAN ONLY BE ONE (1) |
| | LONGEST RUN IN ANY SYSTEM. |
| | |
| | 9.PER WPB FBC 107.2.1, PROVIDE A CHART LISTING ALL |
| | APPLIANCES AND QUANTITY WITH BTU VALUE AND TOTAL BTU |
| | LOAD. NOTE TOTAL BTU LOAD FOR THE 2 PSI SYSTEM (WHICH |
| | INCLUDES TOTAL DOWNSTREAM OF THE 11 INCH WC REGULATOR |
| | AND THE TOTAL LOAD FOR THE LESS THAN 2 PSI SYSTEM. |
| | |
| | 10. PER WPB FBC 107.2.1, PROVIDE, ON THE RISER DIAGRAM, |
| | EHD SIZE(S) OF CSST SEGMENTS TO CORRESPOND WITH |
| | SUPPLIED FBC FG TABLE 402.4 (15) |
| | |
| | 11.PER WPB FBC 107.2.1, LIST THE TABLE(S) USED FOR |
| | CALCULATING PIPE SIZES. |
| | |
| | 12.PER WPB FBC 107.2.1, IDENTIFY OR CLEARLY SHOW THE |
| | SHUTOFF VALVE AHEAD OF THE 11 INCH WC REGULATOR. FBC FG |
| | 409.4, FBC RES G 2420.4 |
| | |
| | 14.PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR |
| | COMBUSTION AIR FOR THE RANGE AND DRYERS PER THE FBC FG |
| | 304.1, 614.6 /FBC RES G 2407.1 AND G2439.4. PROVIDE |
| | MAKEUP AIR FOR THE DRYERS IF REQUIRED. |
| | |
| | 15.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUAL AND DETAIL FOR |
| | TANKLESS WATER HEATER COMBUSTION AIR AND EXHAUST VENT |
| | SYSTEM(S). |
| | |
| | 16.PER WPB FBC 107.2.1, PROVIDE ON FLOOR PLAN, |
| | LOCATIONS OF ALL APPLIANCES AND CORRESPONDING BTU |
| | LOADS. |
| | |
| | 17. THE FUTURE GENERATOR WILL REQUIRE A SEPARATE |
| | PERMIT. PLEASE NOTE THIS ON THE PLAN PER WPB FBC |
| | 107.2.1. IT SHOULD BE NOTED THAT THE "FUTURE GENERATOR" |
| | WILL NEED 10 FOOT SETBACKS FROM OPENINGS INTO THE |
| | STRUCTURE. |
| | |
| | 18. THE FUTURE POOL HEATER WILL REQUIRE A SEPARATE |
| | PERMIT. PLEASE NOTE THIS ON THE PLAN PER WPB FBC |
| | 107.2.1. IT SHOULD BE NOTED THAT THE "FUTURE POOL |
| | HEATER" WILL NEED 10 FOOT SETBACKS FROM OPENINGS INTO |
| | THE STRUCTURE. |
| | |
| | 19. THE FUTURE FIREPLACE WILL REQUIRE A SEPARATE |
| | PERMIT. PLEASE NOTE THIS ON THE PLAN PER WPB FBC |
| | 107.2.1. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |