| Plan Review Stops For Permit 22071179 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2022-08-02 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-08-02 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-08-02 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2022-08-02 08:53:50 | ADDRESS APPROPRIATE FOR PROJECT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-09-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-09-22 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-09-20 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2022-09-22 08:32:10 | FLOOD ZONE - X. | | | NO UNDERGROUND UTILITIES ON-SITE. | | | VALUE VERIFIED. | | | NON-HISTORIC. | | | CT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-31 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-31 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2022-08-31 12:17:01 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED. | | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN | | | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER | | | PREVIOUS COMMENTS. | | | | | | | | | 1. | | | | | | 2.PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA'S | | | FOR THE PROPOSED WINDOWS AND DOORS TO BE INSTALLED. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | NOTE: NOA?S DO NOT HAVE COVER SHEETS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 3. CORRECTED | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-08-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-19 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-19 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2022-08-19 17:03:26 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE | | | SURVEY. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2.PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA'S | | | FOR THE PROPOSED WINDOWS AND DOORS TO BE INSTALLED. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | NOTE: NOA?S DO NOT HAVE COVER SHEETS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 3.PROVIDE A ROOF SHEATHING FASTENER SCHEDULE PER THE | | | CALCULATED DESIGN PRESSURES. | | | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING | | | SCHEDULE FOR WOOD STRUCTURAL PANELS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-08-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-08-11 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-08-11 |
Time |
07:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-09-22 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-09-22 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-09-07 |
Time |
15:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-09-06 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-08-31 |
Time |
08:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-08-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-20 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-07-27 |
Time |
05:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-09-26 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-09-26 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-09-21 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2022-09-21 12:41:29 | 9/21/22 EMAILED IMPACT TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-08-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-19 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-19 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2022-08-19 16:57:39 | IMPACT FEES | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2022-07-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-07-27 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-07-27 |
Time |
14:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-09-15 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-15 |
Time |
06:56 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-01 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-09-01 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2022-09-01 09:43:59 | 2ND PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC P3108.1 - ON THE RISER DIAGRAM, THE TWO | | | WATER CLOSETS ARE CONNECTED WITHOUT A VENT. EACH | | | FIXTURE DRAIN MUST BE VENTED. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-07-27 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-07-27 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-07-27 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2022-07-27 13:29:41 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC P3108.2.1 - THE WATER CLOSET AND THE TUB IN | | | THE GUEST BATH ARE NOT VENTED CORRECTLY. THERE ARE TWO | | | TRAPS ON THE HIGH SIDE OF THE VENTED FIXTURE | | | CONNECTION. ONLY ONE IS ALLOWED. PLEASE RECONFIGURE. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2022-09-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-09-22 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-09-20 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-31 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-31 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2022-08-31 12:15:04 | PLAN REVIEW ROOFING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 2ND REVIEW | | | | | | NOTICE: COMMENTS FROM 1ST REVIEW HAVE NOT BEEN | | | ADDRESSED. SEE BELOW: | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: A ROOFING SUB-PERMIT REQUIRED. | | | PERMITS - 105.1 REQUIRED. | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR SECONDARY WATER | | | BARRIER PER FBC R905.1.1. | | | UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL | | | CONFORM TO THE APPLICABLE STANDARDS? AND SHALL BE | | | APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION | | | R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE. | | | | | | 2.PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA | | | FOR THE PROPOSED ROOF SYSTEM TO BE INSTALLED. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | NOTE: NOA?S DO NOT HAVE COVER SHEETS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-08-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-19 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-19 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2022-08-19 16:59:07 | PLAN REVIEW ROOFING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: A ROOFING SUB-PERMIT REQUIRED. | | | PERMITS - 105.1 REQUIRED. | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR SECONDARY WATER | | | BARRIER PER FBC R905.1.1. | | | UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL | | | CONFORM TO THE APPLICABLE STANDARDS? AND SHALL BE | | | APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION | | | R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE. | | | | | | 2.PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA | | | FOR THE PROPOSED ROOF SYSTEM TO BE INSTALLED. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | NOTE: NOA?S DO NOT HAVE COVER SHEETS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-09-15 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-15 |
Time |
07:00 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-31 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-31 |
Time |
10:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-08-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-19 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-19 |
Time |
16:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-09-02 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-09-02 |
Time |
08:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-08-01 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-08-01 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-08-01 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2022-08-01 16:45:55 | 8/1/2022 FAILED | | | | | | SEPARATE PERMIT REQUIRED FOR: | | | FENCE/WALL, AWNINGS, GENERATOR, MECHANICAL/AC/POOL | | | EQUIPMENT, DRIVEWAY, IRRIGATION, LANDSCAPE, POOL, OTHER | | | | | | | | | PLEASE APPLY FOR A LANDSCAPE PERMIT TO MOVE PERMIT | | | FORWARD | | | | | | VALENTINA BROGLIA | | | ASSOCIATE PLANNER | | | [email protected] | | | |
|
|