Plan Review Details - Permit 22071171
Plan Review Stops For Permit 22071171
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2023-04-06 Cont ID  
Sent By rmcphers Date 2023-04-06 Time 13:13 Rev Time 0.00
Received By rmcphers Date 2023-04-06 Time 13:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-03-14 Cont ID  
Sent By rmcphers Date 2023-03-14 Time 09:48 Rev Time 0.00
Received By rmcphers Date 2023-03-14 Time 09:44 Sent To  
Notes
2023-03-14 09:46:01REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING 10/12 SHOWS 2ND FLOOR AS "TRAINING AREA" -
 PLEASE PROVIDE VERTICAL ACCESSIBILITY FOR THE ASSEMBLY
 AREA - FBC A 201.1.1
  
 2) DRAWING 3/12 --- 4/12 ----- AND 10/12 SHOWS
 CONSTRUCTION TYPE AS TYPE II - CANNOT HAVE WOOD FRAMING
 BEARING WALLS AND WOOD FLOOR FRAMING IN A BUILDING OF
 TYPE II CONSTRUCTION - SEE FBC 603.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-01-27 Cont ID  
Sent By rmcphers Date 2023-01-27 Time 11:02 Rev Time 0.00
Received By rmcphers Date 2023-01-27 Time 10:47 Sent To  
Notes
2023-01-27 11:01:56REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING 8/12 SHOWS 2ND FLOOR AS "TRAINING AREA" -
 PLEASE PROVIDE VERTICAL ACCESSIBILITY FOR THE ASSEMBLY
 AREA - FBC A 201.1.1
  
 2) DRAWING 7/12 SHOWS 2ND FLOOR AS "TRAINING AREA" -
 PLEASE PROVIDE VERTICAL ACCESSIBILITY FOR THE ASSEMBLY
 AREA - FBC A 201.1.1
  
 3) DRAWING 5/12 PLEASE SHOW THE HAND RAIL EXTENSIONS ON
 THE HAND RAIL NOT THE GUARDRAIL. - FBC 1014.6
  
 4) DRAWING 3/12 SHOWS CONSTRUCTION TYPE AS TYPE II -
 CANNOT HAVE WOOD FRAMING BEARING WALLS AND WOOD FLOOR
 FRAMING IN A BUILDING OF TYPE II CONSTRUCTION - SEE FBC
 603.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-12-12 Cont ID  
Sent By rmcphers Date 2022-12-12 Time 10:31 Rev Time 0.00
Received By rmcphers Date 2022-12-12 Time 10:31 Sent To  
Notes
2022-12-12 10:35:17REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE GUARD RAIL HEIGHT ALONG THE STAIRWAY
 - FBC 1015.3 HEIGHT.
 REQUIRED GUARDS SHALL BE NOT LESS THAN 42 INCHES (1067
 MM) HIGH,
  
 FBC 1014.2 HEIGHT.
 HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR
 FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT
 LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38
 INCHES (965 MM).
  
 2) PLEASE SHOW THE HANDRAIL EXTENSIONS - FBC
 1014.6HANDRAIL EXTENSIONS.
 THE HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN
 12 INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO
 SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-10-17 Cont ID  
Sent By rmcphers Date 2022-10-17 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2022-10-17 Time 11:08 Sent To  
Notes
2022-10-17 11:08:56REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) BUILDING CONSTRUCTION TYPE SHOWN "TYPE II" - DOES
 NOT ALLOW COMBUSTIBLE CONSTRUCTION - I THINK THAT THE
 CONSTRUCTION TYPE COULD BE TYPE III B - SEE FBC TABLE
 506.2
  
 2) OCCUPANT LOAD - DRAWINGS SHOW "50 GROSS" - PLEASE
 SHOW THE OCCUPANT LOAD FOR THE TRAINING AREA - FBC 1004
 PLEASE SEE TABLE 1004.5 AND SHOW THE "FUNCTION OF THE
 SPACE" AND THE OCCUPANT LOAD CORRECTLY.
  
 3) STAIR AND BALCONY GUARD RAIL OPENINGS FOR THE
 TRAINING AREA NEED TO COMPLY WITH FBC 1015.4 OPENING
 LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS THAT ALLOW
 PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM
 THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT.
  
 4) PLEASE SHOW THE GUARD RAIL HEIGHT ALONG THE STAIRWAY
 - FBC 1015.3 HEIGHT.
 REQUIRED GUARDS SHALL BE NOT LESS THAN 42 INCHES (1067
 MM) HIGH,
  
 5) SHOW THE VERTICAL ACCESSIBILITY TO THE 2ND FLOOR PER
 FBC 201.1.1
  
 6) PLEASE SHOW THE SQUARE FOOTAGE OF THE 2ND FLOOR FBC
 1004.5
  
 7) PLEASE SHOW IF THE BUILDING HAS FIRE SPRINKLERS OR
 NON SPRINKLERED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-30 Cont ID  
Sent By rmcphers Date 2022-08-30 Time 14:15 Rev Time 0.00
Received By rmcphers Date 2022-08-30 Time 13:54 Sent To  
Notes
2022-08-30 14:15:43REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) 2ND FLOOR CHANGE OF USE FROM STORAGE TO TRAINING
 AREA - PLEASE SHOW THE OCCUPANCY CLASSIFICATION FOR THE
 AREA FBC CHAPTER 3
  
 2) PLEASE SHOW THE OCCUPANT LOAD FOR THE TRAINING AREA
 - FBC 1004
  
 3) STAIR AND BALCONY GUARD RAIL OPENINGS FOR THE
 TRAINING AREA NEED TO COMPLY WITH FBC 1015.4 OPENING
 LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS THAT ALLOW
 PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM
 THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT.
  
 4) SHOW THE VERTICAL ACCESSIBILITY TO THE 2ND FLOOR PER
 FBC 201.1.1

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-05-26 Cont ID  
Sent By jleahy Date 2023-05-26 Time 06:57 Rev Time 0.00
Received By jleahy Date 2023-05-25 Time 08:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2023-04-17 Cont ID  
Sent By mpeterso Date 2023-04-17 Time 11:04 Rev Time 0.00
Received By mpeterso Date 2023-04-17 Time 11:04 Sent To  
Notes
2023-04-17 11:16:59ELECTRIC REVIEW FAILED
 1) IT APPEARS THIS REVISION IS TO INCLUDE CHANGING THE
 AIR CONDITIONING SYSTEM. THE AIR CONDITIONING SYSTEM IS
 STATED AS BEING 3 PHASE, HOWEVER, THE ELECTRICAL PANEL
 SCHEDULE IS LISTED AS A 1 PHASE SYSTEM. PLEASE CORRECT
 CONFLICTS AS APPLICABLE. IN ADDITION PLEASE PROVIDE AN
 UPDATED ELECTRIC RISER DIAGRAM TO INCLUDE ELECTRICAL
 PANEL, DISCONNECT, CONDUIT, CONDUCTOR AND OVERCURRENT
 PROTECTION SIZES. IN ADDITION, INCLUDE A PANEL SCHEDULE
 DETAILING ALL ELECTRIC LOADS AND OVERCURRENT PROTECTION
 SIZES. ALSO INCLUDE AN ACCURATE ELECTRIC LOAD
 CALCULATION. NEC 215.5, NEC 215.2, NEC 220 FBC 107.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-03-16 Cont ID  
Sent By jleahy Date 2023-03-16 Time 14:09 Rev Time 0.00
Received By jleahy Date 2023-03-16 Time 14:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-09-16 Cont ID  
Sent By jleahy Date 2022-09-16 Time 16:28 Rev Time 0.00
Received By jleahy Date 2022-09-16 Time 16:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-04-06 Cont ID  
Sent By cwalker Date 2023-04-06 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-04-06 09:16:12FIRE PROVISO COMMENT:
  
 NO STORAGE SHALL BE ALLOWED UNDER STAIRS. NFPA 101,
 7.2.2.5.3
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-03-08 Cont ID  
Sent By cwalker Date 2023-03-08 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-03-08 09:27:55FIRE PROVISO COMMENT:
  
 NO STORAGE SHALL BE ALLOWED UNDER STAIRS. NFPA 101,
 7.2.2.5.3
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-08-22 Cont ID  
Sent By pleduc Date 2022-08-22 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-08-22 12:31:52FIRE PROVISO COMMENT:
  
 NO STORAGE SHALL BE PERMITTED UNDER STAIRS. NFPA 101,
 7.2.2.5.3
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2023-06-08 Cont ID  
Sent By hmoser Date 2023-06-08 Time 12:21 Rev Time 0.00
Received By hmoser Date 2023-06-07 Time 09:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2023-06-06 Cont ID  
Sent By hmoser Date 2023-06-06 Time 12:32 Rev Time 0.00
Received By hmoser Date 2023-05-10 Time 08:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-04-18 Cont ID  
Sent By medwards Date 2023-04-18 Time 15:11 Rev Time 0.00
Received By medwards Date 2023-04-05 Time 09:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-03-16 Cont ID  
Sent By jleahy Date 2023-03-16 Time 14:09 Rev Time 0.00
Received By jleahy Date 2023-03-07 Time 13:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-27 Cont ID  
Sent By medwards Date 2023-01-27 Time 15:44 Rev Time 0.00
Received By medwards Date 2023-01-26 Time 15:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-21 Cont ID  
Sent By medwards Date 2022-12-21 Time 05:57 Rev Time 0.00
Received By medwards Date 2022-12-08 Time 06:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-17 Cont ID  
Sent By rmcphers Date 2022-10-17 Time 14:00 Rev Time 0.00
Received By rmcphers Date 2022-09-20 Time 07:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-16 Cont ID  
Sent By jleahy Date 2022-09-16 Time 16:29 Rev Time 0.00
Received By jleahy Date 2022-08-19 Time 14:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2023-06-08 Cont ID  
Sent By hmoser Date 2023-06-08 Time 12:20 Rev Time 0.00
Received By hmoser Date 2023-06-08 Time 12:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2023-06-06 Cont ID  
Sent By hmoser Date 2023-06-06 Time 12:32 Rev Time 0.00
Received By hmoser Date 2023-06-06 Time 11:09 Sent To  
Notes
2023-06-06 12:32:08PLAN DENIED
 PROVIDE A VALUE ON THE APPLICATION FOR THE
 RIVISION OR A EXPLANATION WHY THERE IS NO VALUE.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561=805-6676

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2023-04-18 Cont ID  
Sent By medwards Date 2023-04-18 Time 15:05 Rev Time 0.00
Received By medwards Date 2023-04-18 Time 15:11 Sent To  
Notes
2023-04-18 15:09:28PLEASE ADDRESS EACH COMMENT MENTIONED BELOW ON THE
 DRAWINGS.
 WHAT IS GOING TO HAPPEN WITH THE AHU-1 AND AHU-2 WITH
 ITHIS DESIGN?
 THIS NEW DESIGN SHOWS A SPLIT SYSTEM AIR CONDITIONERS
 DETAIL 2/H1. THIS DETAIL SPECIFIES 6- 25 TONS COOLING
 UNITS AND 5-25 TONS AIR HANDLERS. WHERE ARE THESE TO BE
 USED IN THIS PROJECT?
 1ST REVIEW FMC
 PERMIT: 22071171
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 IT APPEARS THERE IS A L9OT OF CHANGES FROM THE ORIGINAL
 SUBMITTAL PERMIT NUMBER 21030310. PLEASE RESPOND TO THE
 FOLLOWING REVIEW COMMENTS FOR THIS REVISED DESIGN.
  
 1) PROVIDE THE CORRECT VALUE OF WORK ON THE APPLICATION
 FOR THIS NEW SYSTEM.
  
 2) PROVIDE A NARRATIVE TELLING THE SCOPE OF WORK FOR
 THIS REVISED DESIGN. FBC 107.3.5
  
 3) THE ORIGINAL DESIGN WAS FOR 3 EXISTING AHUS. THIS
 LATEST SUBMITTAL IS NOW SPECIFYING 6-25 TONS COOLING
 UNITS AND 5-25 TONS AIR HANDLING UNITS.
  
 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THESE NEW
 SYSTEMS.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2023-03-13 Cont ID  
Sent By medwards Date 2023-03-13 Time 13:46 Rev Time 0.00
Received By medwards Date 2023-03-13 Time 13:46 Sent To  
Notes
2023-03-13 13:47:011ST REVIEW FMC
 PERMIT: 22071171
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 IT APPEARS THERE IS A L9OT OF CHANGES FROM THE ORIGINAL
 SUBMITTAL PERMIT NUMBER 21030310. PLEASE RESPOND TO THE
 FOLLOWING REVIEW COMMENTS FOR THIS REVISED DESIGN.
  
 1) PROVIDE THE CORRECT VALUE OF WORK ON THE APPLICATION
 FOR THIS NEW SYSTEM.
  
 2) PROVIDE A NARRATIVE TELLING THE SCOPE OF WORK FOR
 THIS REVISED DESIGN. FBC 107.3.5
  
 3) THE ORIGINAL DESIGN WAS FOR 3 EXISTING AHUS. THIS
 LATEST SUBMITTAL IS NOW SPECIFYING 6-25 TONS COOLING
 UNITS AND 5-25 TONS AIR HANDLING UNITS.
  
 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THESE NEW
 SYSTEMS.
  
 5) WHERE IS THE CONDENSING UNITS GOING TO BE LOCATED?
 SHOW THIS ON THE DRAWING. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-01-27 Cont ID  
Sent By medwards Date 2023-01-27 Time 15:41 Rev Time 0.00
Received By medwards Date 2023-01-27 Time 15:41 Sent To  
Notes
2023-01-27 15:44:17PLEASE PROVIDE A MECHANICAL DRAWING THAT IS READABLE.
 THE FONT IS NOT READABLE ON THE DRAWING DATED
 01/26/2023. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-12-21 Cont ID  
Sent By medwards Date 2022-12-21 Time 05:56 Rev Time 0.00
Received By medwards Date 2022-12-21 Time 05:56 Sent To  
Notes
2022-12-21 05:57:112ND REVIEW FMC
 PERMIT: 22071171
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DESIGNER OF RECORD FOR THE ORIGINAL DESIGN MUST
 SUBMIT THE REVISED DRAWINGS OR SUBMIT A LETTER STATING
 THEY ARE RELEASING THEMSELVES FROM THIS PROJECT.
  
 2) THE MECHANICAL DRAWING SUBMITTED DOES NOT INDICATE
 WHICH FLOOR THIS NEW SPACE WILL BE LOCATED IN THIS
 BUILDING. PROVIDE A FULL SET OF DRAWINGS FOR THIS
 REVISION. FBC 107.3.5
  
 3) PROVIDE THE COMPLETE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC C403.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-10-04 Cont ID  
Sent By medwards Date 2022-10-04 Time 08:58 Rev Time 0.00
Received By medwards Date 2022-10-04 Time 07:50 Sent To  
Notes
2022-10-04 08:59:091ST REVIEW FMC
 PERMIT: 22071171
  
 CODES IN EFFECT: 2020
  
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
  
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A COMPLETE SCOPE OF WORK FOR THE MECHANICAL
 DESIGN. FBC 107.3.5
  
 2) THERE IS A 1 PAGE MECHANICAL SIZING SHEET SUBMITTED,
 THE DUCTWORK DRAWING DOES NOT SHOW A NEW SYSTEM. PLEASE
 EXPLAIN WHAT THIS SHEET IS SERVING.
  
 3) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS NEW
 TRAINING AREA. FMC 403.3.1.1
  
 4) THE DRAWING SUBMITTED IS NOT FROM THE EOR FOR THIS
 PROJECT PLEASE SUBMIT A DRAWING FROM THIS DESIGNER OR A
 CHANGE OR EOR. 61G15-27.001
  
 5) THE DRAWING SUBMITTED DOES NOT SHOW THE MAIN TRUNK
 LINE SIZES, PLEASE SHOW THE MAIN TRUNK LINE SIZES. FBC
 107.3.5
  
 6) THE REVISION APPLICATION SUBMITTED DOES NOT SHOW A
 VALUE FOR THIS NEW SCOPE OF WORK. PROVIDE A VALUE FOR
 THIS REVISION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-04-10 Cont ID  
Sent By rwbrown Date 2023-04-10 Time 09:14 Rev Time 0.00
Received By rwbrown Date 2023-04-10 Time 09:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-08-29 Cont ID  
Sent By rwbrown Date 2022-08-29 Time 10:12 Rev Time 0.00
Received By rwbrown Date 2022-08-29 Time 10:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2023-06-06 Cont ID  
Sent By hmoser Date 2023-06-06 Time 11:49 Rev Time 0.00
Received By hmoser Date 2023-06-06 Time 11:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2023-04-17 Cont ID  
Sent By mpeterso Date 2023-04-17 Time 11:19 Rev Time 0.00
Received By mpeterso Date 2023-04-17 Time 11:17 Sent To  
Notes
2023-04-17 11:21:16SIGNATURE REVIEW FAILED
 1) SHEETS LABELED E1.1 AND DUCT FLOOR PLAN DO NOT
 DETAIL THE REQUIRED DIGITAL SIGNATURE. PLEASE CORRECT
 AS OUTLINED BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2023-03-14 Cont ID  
Sent By rmcphers Date 2023-03-14 Time 09:48 Rev Time 0.00
Received By rmcphers Date 2023-03-14 Time 09:48 Sent To  
Notes
2023-03-14 09:49:43SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS 8/12, 7/12, 10/12 DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-01-27 Cont ID  
Sent By rmcphers Date 2023-01-27 Time 11:04 Rev Time 0.00
Received By rmcphers Date 2023-01-27 Time 11:04 Sent To  
Notes
2023-01-27 11:05:45SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS 8/12, 7/12, 10/12 AND THE MECHANICAL
 DRAWING DOES NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-12 Cont ID  
Sent By rmcphers Date 2022-12-12 Time 10:36 Rev Time 0.00
Received By rmcphers Date 2022-12-12 Time 10:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-10-17 Cont ID  
Sent By rmcphers Date 2022-10-17 Time 14:00 Rev Time 0.00
Received By rmcphers Date 2022-10-17 Time 14:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-30 Cont ID  
Sent By rmcphers Date 2022-08-30 Time 14:18 Rev Time 0.00
Received By rmcphers Date 2022-08-30 Time 14:18 Sent To  
Notes
2022-08-30 14:19:17SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) SIGNED AND SEALED DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  