Plan Review Details - Permit 22071150
Plan Review Stops For Permit 22071150
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-12-20 Cont ID  
Sent By aoliver Date 2022-12-20 Time 10:41 Rev Time 0.00
Received By aoliver Date 2022-12-20 Time 10:41 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-11-28 Cont ID  
Sent By jwitmer Date 2022-11-28 Time 16:31 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-11-28 16:31:01COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-10-24 Cont ID  
Sent By jwitmer Date 2022-10-24 Time 17:19 Rev Time 0.00
Received By jwitmer Date 2022-10-24 Time 17:09 Sent To  
Notes
2022-10-24 17:19:22COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-01-03 Cont ID  
Sent By jwitmer Date 2023-01-03 Time 10:26 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-11-28 Cont ID  
Sent By jwitmer Date 2022-11-28 Time 16:35 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-10-24 Cont ID  
Sent By jwitmer Date 2022-10-24 Time 17:22 Rev Time 0.00
Received By jwitmer Date 2022-10-24 Time 17:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-01-06 Cont ID  
Sent By mpeterso Date 2023-01-06 Time 14:25 Rev Time 0.00
Received By mpeterso Date 2023-01-06 Time 14:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-02 Cont ID  
Sent By mpeterso Date 2022-12-02 Time 14:43 Rev Time 0.00
Received By mpeterso Date 2022-12-02 Time 14:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-06 Cont ID  
Sent By mpeterso Date 2022-10-06 Time 08:39 Rev Time 0.00
Received By mpeterso Date 2022-10-06 Time 08:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-12-30 Cont ID  
Sent By cwalker Date 2022-12-30 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-11-18 Cont ID  
Sent By cwalker Date 2022-11-18 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-13 Cont ID  
Sent By cwalker Date 2022-09-13 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-06 Cont ID  
Sent By mpeterso Date 2023-01-06 Time 14:27 Rev Time 0.00
Received By mpeterso Date 2022-12-29 Time 08:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-20 Cont ID  
Sent By aoliver Date 2022-12-20 Time 10:43 Rev Time 0.00
Received By aoliver Date 2022-12-12 Time 10:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-02 Cont ID  
Sent By mpeterso Date 2022-12-02 Time 14:47 Rev Time 0.00
Received By mpeterso Date 2022-11-17 Time 07:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-10-24 Cont ID  
Sent By jwitmer Date 2022-10-24 Time 17:22 Rev Time 0.00
Received By jwitmer Date 2022-09-14 Time 06:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-10-24 Cont ID  
Sent By jwitmer Date 2022-10-24 Time 17:19 Rev Time 0.00
Received By jwitmer Date 2022-10-24 Time 17:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-01-03 Cont ID  
Sent By medwards Date 2023-01-03 Time 16:20 Rev Time 0.00
Received By medwards Date 2023-01-03 Time 16:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-12-19 Cont ID  
Sent By medwards Date 2022-12-19 Time 11:35 Rev Time 0.00
Received By medwards Date 2022-12-19 Time 11:35 Sent To  
Notes
2022-12-19 11:38:00PLEASE SHOW THAT TF-10-1 WILL TERMINATE OUTDOORS. THE
 COPY PRINT ROOM WILL NEED .5 CFMS OF EXHAUST. FMC TABLE
 403.3.1.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-11-21 Cont ID  
Sent By medwards Date 2022-11-21 Time 15:48 Rev Time 0.00
Received By medwards Date 2022-11-21 Time 15:48 Sent To  
Notes
2022-11-21 15:49:051ST REVIEW FMC
 PERMIT: 22071150
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-401 TERMINAL BOX SCHEDULE INDICATES THAT
 VAV-10-RH-2 HAS AN INLET SIZE OF 8 INCH AND MAX FLOW
 RATE OF 700 CFM???S. SHEET M-501 INDICATES THAT
 VAV-10-RH-2 HAS A 12 DUCT WITH A MAX FLOW RATE OF 1400
 CFM???S. PLEASE MAKE CORRECTIONS.
  
 2) PROVIDE THE OUTDOOR AIR CALCULATION FOR EACH
 OCCUPANCY CLASSIFICATION ACCORDING THE FMC TABLE
 403.3.1.1 IE: THE CONFERENCE ROOM BASED ON THE SQ. FT.
 PROVIDED WOULD HAVE ROOM FOR 17 OCCUPANTS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-09-16 Cont ID  
Sent By medwards Date 2022-09-16 Time 15:07 Rev Time 0.00
Received By medwards Date 2022-09-16 Time 15:07 Sent To  
Notes
2022-09-16 15:07:371ST REVIEW FMC
 PERMIT: 22071150
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF
 THE TENANT SPACE. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 2) THE EXHAUST FROM THE PRINTING ROOM MUST BE EXHAUSTED
 TO THE OUTDOORS AND NOT INTO THE RETURN AIR PLENUM. FMC
 TABLE 403.3.1.1
  
 3) PROVIDE THE DUCT SIZES FOR THE SUPPLY DUCT FOR
 VAV-10-RH-3. FBC 107.3.5
  
 4) SHEET M-401: IDENTIFY EACH VAV IN THE TERMINAL BOX
 SCHEDULE TO MATCH SHEET M-501.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-11-22 Cont ID  
Sent By ccole Date 2022-11-22 Time 10:04 Rev Time 0.00
Received By ccole Date 2022-11-22 Time 09:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-09-23 Cont ID  
Sent By ccole Date 2022-09-23 Time 17:00 Rev Time 0.00
Received By ccole Date 2022-09-23 Time 16:27 Sent To  
Notes
2022-09-23 17:01:041ST REVIEW FBC-2020 PLUMBING
 PERMIT-22071150
 9/23/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-501: PROVIDE PLUMBING RISER DRAWINGS- SEC.
 107.3.5.1.3 WPB.
  
 2) P-501: PROVIDE A MEANS OF DELIVERING THE REQUIRED
 HOT WATER FROM THE LOUNGE SINK, AND A MEANS OF LIMITING
 THE TEMPERATURE OF THE HOT WATER- REFER TO SECS. 607.1
 & 607.1.1 FBC P.
  
 3) P-001; PROVIDE A PLUMBING FIXTURE AND EQUIPMENT
 SCHEDULE ON THE- SEC. 107.3.5.1.3 WPB.
  
 4) P-501: THE PLAN SHOWS THE NEW SANITARY PIPING RUN IN
 THE CEILING BELOW THE FLOOR. PLEASE CLARIFY IF THE
 SPACE IS A PLENUM AND INDICATE THE TYPE OF DWV AND
 WATER PIPING WILL BE INSTALLED- SEC. 303.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-01-06 Cont ID  
Sent By mpeterso Date 2023-01-06 Time 14:27 Rev Time 0.00
Received By mpeterso Date 2023-01-06 Time 14:25 Sent To  
Notes
2023-01-03 16:21:07MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-19 Cont ID  
Sent By medwards Date 2022-12-19 Time 11:42 Rev Time 0.00
Received By medwards Date 2022-12-19 Time 11:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-12-02 Cont ID  
Sent By mpeterso Date 2022-12-02 Time 14:47 Rev Time 0.00
Received By mpeterso Date 2022-12-02 Time 14:43 Sent To  
Notes
2022-11-22 10:05:50PLUMBING DIGITAL SIGNATURES AND SEALS PASSED.
2022-11-21 15:51:38MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-06 Cont ID  
Sent By mpeterso Date 2022-10-06 Time 08:42 Rev Time 0.00
Received By mpeterso Date 2022-10-06 Time 08:42 Sent To  
Notes
2022-10-06 08:45:43SIGNATURE REVIEW FAILED
  
 IT APPEARS NONE OF THE MECHANICAL, ELECTRICAL,
 PLUMBING, OR FIRE PROTECTION PLANS ARE NOT SIGNED AND
 SEALED AS REQUIRED. PLEASE CORRECT AS APPLICABLE AS
 OUTLINED BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
2022-09-16 15:10:34DESIGNER MUST DIGITALLY SIGN THE MECHANICAL DOCUMENTS.