Plan Review Stops For Permit 22071149
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-09-13 Cont ID  
Sent By cwalker Date 2022-09-13 Time   Rev Time 0.00
Received By cpuell Date 2022-09-14 Time 08:35 Sent To  
Notes
2022-09-14 08:41:41ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-12-06 Cont ID  
Sent By aoliver Date 2022-12-06 Time 15:54 Rev Time 0.00
Received By aoliver Date 2022-12-06 Time 15:54 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-11-28 Cont ID  
Sent By jwitmer Date 2022-11-28 Time 16:48 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-11-28 16:48:32COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-10-31 Cont ID  
Sent By jwitmer Date 2022-10-31 Time 14:46 Rev Time 0.00
Received By jwitmer Date 2022-10-31 Time 14:45 Sent To  
Notes
2022-10-31 14:45:59COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-11-28 Cont ID  
Sent By jwitmer Date 2022-11-28 Time 16:48 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-31 Cont ID  
Sent By jwitmer Date 2022-10-31 Time 14:46 Rev Time 0.00
Received By jwitmer Date 2022-10-31 Time 14:45 Sent To  
Notes
2022-10-31 14:47:16WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22071149
 ADD: 250 S AUSTRALIAN BLVD # 15TH FLOOR COMMON CORRIDOR
 & RESTROOMS
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 31/ 2022
 ACTION: DENIED
 1) SHEET LS101 BUILDING DESCRIPTION LIST 18 STORIES,
 TYPE I-A, FULLY FIRE SPRINKLERED, FIRE ALARM TO BE
 RETROFITTED. MISSING ELEVATOR LOBBIES AND OR
 EXCEPTIONS.
 1A) ELEVATOR LOBBY REQUIRED. FBC-B 403.5.4 SMOKEPROOF
 ENCLOSURES.
  
 1B) EXISTING BUILDING CODE, LEVEL II ALTERATION.
 803.2.2 SUPPLEMENTAL SHAFT AND FLOOR OPENING ENCLOSURE
 REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS
 50 PERCENT OF THAT FLOOR AREA, THE ENCLOSURE
 REQUIREMENTS OF SECTION 803.2 SHALL APPLY TO VERTICAL
 OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE FLOOR.
 EXCEPTION: VERTICAL OPENINGS LOCATED IN TENANT SPACES
 THAT ARE ENTIRELY OUTSIDE THE WORK AREA.
  
 1C) FBC-B 1016.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
 1.EXIT ACCESS THROUGH AN ENCLOSED ELEVATOR LOBBY IS
 PERMITTED. ACCESS TO NOT LESS THAN ONE OF THE REQUIRED
 EXITS SHALL BE PROVIDED WITHOUT TRAVEL THROUGH THE
 ENCLOSED ELEVATOR LOBBIES REQUIRED BY SECTION 3006.
  
 1D) FBC-B 403.5.4 SMOKEPROOF ENCLOSURES. EVERY REQUIRED
 INTERIOR EXIT STAIRWAY SERVING FLOORS MORE THAN 75 FEET
 (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS SHALL BE A SMOKEPROOF ENCLOSURE IN
 ACCORDANCE WITH SECTIONS 909.20 AND 1023.11.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-06 Cont ID  
Sent By mpeterso Date 2022-10-06 Time 09:21 Rev Time 0.00
Received By mpeterso Date 2022-10-06 Time 09:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-11-18 Cont ID  
Sent By cwalker Date 2022-11-18 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-13 Cont ID  
Sent By cwalker Date 2022-09-13 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-07 Cont ID  
Sent By aoliver Date 2022-12-07 Time 13:01 Rev Time 0.00
Received By aoliver Date 2022-12-06 Time 15:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-11-28 Time   Rev Time 0.00
Received By aoliver Date 2022-11-17 Time 07:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-10-31 Time   Rev Time 0.00
Received By cdecoeur Date 2022-09-14 Time 06:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-10-31 Time   Rev Time 0.00
Received By jwitmer Date 2022-10-31 Time 14:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-11-21 Cont ID  
Sent By medwards Date 2022-11-21 Time 14:54 Rev Time 0.00
Received By medwards Date 2022-11-21 Time 14:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-09-16 Cont ID  
Sent By medwards Date 2022-09-16 Time 13:29 Rev Time 0.00
Received By medwards Date 2022-09-16 Time 13:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-11-22 Cont ID  
Sent By ccole Date 2022-11-22 Time 09:12 Rev Time 0.00
Received By ccole Date 2022-11-21 Time 16:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-09-26 Cont ID  
Sent By ccole Date 2022-09-26 Time 10:24 Rev Time 0.00
Received By ccole Date 2022-09-23 Time 17:03 Sent To  
Notes
2022-09-26 10:26:461ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22071149
 9/26/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A101 & A401: PLEASE PROVIDE THESE
 SITE-SPECIFIC DETAILS IN COMPLIANCE WITH THE FBC ACC-
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SEC. 604.3.
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SEC. 606.2.
 C) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES
 604. PLEASE NOTE THE MEASUREMENTS SHALL BE TO THE TOPS
 OF THE GRIPPING SURFACES.
 E) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
 F) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2 & FIGURES 306.2 & 306.3.
 G) CLEAR FLOOR SPACE DIMENSIONS FOR THE DRINKING
 FOUNTAIN- SEC. 602.2
 H) KNEE AND TOE CLEARANCES FOR THE DRINKING FOUNTAIN,
 AND SPOUT HEIGHTS- SECS. 606.2, 602.4, 602.5, AND
 602.7.
  
 2) P-501: SHOW THE MEANS OF PROVIDING TEMPERED WATER
 DELIVERY FROM THE NEW LAVATORIES- SEC. 419.5 FBC P.
  
 3) P-001: PLEASE PROVIDE A PLUMBING FIXTURE SCHEDULE-
 SEC. 404.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-22 Cont ID  
Sent By ccole Date 2022-11-22 Time 09:22 Rev Time 0.00
Received By ccole Date 2022-11-22 Time 09:12 Sent To  
Notes
2022-11-21 14:55:28MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-06 Cont ID  
Sent By mpeterso Date 2022-10-06 Time 09:22 Rev Time 0.00
Received By mpeterso Date 2022-10-06 Time 09:22 Sent To  
Notes
2022-10-06 09:25:03SIGNATURE REVIEW FAILED
  
 SHEETS 29,30.40.41,42, AND 43 DO NO HAVE THE REQUIRED
 DIGITAL SIGNATURE. PLEASE CORRECT AS APPLICABLE AS
 OUTLINED BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
2022-09-16 13:33:43SHEETS M501 AND M 901 WILL NEED THE DESIGNERS DIGITAL
 SIGNATURE. FS 471/481.

Review Stop Z ZONING
Rev No 1 Status P Date 2022-09-20 Cont ID  
Sent By asangele Date 2022-09-20 Time 12:17 Rev Time 0.00
Received By asangele Date 2022-09-20 Time 12:17 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy