Plan Review Details - Permit 22071084
Plan Review Stops For Permit 22071084
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-09-22 Cont ID  
Sent By jwitmer Date 2022-09-22 Time 14:36 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-09-22 14:37:15TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-09-06 Cont ID  
Sent By jwitmer Date 2022-09-06 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2022-09-06 Time 13:17 Sent To  
Notes
2022-09-06 13:25:21TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-09-22 Cont ID  
Sent By jwitmer Date 2022-09-22 Time 15:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-09-22 12:50:54WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22071084
 ADD: 3800 WASHINGTON RD # 211
 CONT: PROJECT SOLUTIONS LLC
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. SEPT. 09/2022
 ACTION: PASSED/ BUILDING PROVISO
  
 1) BUILDING PROVISO: DEFERRED SUBMITTAL, SUBMIT PRODUCT
 CUT SHEETS AFTER ISSUANCE. THROUGH-PENETRATIONS
 FIRESTOP SYSTEMS
 (HORIZONTAL ASSEMBLIES). IF A NEW FLOOR PENETRATION IS
 MADE FOR THE FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW
 COMPLIANCE WITH THE 2020 FBC-B SECTION
 714.5.1.2. THROUGH-PENETRATIONS FIRESTOP SYSTEMS
 (HORIZONTAL ASSEMBLIES). THROUGH PENETRATIONS SHALL BE
 PROTECTED BY A THROUGH PENETRATION FIRESTOP
 SYSTEM INSTALLED IN ACCORDANCE WITH ASTM E814 OR UL
 1479. THE SYSTEM SHALL HAVE AN F RATING / T RATING OF
 NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE
 REQUIRED RATING OF THE FLOOR PENETRATED.
  
 2) BUILDING PROVISO: DEFERRED SUBMITTAL, PROVIDE
 DOCUMENTATION( AFTER PERMIT ISSUANCE) OF SLAB BEING
 X-RAYED TO THE BUILDING
 DEPARTMENT BEFORE CORE DRILLING OCCURS.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-09-06 Cont ID  
Sent By jwitmer Date 2022-09-06 Time 13:43 Rev Time 0.00
Received By jwitmer Date 2022-09-06 Time 13:17 Sent To  
Notes
2022-09-06 13:43:46WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22071084
 ADD: 3800 WASHINGTON RD # 211
 CONT: PROJECT SOLUTIONS LLC
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 09/2022
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE VALUE OF THE
 PROJECT TO BE $106,000.00 DOLLARS. THE EXISTING AND
 PROPOSED FLOOR PLAN ARE DRAWN BY THE CGC PLEASE REVIEW
 W 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION AND FLORIDA
 STATUTE 481. CERTIFICATION BY CONTRACTOR. 107.3.4.3.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS AND OR SCHEDULES WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS AND OR SCHEDULES
 DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 REQUIRES THE CONTRACTOR FOR THAT TRADE THAT WILL BE
 LICENSED IN THAT TRADE, WILL ALSO BE THE CONTRACTOR
 THAT DESIGNS THE SYSTEM UNDER THAT TRADE. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 481.229 EXCEPTIONS; EXEMPTIONS FROM LICENSURE (1) (C)
 ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000.00, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER
 BUILDING INTENDED FOR PUBLIC USE, PROVIDED THAT THE
 SERVICES OF A REGISTERED ARCHITECT SHALL NOT BE
 REQUIRED FOR MINOR SCHOOL PROJECTS PURSUANT TO 1013.45.
 2) SCOPE OF WORK INDICATES THE REMOVAL OF ALL FLOOR
 TILE AND INSTALLATION OF NEW FLOOR TILE. FLOOR
 INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE,
 MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE
 & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR
 AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 3) NEW THROUGH FLOOR PENETRATIONS. THROUGH-PENETRATIONS
 FIRESTOP SYSTEMS (HORIZONTAL ASSEMBLIES). IF A NEW
 FLOOR PENETRATION IS MADE FOR THE FUTURE SHOWER DRAIN,
 THEN YOU NEED TO SHOW COMPLIANCE WITH THE 2020 FBC-B
 SECTION 714.5.1.2. THROUGH-PENETRATIONS FIRESTOP
 SYSTEMS (HORIZONTAL ASSEMBLIES). THROUGH PENETRATIONS
 SHALL BE PROTECTED BY A THROUGH PENETRATION FIRESTOP
 SYSTEM INSTALLED IN ACCORDANCE WITH ASTM E814 OR UL
 1479. THE SYSTEM SHALL HAVE AN F RATING / T RATING OF
 NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED
 RATING OF THE FLOOR PENETRATED.
  
 4) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A
 BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM (MR BOARD) SHALL NOT BE USED FOR
 SHOWER & TUB ENCLOSURES BUT CAN BE USED FOR BACKING
 BOARD FOR A BASE FOR TILE IN WATER CLOSET COMPARTMENT
 WALLS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840 AND THE MANUFACTURE?S RECOMMENDATIONS.
  
 5) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-09-02 Cont ID  
Sent By jleahy Date 2022-09-02 Time 12:05 Rev Time 0.00
Received By jleahy Date 2022-09-02 Time 11:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-02 Cont ID  
Sent By cwalker Date 2022-09-02 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-09-02 09:34:24FIRE PROVISO COMMENTS:
  
 ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND OR
 FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL PHASES
 OF DEMOLITION AND CONSTRUCTION.
  
 ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR
 FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 ANY WORK ON ANY LIFE SAFETY SYSTEM (FIRE SPRINKLER
 AND/OR FIRE ALARM) MUST BE CONDUCTED UNDER SEPARATE
 PERMITS AND SHOP DRAWINGS.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By aoliver Date 2022-09-20 Time 07:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-08 Cont ID  
Sent By jwitmer Date 2022-09-08 Time 09:46 Rev Time 0.00
Received By asangele Date 2022-09-08 Time 09:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-09-22 Cont ID  
Sent By medwards Date 2022-09-22 Time 10:18 Rev Time 0.00
Received By medwards Date 2022-09-22 Time 10:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-09-21 Cont ID  
Sent By medwards Date 2022-09-21 Time 10:45 Rev Time 0.00
Received By medwards Date 2022-09-21 Time 10:45 Sent To  
Notes
2022-09-21 10:46:31PLEASE PROVIDE THE REQUESTED INFORMATION FROM PREVIOUS
 REVIEW COMMENTS BELOW.
  
 PROVIDE A MECHANICAL DRAWING THAT SHOWS THE CHANGES IN
 THE MECHANICAL SYSTEM. THIS DRAWING MUST HAVE THE
 DESIGNERS PRINTED NAME AND SIGNATURE ALONG WITH THE JOB
 ADDRESS. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-09-01 Cont ID  
Sent By medwards Date 2022-09-01 Time 07:20 Rev Time 0.00
Received By medwards Date 2022-09-01 Time 07:20 Sent To  
Notes
2022-09-01 07:22:02PROVIDE A MECHANICAL DRAWING THAT SHOWS THE CHANGES IN
 THE MECHANICAL SYSTEM. THIS DRAWING MUST HAVE THE
 DESIGNERS PRINTED NAME AND SIGNATURE ALONG WITH THE JOB
 ADDRESS. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-09-22 Cont ID  
Sent By ccole Date 2022-09-22 Time 08:52 Rev Time 0.00
Received By ccole Date 2022-09-22 Time 08:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-09-02 Cont ID  
Sent By ccole Date 2022-09-02 Time 06:53 Rev Time 0.00
Received By ccole Date 2022-09-02 Time 06:34 Sent To  
Notes
2022-09-02 06:54:371ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22071084
 9/2/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A PLUMBING RISER DRAWING SHOWING NEW DRAIN
 AND VENT PIPING CONNECTIONS FOR THE RELOCATED TOILET-
 SEC. 107.3.5.1.3 WPB.
  
 2) PLEASE SHOW A NEW SHOWER PAN LINER WILL BE INSTALLED
 AT THE NEW SHOWER. THE PLAN NOTE INDICATES AN EXISTING
 LINER- SEC. 421.5.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-09-02 Cont ID  
Sent By ccole Date 2022-09-02 Time 06:55 Rev Time 0.00
Received By ccole Date 2022-09-02 Time 06:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status N Date 2022-09-08 Cont ID  
Sent By dbattles Date 2022-09-08 Time 14:32 Rev Time 0.00
Received By dbattles Date 2022-09-08 Time 14:32 Sent To  
Notes
2022-09-08 14:32:50INTERIOR WORK ONLY.

Review Stop Z ZONING
Rev No 1 Status F Date 2022-09-08 Cont ID  
Sent By asangele Date 2022-09-08 Time 09:42 Rev Time 0.00
Received By asangele Date 2022-09-08 Time 09:42 Sent To  
Notes
2022-09-08 09:45:48FAILED
 9/8/2022
  
 YOU CANNOT REMOVE THE EXTERIOR WALL PLEASE PROVIDE
 CLARIFICATION.
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]