Plan Review Details - Permit 22071043
Plan Review Stops For Permit 22071043
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-09-26 Cont ID  
Sent By rmcdouga Date 2022-09-26 Time 14:54 Rev Time 0.00
Received By rmcdouga Date 2022-09-26 Time 14:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-09-20 Cont ID  
Sent By rmcdouga Date 2022-09-20 Time 09:58 Rev Time 0.00
Received By rmcdouga Date 2022-09-20 Time 09:58 Sent To  
Notes
2022-09-20 10:02:46PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE COMMENTS FROM THE PREVIOUS REVIEW WERE NOT
 RESOLVED.
  
 1) THE SOUND TESTING REPORTS THAT YOU SUBMITTED ARE FOR
 A 6" SLAB WITH A SUSPENDED CEILING BELOW IT. THIS
 BUILDING DOES NOT HAVE A SUSPENDED CEILING BELOW THE
 FLOOR. THE TEST HAS TO MATCH THE CONDITIONS AT THE
 SITE. SUBMIT THE FOLLOWING TEST REPORTS FOR THE SOUND
 UNDERLAYMENT: E-90 & E-492.
  
 - FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 - FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 SUBMIT THE TEST REPORTS FOR THE SOUND INSULATION WHERE
 THERE IS NO CEILING ASSEMBLY BELOW THE FLOOR SLAB.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-09-06 Cont ID  
Sent By rmcdouga Date 2022-09-06 Time 14:49 Rev Time 0.00
Received By rmcdouga Date 2022-09-06 Time 14:49 Sent To  
Notes
2022-09-06 15:27:07PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SOUND TESTING REPORTS THAT YOU SUBMITTED ARE FOR
 A 6" SLABE WITH A SUSPENDED CEILING BELOW IT. THIS
 BUILDING DOES NOT HAVE A SUSPENDED CEILING BELOW THE
 FLOOR. THE TEST HAS TO MATCH THE CONDITIONS AT THE
 SITE. SUBMIT THE FOLLOWING TEST REPORTS FOR THE SOUND
 UNDERLAYMENT: E-84, E-90 & E-492.
 - FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 - FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 - FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 SUBMIT THE TEST REPORTS FOR THE SOUND INSULATION
 INCLUDING FLAME SPREAD AND SMOKE DEVELOPED FOR THE
 APPLICABLE CONSTRUCTION CONDITIONS.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-09-08 Cont ID  
Sent By cwalker Date 2022-09-08 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-08-02 Cont ID  
Sent By cwalker Date 2022-08-02 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-08-02 10:45:45PROVIDE TESTING DATA FOR THE NEW VINYL FLOORING AND THE
 UNDERLAYMENT FOR THE PRODUCT FIRE PERFORMANCE INCULDING
 THE CRITICAL RADIANT FLUX FOR BOTH FINISH FLOOR AND
 UNDERLAYMENT. NFPA 101, 10.2.7
  
 C. WALKER
  
 561-804-4762
  
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-26 Cont ID  
Sent By rmcdouga Date 2022-09-26 Time 14:54 Rev Time 0.00
Received By rmcdouga Date 2022-09-21 Time 06:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-20 Cont ID  
Sent By rmcdouga Date 2022-09-20 Time 09:58 Rev Time 0.00
Received By rmcdouga Date 2022-09-07 Time 14:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-06 Cont ID  
Sent By rmcdouga Date 2022-09-06 Time 14:49 Rev Time 0.00
Received By rmcdouga Date 2022-08-01 Time 06:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-09-06 Cont ID  
Sent By rmcdouga Date 2022-09-06 Time 14:49 Rev Time 0.00
Received By rmcdouga Date 2022-09-06 Time 14:49 Sent To  
Notes
***NONE***