Plan Review Details - Permit 22071010
Plan Review Stops For Permit 22071010
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-11-30 Cont ID  
Sent By rmcdouga Date 2022-11-30 Time 13:28 Rev Time 0.00
Received By rmcdouga Date 2022-11-30 Time 13:28 Sent To  
Notes
2022-11-30 13:30:20THIS VEHICLE CHARGING STATION IS NOT FOR PUBLIC USE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-09-30 Cont ID  
Sent By rmcdouga Date 2022-09-30 Time 15:09 Rev Time 0.00
Received By rmcdouga Date 2022-09-30 Time 14:14 Sent To  
Notes
2022-09-30 14:54:04PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY INTENDED USERS OF THE CAR CHARGING STATION.
 FOR EXAMPLE ARE THEY FOR THE USE OF THE EMPLOYEES,
 FLEET VEHICLES, CUSTOMERS, ETC. FBC AMENDMENTS 107.2.1
  
 2) IF THE CHARGING STATION IS FOR USE BY THE PUBLIC,
 SHOW HOW THE CAR CHARGING STATION AND PARKING COMPLY
 WITH FBC ACCESSIBILITY. NOTE: THE BUILDING OFFICIAL HAS
 DETERMINED THAT ACCESSIBLE CHARGING STATIONS ARE TO BE
 PROVIDED BASED ON THE NUMBER OF CHARGING STATIONS
 PROVIDED AT EACH LOCATION USING FBC ACCESSIBILITY TABLE
 208.2. IF THERE ARE BETWEEN 1 - 25 PARKING SPACES
 PROVIDED WITH CHARGING STATIONS, THEN 1 SUCH SPACE MUST
 BE ACCESSIBLE. ADVISORY 208.2 MINIMUM NUMBER. THE TERM
 "PARKING FACILITY" IS USED IN SECTION 208.2 INSTEAD OF
 THE TERM "PARKING LOT" SO THAT IT IS CLEAR THAT BOTH
 PARKING LOTS AND PARKING STRUCTURES ARE REQUIRED TO
 COMPLY WITH THIS SECTION. THE NUMBER OF PARKING SPACES
 REQUIRED TO BE ACCESSIBLE IS TO BE CALCULATED
 SEPARATELY FOR EACH PARKING FACILITY; THE REQUIRED
 NUMBER IS NOT TO BE BASED ON THE TOTAL NUMBER OF
 PARKING SPACES PROVIDED IN ALL OF THE PARKING
 FACILITIES PROVIDED ON THE SITE.
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-10 Cont ID  
Sent By jleahy Date 2022-12-10 Time 12:08 Rev Time 0.00
Received By jleahy Date 2022-12-10 Time 11:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-08-13 Cont ID  
Sent By jleahy Date 2022-08-13 Time 17:48 Rev Time 0.00
Received By jleahy Date 2022-08-13 Time 17:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-12-10 Cont ID  
Sent By jleahy Date 2022-12-10 Time 12:09 Rev Time 0.00
Received By jleahy Date 2022-12-05 Time 09:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-11-30 Cont ID  
Sent By rmcdouga Date 2022-11-30 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2022-10-05 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-30 Cont ID  
Sent By rmcdouga Date 2022-09-30 Time 15:09 Rev Time 0.00
Received By rmcdouga Date 2022-08-24 Time 16:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-13 Cont ID  
Sent By jleahy Date 2022-08-13 Time 17:48 Rev Time 0.00
Received By jleahy Date 2022-08-10 Time 07:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-12-10 Cont ID  
Sent By jleahy Date 2022-12-10 Time 12:09 Rev Time 0.00
Received By jleahy Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-11-30 Cont ID  
Sent By rmcdouga Date 2022-11-30 Time 13:51 Rev Time 0.00
Received By rmcdouga Date 2022-11-30 Time 13:50 Sent To  
Notes
2022-11-30 14:33:27FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 1) PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN. FBC
 107.2.1, FS 471, 481
  
 2) ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO
 HAVE THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON
 THEM. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-09-30 Cont ID  
Sent By rmcdouga Date 2022-09-30 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2022-09-30 Time 14:14 Sent To  
Notes
2022-09-30 14:46:46ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 FS 481 & FAC 61G1 OR FS 471 & FAC 61G15
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-13 Cont ID  
Sent By jleahy Date 2022-08-13 Time 17:48 Rev Time 0.00
Received By jleahy Date 2022-08-13 Time 17:48 Sent To  
Notes
2022-08-13 17:50:06FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN. FBC 107.2.1,
 FS 471, 481