Plan Review Details - Permit 22070842
Plan Review Stops For Permit 22070842
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-08-31 Cont ID  
Sent By cpuell Date 2022-08-31 Time 09:30 Rev Time 0.00
Received By cpuell Date 2022-08-31 Time 09:30 Sent To  
Notes
2022-08-31 09:30:48WORK TO BE DONE ON THE NORTH BUILDING WITH THE ADDRESS
 OF 404 10TH ST

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-08-29 Cont ID  
Sent By cpuell Date 2022-08-29 Time 14:10 Rev Time 0.00
Received By cpuell Date 2022-08-29 Time 14:10 Sent To  
Notes
2022-08-29 14:11:07UNIT A IS NOT A RECOGNIZED ADDRESS, PLEASE INDOCATE IF
 THE WORK IS FOR THE NORTH OR THE SOUTH BUILDING, IS IT
 ONLY FOR 1 UNIT OR THE WHOLE BUILDING. PLEASE RESPOND
 TO [email protected] OR CALL 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-09-13 Cont ID  
Sent By rmcdouga Date 2022-09-13 Time 17:25 Rev Time 0.00
Received By rmcdouga Date 2022-09-13 Time 17:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-19 Cont ID  
Sent By rmcdouga Date 2022-08-19 Time 14:02 Rev Time 0.00
Received By rmcdouga Date 2022-08-19 Time 13:47 Sent To  
Notes
2022-08-19 14:11:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE ARE TWO STRUCTURES ON THE PROPERTY. PROVIDE A
 SITE PLAN THAT CLEARLY INDICATES THE STRUCTURE THAT IS
 TO BE REPAIRED. FBC AMENDMENTS 107.2.1
  
 2) THE PROPERTY APPRAISER SHOWS THIS AS A MULTIFAMILY
 PROPERTY. SPECIFY THE NUMBER OF SEPARATE LIVING UNITS
 THAT ARE LOCATED IN THE STRUCTURE THAT IS TO BE
 REPAIRED. FBC 107.2.1
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-09-01 Cont ID  
Sent By pleduc Date 2022-09-01 Time   Rev Time 0.00
Received By pleduc Date 2022-09-01 Time 12:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-07-28 Cont ID  
Sent By pleduc Date 2022-07-28 Time   Rev Time 0.00
Received By pleduc Date 2022-07-28 Time 12:29 Sent To  
Notes
2022-07-28 12:53:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE ENGINEER REPORT UNDER PROJECT ASSUMPTION # 1,
 INDICATES THE BUILDING IS A SINGLE FAMILY HOME.
  
 MY RECORDS INDICATE THAT THIS IS A MULTI UNIT APARTMENT
 BUILDING.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE REVIEW TO ENSURE CORRECT IDENTIFICATION.
  
  
 1A) THERE IS NO INDICATION OF IF THIS BUILDING AND
 MUTIPLE FAMILY RESIDENTS WILL BE ALLOWED TO REMAIN OR
 REQUIRED TO VACANT DURING THE CONSTRUCTION PROCESSING.
  
 IS THERE ANY DANGER OF COLLASPE OR WILL ANY EXITS BE
 BLOCKED BY THE CONSTRUCTION PROCESSES?
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS AND /OR A
 SITE PLAN AFFORDING PROTECTION OF THE RESIDENTS AND
 EXITING IN CASE OF EMERGENCY.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-14 Cont ID  
Sent By shill Date 2022-09-14 Time 15:45 Rev Time 0.00
Received By shill Date 2022-08-31 Time 08:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-29 Cont ID  
Sent By cpuell Date 2022-08-29 Time 14:11 Rev Time 0.00
Received By cpuell Date 2022-07-27 Time 07:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-08-19 Cont ID  
Sent By rmcdouga Date 2022-08-19 Time 14:01 Rev Time 0.00
Received By rmcdouga Date 2022-08-19 Time 14:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-09-07 Cont ID  
Sent By kdefranc Date 2022-09-07 Time 14:21 Rev Time 0.00
Received By kdefranc Date 2022-09-07 Time 14:20 Sent To  
Notes
2022-09-07 14:21:029/7/22 - PASSED
  
 PREVIOUS REVIEW COMMENT:
 1. PLEASE PROVIDE A REVISED IRRIGATION PLAN
 IDENTIFYING/INDICATING/DEMONSTRATING THE PROPOSED
 BACKFLOW ASSEMBLIES, METERS, CONTROLLERS, AND RAIN
 SENSORS IN THE LOCATION AS DEMONSTRATED IN THE
 IRRIGATION PLAN APPROVED BY RESOLUTION NO. 29-22.
 [WITHDRAWN]
  
  
 KEVIE DEFRANC
 PLANNER ? PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-08-01 Cont ID  
Sent By kdefranc Date 2022-08-01 Time 12:26 Rev Time 0.00
Received By kdefranc Date 2022-08-01 Time 12:24 Sent To  
Notes
2022-08-01 12:25:598/1/22 ? FAILED
  
 REVIEW COMMENT TO BE ADDRESSED:
 1. PLEASE PROVIDE A REVISED IRRIGATION PLAN
 IDENTIFYING/INDICATING/DEMONSTRATING THE PROPOSED
 BACKFLOW ASSEMBLIES, METERS, CONTROLLERS, AND RAIN
 SENSORS IN THE LOCATION AS DEMONSTRATED IN THE
 IRRIGATION PLAN APPROVED BY RESOLUTION NO. 29-22.
  
  
 KEVIE DEFRANC
 PLANNER ? PLANNING DIVISION
 [email protected]
 561-822-1449
  