Plan Review Details - Permit 22070830
Plan Review Stops For Permit 22070830
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-02-28 Cont ID  
Sent By jwitmer Date 2023-02-28 Time 09:05 Rev Time 0.00
Received By jwitmer Date 2023-02-28 Time 06:42 Sent To  
Notes
2023-02-28 09:04:59BUILDING PROVISO: ) SHEET S-302 & S-303 HAS SEVERAL
 DETAILS REQUIRING SITE WELDING WELDED OR BOLTED
 CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND
 OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD
 BRUNELLE AT 561-805-6670.
  
  
 NFPA PASSED: TIGER ENCLOSURE, FOUNDATIONS FOR POLES,
 BOTTOM RAIL FOR FENCE/ MESH ENCLOSURE PLUS 2 GATE
 CONTROLS, 1ST A GULLOTINE TYPE GATE, THE 2ND RAISED
 STRUCTURE WITH CABLES FOR GULLOTINE GATE STRUCTURE,
 EARTH FLOOR WITHIN THE TIGER ENCLOSURE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By jwitmer Date 2022-10-25 Time 13:00 Rev Time 0.00
Received By jwitmer Date 2022-10-25 Time 10:32 Sent To  
Notes
2022-10-25 13:00:32WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22070830
 ADD: 1301 SUMMIT BLVD. (TIGER EXIHIBIT EXSPANSION)
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 25TH/ 2022
 ACTION: DENIED
 1) NO PERMIT APPLICATION WAS SUBMITTED WITH THIS
 REVIEW. 2020 FLORIDA BUILDING CODE W 2020 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 105.1 PERMITS. SHALL FIRST MAKE
 APPLICATION TO THE BUILDING OFFICIAL AND OBTAIN THE
 REQUIRED PERMIT.
 2) SUPPORTING DOCUMENTS, THERE ARE 66 PAGES OF
 SPECIFICATIONS TO BE USED FOR BID PURPOSES, SOMETHING
 WE DO NOT REVIEW, SHOULD NOT BE LOADED EACH PAGE, IF
 SUBMITTED THIS DOCUMENT NEEDS TO BE ONE DOCUMENT, NOT
 66 PAGES, THIS IS FOR CONTRACTORS TO BID FROM. PLEASE
 REFORMATE INTO ONE DOCUMENT.
 3) THE PLANS WERE NOT LOADED IN ORDER OF THE DRAWING
 INDEX, FOR EXAMPLE THE 7 PAGES OF EXISTING SITE SURVEY
 WERE NOT LOADED CONSECUTIVELY, THERE ARE STRUCTURAL
 SHEETS LOADED BETWEEN.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION:
  
 107.2.1.3. QUALITY OF PLANS. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS FOR
 THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 4) THE EXISTING 7PAGES OF SITE SURVEY DO NOT REFLECT
 THAT ALL OF THE ZOO IS IN AN AE FLOOD ZONE NAVD88 BFE
 IS 12.2???. THIS NEEDS TO BE ADDED TO THE SURVEY AND
 FOR THE TIGER EXHIBIT EXPANSION SHOW EXISTING
 ELEVATIONS IN NAVD88.
  
 5) IT IS NOT CLEAR IF THE TIGER NIGHT HOUSE IS BEING
 RENOVATED OR NOT. ENCLOSED BUILDINGS THAT ARE PART OF
 THIS PROJECT WILL NEED TO PROVIDE THEIR FINISH FLOOR
 HEIGHT IN NAVD 88 SINCE THEY ARE LOCATED WITHIN AN AE
 FLOOD ZONE WITH A BFE AT 12.2 FEET. WITH THE DOLLAR
 AMOUNT BEING SPENT IT WOULD APPEAR A SUBSTANTIAL
 IMPROVEMENT WILL OCCUR AND NEED TO MEET THE CURRENT
 STANDARD OF A 2-FOOT FREEBOARD OR PROVIDE FLOODPROOFING
 METHODS TO THE HEIGHT OF 14.2 FT. NAVD88.
  
 1612.5 FLOOD HAZARD DOCUMENTATION. WEST PALM BEACH MUNI
 CODE. ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD
 PREVENTION & CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW
 CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN
 ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF PERMIT
 APPLICATION AFTER SEPT. 12/2016,
 AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
 AFTER OCT. 11/ 2017 THE BUILDING DEPARTMENT WILL HAVE
 ADOPTED THE NEW FLOOD MAPS IN NAVD 88 ELEVATIONS. YOU
 CAN GO TO THE WEBSITE:
 WWW.NGS.NOAA.GOV/TOOLS/VERTCON/VERTCON.HTML FOR
 CONVERSIONS.
  
  
 SUBSTANIAL IMPROVEMENT. SECTION 94-546 PROVISIONS FOR
 FLOOD HAZARD REDUCTION. (A)(3) ANY ALTERATION, REPAIR,
 RECONSTRUCTION, OR IMPROVEMENTS TO A PROPERTY WHICH THE
 CUMULATIVE COST FOR ANY FIVE YEAR PERIOD EQUALS OR
 EXCEEDS 50 % OF THE BUILDING VALUE AT THE COMMENCEMENT
 OF THE FIVE YEAR PERIOD SHALL MEET THE REQUIREMENTS OF
 NEW CONSTRUCTION AS CONTAINED IN THIS ARTICLE.
 CERTIFIED APPRAISAL.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
  
 (2) ONCE THE FIRST-FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
  
 6) SHEET S-002;
 6A) THE WIND DESIGN IS LABELED A B EXPOSURE WITH I-95
 BEING JUST WEST OF THE ZOO AND THE DRYER PARK LAND TO
 THE NORTH & SOUTH OF THE ZOO, THERE ARE NO STRUCTURES
 NORTH OF SOUTH OF THE ZOO FOR OVER A MILE WIDE, AND
 VIEWING THE LOCATION OF THE ZOO EAST TO WEST THERE
 WOULD BE AT LEAST 1,200 FEET WITH NO STRUCTURES IN
 AREAS THIS COULD BE OVER 1,500 FT, THIS IS CLEARLY A C
 EXPOSURE.
  
 6B) THE PRESSURE CHART FOR ROOF AND WALLS WILL CHANGE
 WITH WALLS AND ROOF THAT OVER 15 FEET IN HEIGHT BECAUSE
 OF THE ADJUSTMENT FACTORS FOR HEIGHT & EXPOSURE. .
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 6C) A GEOTECHNICAL REPORT BY NUTTING ENGINEERING #
 19780 WAS COMPLETED 12/21 PLEASE PROVIDE EITHER A PAPER
 FORM SIGNED AND SEALED OR ELECTRONIC FORM WITH DIGITAL
 SIGNATURES THIS IS AND AREA OF QUESTIONABLE SOILS. 2020
 FBC-BUILDING 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 6D) HEADING SPECIAL INSPECTIONS. IN THE 2020
 FBC-BUILDING CODE SECTION 1704 AND 1705 ARE RESERVED.
  
 7) SHEET S-302 & S-303 HAS SEVERAL DETAILS REQUIRING
 SITE WELDING WELDED OR BOLTED CONNECTIONS. THIS
 BUILDING CONTAINS EITHER BOLTED AND OR WELDED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR RICHARD
 BRUNELLE AT 561-805-6670.
  
 8) DRAWING INDEX SHOWS PLUMBING AND ELECTRICAL SHEETS
 BUT NO SUCH SHEETS WERE UPLOADED?
 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 9) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-02-22 Cont ID  
Sent By mpeterso Date 2023-02-22 Time 13:14 Rev Time 0.00
Received By mpeterso Date 2023-02-22 Time 11:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-10-25 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2022-10-25 13:05:43NO ELECTRICAL SHEETS SUBMITTED THIS REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2023-02-21 Cont ID  
Sent By rrossano Date 2023-02-21 Time   Rev Time 0.00
Received By rrossano Date 2023-02-21 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-02-21 Cont ID  
Sent By pleduc Date 2023-02-21 Time   Rev Time 0.00
Received By pleduc Date 2023-02-16 Time 09:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-19 Cont ID  
Sent By   Date 2022-09-19 Time   Rev Time 0.00
Received By bdolan Date 2022-09-19 Time 11:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2023-02-28 Time   Rev Time 0.00
Received By lmarchan Date 2023-02-15 Time 16:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-10-25 Time   Rev Time 0.00
Received By cdecoeur Date 2022-09-09 Time 08:27 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status N Date 2023-02-28 Cont ID  
Sent By jwitmer Date 2023-02-28 Time 09:01 Rev Time 0.00
Received By jwitmer Date 2023-02-28 Time 06:41 Sent To  
Notes
2023-02-28 09:01:16TIGER ENCLOSURE, FOUNDATIONS FOR POLES, BOTTOM RAIL FOR
 FENCE/ MESH ENCLOSURE PLUS 2 GATE CONTROLS, 1ST A
 GULLOTINE TYPE GATE, THE 2ND RAISED STRUCTURE WITH
 CABLES FOR GULLOTINE GATE STRUCTURE, EARTH FLOOR WITHIN
 THE TIGER ENCLOSURE.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By jwitmer Date 2022-10-25 Time 13:05 Rev Time 0.00
Received By jwitmer Date 2022-10-25 Time 11:16 Sent To  
Notes
2022-10-25 11:26:381) THE PLANS WERE NOT LOADED IN ORDER OF THE DRAWING
 INDEX, FOR EXAMPLE THE 7 PAGES OF EXISTING SITE SURVEY
 WERE NOT LOADED CONSECUTIVELY, THERE ARE STRUCTURAL
 SHEETS LOADED BETWEEN.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION:
  
 107.2.1.3. QUALITY OF PLANS. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS FOR
 THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 2) THE EXISTING 7PAGES OF SITE SURVEY DO NOT REFLECT
 THAT ALL OF THE ZOO IS IN AN AE FLOOD ZONE NAVD88 BFE
 IS 12.2???. THIS NEEDS TO BE ADDED TO THE SURVEY AND
 FOR THE TIGER EXHIBIT EXPANSION SHOW EXISTING
 ELEVATIONS IN NAVD88.
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-02-21 Cont ID  
Sent By ccole Date 2023-02-21 Time 10:54 Rev Time 0.00
Received By ccole Date 2023-02-21 Time 10:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-10-25 Cont ID  
Sent By jwitmer Date 2022-10-25 Time 13:03 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-10-25 13:04:11NO PLUMBING SHEET SUBMITTED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-02-22 Cont ID  
Sent By mpeterso Date 2023-02-22 Time 13:34 Rev Time 0.00
Received By mpeterso Date 2023-02-22 Time 13:34 Sent To  
Notes
2023-02-22 13:35:55PASSED SIGNATURE. FIRST TIME FOR MICHAEL LEONARD PE
 SELF-CERTIFYING SIGNATURE. ADDED TO THE LIST. MP
2023-02-21 10:29:16PLUMBING (P) PLANS APPROVED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-10-25 Cont ID  
Sent By jwitmer Date 2022-10-25 Time 13:03 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-10-25 13:03:16THERE WERE NO SIGNATURE NOR SEAL ON ANY SHEETS FFROM
 ANY ARCHITECT OR ENGINEER. . 107.1 SUBMITTAL DOCUMENTS/
 SIGNATURES & SEALS. IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT, INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR
 ENGINEER LEGALLY REGISTERED UNDER THE LAWS OF THIS
 STATE REGULATING THE PRACTICE OF ARCHITECTURE OR
 INTERIOR DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART 1, OR LANDSCAPE ARCHITECT AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTES.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2023-02-21 Cont ID  
Sent By jroach Date 2023-02-21 Time 13:32 Rev Time 0.00
Received By jroach Date 2023-02-21 Time 13:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-09-21 Cont ID  
Sent By jroach Date 2022-09-21 Time 11:38 Rev Time 0.00
Received By jroach Date 2022-09-21 Time 11:32 Sent To  
Notes
***NONE***