| 2022-08-04 16:47:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22070773 320 BELVEDERE RD |
| | |
| | |
| | 1ST REVIEW |
| | |
| | PROVISO: P-4.01/PLUMBING FIXTURE SCHEDULE CALLS FOR |
| | SELECTION OF FIXTURES BY OWNER/ARCHITECT. A PLAN |
| | REVISION WILL BE REQUIRED SHOWING THE MANUFACTURER, |
| | MODEL. REVISION SHALL BE SUBMITTED, APPROVED AND IN |
| | PLACE AT TIME OF FINAL INSPECTION. |
| | |
| | PROVISO: P-2.01/KEYNOTES 20/21: A 3 INCH SANITARY DRAIN |
| | IS NOTED FOR THE DRY STORAGE ROOM; CONNECTION TO |
| | EXISTING SANITARY. A PLAN REVISION WILL BE REQUIRED |
| | SHOWING THE CONNECTION TO EXISTING. REVISION SHALL BE |
| | SUBMITTED, APPROVED AND IN PLACE AT TIME OF FINAL |
| | INSPECTION. |
| | |
| | PROVISO: RMS 128/129 AND 130/131 ARE RECONFIGURED TO |
| | ELIMINATE ONE BATHROOM IN EACH CONFIGURATION. A PLAN |
| | REVISION WILL BE REQUIRED SHOWING THE REVISED WATER AND |
| | SANITARY. REVISION SHALL BE SUBMITTED, APPROVED AND IN |
| | PLACE AT TIME OF FINAL INSPECTION. |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. THE BACKFLOW PERMIT AND INTERCEPTOR PERMITS ARE |
| | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| | PRIMARY PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO |
| | BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED |
| | BY EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. |
| | A SEPARATE PERMIT IS REQUIRED FOR EACH, HOWEVER A |
| | REVIEW OF THE SYSTEMS UNDER THE MAIN PERMIT IS ALSO |
| | REQUIRED. |
| | |
| | 2. GREASE INTERCEPTOR: P-1.00 CALLS FOR A GB-500 |
| | INTERCEPTOR; P-4.04 CALLS FOR A GB-250 INTERCEPTOR. |
| | ADDITIONALLY P-1.00 REFERS TO P-4.02 AND SHOULD REFER |
| | TO P-4.04. PER WPB FBC 107.2.1, PLEASE CLARIFY AND |
| | RECONCILE THE TWO PLANS. |
| | |
| | 3. GREASE INTERCEPTOR: PROVIDE AN ENLARGED PIPING |
| | DIAGRAM SHOWING THE LOCATIONS OF CLEANOUTS, SAMPLING |
| | POINT AND VENTS AS REQUIRED BY THE MANUFACTURER AND FBC |
| | PL 1003.9. COORDINATE AND RECONCILE WITH P-1.00 |
| | |
| | 4.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| | FOR NEW TOILET ROOM INDICATING THE FOLLOWING: |
| | ***B) A.602/ KEYNOTE 3: PLUMBING FIXTURE SCHEDULE CALL |
| | FOR FLOOR MOUNTED WATER CLOSET. PER FBC ACC 604.8.1.1., |
| | PROVIDE A 60 INCH BY 59 INCH CLEAR FLOOR SPACE FOR THE |
| | WATER CLOSET. RECONCILE WITH A.601/WATER CLOSET DETAIL. |
| | ***F) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL |
| | COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 |
| | INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED |
| | BEHIND GRAB BARS. |
| | ***J) A.602; CLEAR FLOOR SPACE FOR URINAL DOES NOT |
| | MATCH THE ELEVATION. PER WPB FBC 107.2.1, PLEASE |
| | CLARIFY AND RECONCILE. |
| | ***K) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER |
| | SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE |
| | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| | CONTACT. |
| | ***L) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 603.3. |
| | ***M) PROVIDE ELEVATION DETAIL FOR THE DRINKING |
| | FOUNTAIN SHOWING COMPLIANCE WITH FBC ACC 602.2, 602.3, |
| | 602.4, 602.5 AND 602.7 |
| | |
| | 5.MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR |
| | THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING: |
| | ***A) WATER HEATER(S) |
| | ***B) BACKFLOW PREVENTER DEVICES |
| | ***C) THERMOSTATIC MIXING VALVES |
| | ***D) KITCHEN EQUIPMENT |
| | |
| | 6.P-2.01/KEYNOTE 2, A.101B/KEYNOTE 15 AND |
| | A.101C/KEYNOTE 15, D.101/KEYNOTE 27: ALL NOTE REMOVAL |
| | OF EXISTING PLUMBING FIXTURES AND REPLACE WITH NEW. RMS |
| | 128/129 AND 130/131 ARE RECONFIGURED TO ELIMINATE ONE |
| | BATHROOM IN EACH CONFIGURATION. |
| | PER WPB FBC 107.2.1., PROVIDE THE FOLLOWING: |
| | ***A) PER FBC ACC 809.4, PLEASE IDENTIFY THE ACCESSIBLE |
| | GUEST ROOMS AND PROVIDE ELEVATION AND PLAN DETAILS FOR |
| | ACCESSIBLE BATHING ROOM(S) SHOWING COMPLIANCE WITH FBC |
| | ACC 603 THROUGH 610. |
| | ***B) REGARDING THE SHOWERS; WILL THEY BE TILE FLOOR |
| | WITH LINER OR A MANUFACTURED COMPARTMENT OR BASE? |
| | IF MANUFACTURED, PROVIDE A MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUAL. SHOW COMPLIANCE WITH |
| | FBC PL 421.1. ASME A112.19.2/CSA B45.1 OR CSA |
| | B45.5/IAPMO Z124. |
| | IN ALL CASES, PER FBC PL 421.4.1, BATHTUB FLOORS, |
| | SHOWER FLOORS, WALL AREAS ABOVE BUILT-IN TUBS THAT HAVE |
| | INSTALLED SHOWER HEADS AND WALLS IN SHOWER COMPARTMENTS |
| | SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND |
| | NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL |
| | EXTEND TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM) |
| | ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES |
| | (1778 MM) ABOVE THE DRAIN OF THE TUB OR SHOWER. SUCH |
| | WALLS SHALL FORM A WATER-TIGHT JOINT WITH EACH OTHER |
| | AND WITH EITHER THE TUB OR SHOWER FLOOR. |
| | IF TILE FLOOR, PROVIDE A CROSS-SECTION SHOWER |
| | WALL/FLOOR/DRAIN AND THRESHOLD DETAIL |
| | DETAIL SHALL INCLUDE ALL COMPONENTS OF FBC PL 421.5.2 |
| | AS FOLLOWS |
| | LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 |
| | INCHES ABOVE THE FINISHED THRESHOLD LEVEL |
| | LINERS SHALL BE RECESSED AND FASTENED TO AN APPROVED |
| | BACKING |
| | LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY POINT |
| | LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD |
| | LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12 |
| | UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED |
| | TOWARD THE FIXTURE DRAIN |
| | LINERS SHALL BE SECURELY FASTENED TO THE WASTE OUTLET |
| | AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT JOINT |
| | BETWEEN THE LINER AND THE OUTLET |
| | FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE |
| | LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY |
| | SOUND BASE. |
| | LINER MATERIAL (SPECIFY LINER MATERIAL COMPLYING WITH |
| | ONE OF THE FOLLOWING FBC PL SECTIONS-421.5.2.1, |
| | 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5 OR |
| | 421.5.2.6.) NOTE THAT FBC PL 421.5.2.1 PLASTICIZED |
| | POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE |
| | REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED. |
| | ***C) PROVIDE A SPECIFICATION FOR THE SHOWER CONTROL |
| | VALVE SHOWING COMPLIANCE WITH FBC PL 412.3. INDIVIDUAL |
| | SHOWER AND TUB-SHOWER COMBINATION VALVES SHALL BE |
| | BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION |
| | BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO |
| | THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA |
| | B125.16 OR ASME A112.18.1/CSA B125.1 |
| | ***D) RMS 128/129 AND 130/131 ARE RECONFIGURED TO |
| | ELIMINATE ONE BATHROOM IN EACH CONFIGURATION. A PLAN |
| | REVISION WILL BE REQUIRED SHOWING THE REVISED WATER AND |
| | SANITARY. REVISION SHALL BE SUBMITTED, APPROVED AND IN |
| | PLACE AT TIME OF FINAL INSPECTION. |
| | |
| | |
| | 7.P-3.01/KITCHEN: ITEMS 1.1, 1.3 AND 90, EVAPORATOR |
| | COIL DRAINS SHALL NOT DISCHARGE TO THE GREASY WASTE |
| | (FBC PL 1003.2), OR TO SANITARY (WPB CODE OF ORDINANCE |
| | CHAPTER 90, ARTICLE 3, SECTION 90-12B5). PER WPB FBC |
| | 107.2.1, DISCHARGE TO STORM OR TO DRYWELL. PROVIDE |
| | ROUTING AND A DETAIL. |
| | |
| | 8. P-3.01/KITCHEN: ITEMS 84, 85, 88 AND FLOOR DRAINS |
| | NOT RECEIVING GREASY WASTE SHALL NOT DISCHARGE TO THE |
| | GREASY WASTE (FBC PL 1003.2). DISCHARGE TO SANITARY. |
| | |
| | 9. P-3.01/KITCHEN: PER FBC PL 708.1.3, PROVIDE AN |
| | IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF THE |
| | BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 AS |
| | WELL. |
| | |
| | 10. P-3.02/BAR: UNDERCOUNTER REFRIGERATION COIL AND |
| | BACK BAR COOLER SHALL NOT DISCHARGE TO THE GREASY WASTE |
| | (FBC PL 1003.2), OR TO SANITARY (WPB CODE OF ORDINANCE |
| | CHAPTER 90, ARTICLE 3, SECTION 90-12B5). PER WPB FBC |
| | 107.2.1, DISCHARGE TO STORM OR TO DRYWELL. PROVIDE |
| | ROUTING AND A DETAIL. |
| | |
| | 11. P-3.02/BAR: BAR EQUIPMENT SHALL NOT DISCHARGE TO |
| | THE GREASY WASTE (FBC PL 1003.2). DISCHARGE TO |
| | SANITARY. |
| | |
| | 12.P-3.02/BAR: PER FBC PL 901.2, 901.2.1 AND 909.1, |
| | PROVIDE A VENT(S) FOR THE SYSTEM. COMPLY WITH ONE OR |
| | MORE OF THE METHODS LAID OUT IN FBC PL CHAPTER 9. |
| | |
| | 13.P-3.02/BAR: PER FBC PL 708.1.3, PROVIDE AN |
| | IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF THE |
| | BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 AS |
| | WELL. |
| | |
| | 14. P3.03/GRILL: BAR EQUIPMENT SHALL NOT DISCHARGE TO |
| | THE GREASY WASTE (FBC PL 1003.2). DISCHARGE TO |
| | SANITARY. |
| | |
| | 15. P3.03/GRILL: PROVIDE INDIVIDUAL VENT TO THE |
| | OUTDOORS PER FBC PL 904.1. |
| | |
| | 16. P3.03/GRILL: PER FBC PL 708.1.3, PROVIDE AN |
| | IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF THE |
| | BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 AS |
| | WELL. |
| | |
| | 17. P3.03/GRILL: P-4.02/DETAIL 6 PROVIDES FOR A TRAP |
| | PRIMER TO FLOOR DRAIN FROM LAVATORY-TRAP. PLAN SHOWS |
| | WATER SOURCE TRAP PRIMER FOR WHICH THERE IS NO DETAIL. |
| | PER WPB FBC 107.2.1, CLARIFY. |
| | |
| | 18.P-3.04/WOMEN'S RESTROOM: PER FBC PL 909.1, PROVIDE A |
| | VENT(S) FOR THE WC-2 WATER CLOSETS. |
| | |
| | 19. P-3.04/MEN'S RESTROOM: PER FBC PL 909.1, PROVIDE |
| | VENT(S) FOR THE UR URINALS. |
| | |
| | 20. P-3.04/MEN'S RESTROOM: PER FBC PL 909.1, PROVIDE A |
| | VENT FOR THE 3 INCH FLOOR DRAIN. |
| | |
| | 21. P-3.04/COMMON RESTROOMS: PER FBC PL 708.1.3, |
| | PROVIDE AN IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF |
| | THE BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 |
| | AS WELL. |
| | |
| | 22.P-3.05/DRY STORAGE: PER FBC PL 708.1.3, PROVIDE AN |
| | IN-LINE/TWO-WAY CLEANOUT AT THE JUNCTION OF THE |
| | BUILDING DRAIN AND BUILDING SEWER. SHOW ON P-2.01 AS |
| | WELL. |
| | |
| | 23. P-3.04/COMMON RESTROOMS: PER FBC PL 607.1, 607.1.1 |
| | AND 607.1.2, SPECIFY AND PROVIDE AT THE LAVATORIES A |
| | WATER TEMPERATURE LIMITING DEVICES THAT CONFORM TO ASSE |
| | 1070 AND LIMITING THE TEMPERED WATER TO A MAXIMUM OF |
| | 110F. |
| | |
| | 24.PER WPB FBC 107.2.1, PROVIDE PIPING MATERIAL SPEC |
| | FOR SANITARY SOIL, WASTE AND VENT PIPING. |
| | |
| | 25.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE |
| | LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| | PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE |
| | SAME. |
| | |
| | 26. PER WPB FBC 107.2.1, PROVIDE ENERGY EFFICIENCY FOR |
| | EACH SCHEDULED WATER HEATER WATER HEATER; COMPLY WITH |
| | FBC EC TABLE C404.2 |
| | |
| | 27. P-4.02/DETAIL 3: PER WPB FBC 107.2.1, PROVIDE |
| | SPECIFICATION AND SIZE FOR EXPANSION TANK ON THE WATER |
| | HEATER DETAIL. |
| | |
| | 28. P-4.02/DETAIL 3: SWING CHECK VALVES WHEN INSTALLED |
| | IN THE VERTICAL POSITION; FLOW SHOWN IS FROM TOP |
| | DOWNWARD. VALVE IS DEPENDENT ON GRAVITY TO CLOSE AND |
| | FLOW SHOULD BE FROM THE BOTTOM UPWARD. IF SWING CHECKS |
| | ARE TO BE USED THEN IN THIS PARTICULAR CASE, INDICATE |
| | THE PIPING IN A HORIZONTAL POSITION. IF VERTICAL |
| | INSTALLATION IS REQUIRED WITH FLOW FROM THE TOP |
| | DOWNWARD, SPECIFY A VALVE SUCH AS A SPRING CHECK |
| | SPECIFICALLY DESIGNED FOR THAT PURPOSE. ADDITIONALLY, |
| | PROVIDE A FLOW DIRECTIONAL ARROW AT THE VALVE. WPB FBC |
| | 107.2.1 |
| | |
| | 29. P-4.01/WATER HEATER SCHEDULE: EEMAX EMT1.0 AND |
| | EEMAX EMT2.5 ARE STORAGE TANK TYPE WATER HEATERS. PER |
| | WPB FBC 107.2.1, PROVIDE A DETAIL OF WATER HEATER |
| | SHOWING HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW, |
| | HW, VALVES, THERMAL EXPANSION CONTROL DEVICE (INCLUDING |
| | SIZE), T&P DISCHARGE (INCLUDING TERMINATION) AND WATER |
| | HEATER PAN AND DRAIN INCLUDING TERMINATION IF IN A |
| | LOCATION THAT CAN CAUSE WATER DAMAGE; COMPLY WITH FBC |
| | PL 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6, |
| | 504.7, 504.7.1 AND 504.7.2. PROVIDE TEMPERATURE OF HOT |
| | WATER AT OUTLET. |
| | |
| | 30.PER WPB FBC 107.2.1, PROVIDE TRAP PRIMER DETAIL FOR |
| | FLOOR DRAINS WHERE A LAVATORY OR SINK P-TRAP SUPPLY IS |
| | NOT AVAILABLE. SEE P-3.01A/WATER ISOMETRIC KEYNOTE 4. |
| | |
| | 31.P-4.01/SHOCK ABSORBERS CHART: PER WPB FBC 107.2.1 |
| | AND FBC PL 604.9, PROVIDE NOTE STATING WATER HAMMER |
| | ARRESTORS SHALL BE ASSE 1010 COMPLIANT. |
| | |
| | 32. P-3.05/DRY STORAGE: PER FBC PL 1002.4.1, PLEASE |
| | PROVIDE A TRAP SEAL PROTECTION DEVICE FOR THE FLOOR |
| | TROUGH. |
| | |
| | 33. P-3.05/DRY STORAGE: PER WPB FBC 107.2.1, PLEASE |
| | PROVIDE A SCHEDULE AND SPECIFICATION FOR FLOOR DRAINS, |
| | FLOOR SINKS AND TROUGH DRAINS. |
| | |
| | 34.P-3.05 & P-4.02/DETAIL 4: PER WPB FBC 107.2.1, SHOW |
| | THE INSTALLATION OF THE BACKFLOW PREVENTER(S) AND |
| | BACKFLOW PREVENTER SPECIFICATION. THE BACKFLOW |
| | PREVENTER IN P-3.05 IS NOT IN-LINE. CLARIFY AND |
| | RECONCILE THE DRAWINGS. |
| | |
| | 35.PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON |
| | THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM |
| | THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW |
| | SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT |
| | AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR |
| | SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS |
| | WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR FINAL INSPECTION. |
| | |
| | 36.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL |
| | 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING |
| | LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF |
| | 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE |
| | A MINIMUM SLOPE OF 1/8 INCH PER FOOT." |
| | |
| | 37. P-2.01/KEY NOTE 28 AND PD-1.01/ KEY NOTE 4: |
| | RELOCATED IWHS; PER WPB FBC 107.2.1, PROVIDE THE |
| | FOLLOWING: |
| | ***A) A WATER RISER DIAGRAM TO INCLUDE ALL COMPONENTS |
| | AND SIZING OF THE HOT AND COLD WATER PIPING INTEGRATED |
| | WITH EXISTING |
| | ***B) A DETAIL FOR INSTALLATION OF UNITS TO INCLUDE ALL |
| | DOMESTIC WATER PIPING AND GAS PIPING. |
| | ***C) A DETAIL FOR STRUCTURAL SUPPORT SYSTEM. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |