| Plan Review Stops For Permit 22070748 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
6 |
Status |
P |
Date |
2023-01-06 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-01-06 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-01-06 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2023-01-06 11:32:50 | WORK IS TO BE DONE ON THE NORTH BUILDING DOWNSTAIRS AND | | | UPSTAIRS, 2 UNITS NOW IN THE BACK. SOUTH BUILDING WILL | | | NOW HAVE THE ADDRESS O F723 22ND ST 100, NORTH BLDG NE | | | UNIT 201 AND NW 202 |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
5 |
Status |
F |
Date |
2023-01-06 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-01-06 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-01-06 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2023-01-06 10:19:26 | LEFT VM FOR JAY CUNNINGHAM THAT I NEED THE OWNER TO | | | CONTACT ME SO THAT WE CAN GO OVER THE ADDRESS OPTION | | | FOR ALL THE UNITS. PLEASE HAVE THE OWNER CONTACT ME AT | | | 561-805-6659 OR AT [email protected] |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
4 |
Status |
F |
Date |
2023-01-05 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-01-05 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-01-05 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2023-01-05 08:14:35 | SPOKE WITH ZONING, THEY HAVE APPROVED 3 UNITS, PLEASE | | | HAVE THE OWNER CONTACT ME SO THAT WE CAN ESTABLISH | | | THREE ADDRESSES. PLEASE EMAIL [email protected] OR | | | CALL 561-805-6659 TO DISCUSS. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
F |
Date |
2023-01-03 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-01-03 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-01-03 |
Time |
12:13 |
Sent To |
|
|
| Notes |
| 2023-01-03 12:14:55 | SPOKE WITH ZONING, THEY HAVE APPROVED 3 UNITS, PLEASE | | | HAVE THE OWNER CONTACT ME SO THAT WE CAN ESTABLISH | | | THREE ADDRESSES. PLEASE EMAIL [email protected] OR | | | CALL 561-805-6659 TO DISCUSS. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
2022-10-20 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-10-20 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-10-20 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2022-10-20 09:32:53 | CURRENTLY THIS PARCEL ONLY HAS TWO UNITS, A SINGLE | | | FAMILY HOME (SOUTH BUILDING) AND A GARAGE APARTMENT. | | | THE PLANS INDICATE THAT THE NORTH GARAGE APARTMENT IS | | | TO BE TWO UNITS. IF ZONING ALLOWS THE ADDITIONAL UNIT | | | PLEASE HAVE THE OWNER CONTACT [email protected] OR | | | CALL 561-805-6659 TO DISCUSS READDRESSING THE PARCEL TO | | | ACCOMIDATE THE ADDITIONAL UNIT. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2022-07-19 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-07-19 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-07-19 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2022-07-19 14:43:36 | IS THIS FOR THE SOUTH BLDG WITH THE ADDRESS OF 723 22ND | | | ST A OR THE NORTH BLDG 723 22ND ST B? IS THE DEMO DUE | | | TO A FUTURE REMODEL? PLEASE CONTACT | | | [email protected] OR CALL 561-805-6659 |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
P |
Date |
2022-12-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-21 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-12-21 |
Time |
11:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2022-11-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-21 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-21 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2022-11-21 11:53:12 | THE LETTER PROVIDED NEEDS TO BE SIGNED -- | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2022-07-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-27 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-27 |
Time |
07:48 |
Sent To |
|
|
| Notes |
| 2022-07-27 07:48:17 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-12-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-21 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-12-21 |
Time |
11:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-11-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-21 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-11-21 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2022-11-21 11:45:43 | RENOVATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | | | | 1. FBC 107 YOU CANNOT CHANGE THE OCCUPANCY WITH AN | | | INTERIOR DEMO PERMIT. SUBMIT AN APPLICATION THAT MORE | | | CLEARLY DESCRIBES THE SCOPE OF WORK, INCLUDE THE | | | ELIMINATION OF HABITABLE UNITS IN THE DESCRIPTION. THIS | | | PERMIT TYPE WILL BE CHANGED TO COMMERCIAL INTERIOR. | | | | | | 2. SEE ZONING COMMENTS - CANNOT HAVE MORE THAN 2 UNITS | | | ON THE PROPERTY - | | | | | | 3. FBC B 708.1, ON THE PLAN SHOW ALL FIRE RATED WALLS. | | | IT APPEARS THAT WORK WAS DONE WITHOUT PERMITS, NOT | | | CLEAR IF THE TENANT SEPARATION WAS MAINTAINED. | | | | | | 4. FBC B CHAPTER 7, PROVIDE A PLAN WHICH SHOWS BUILDING | | | TYPE, SQUARE FOOT AREA, CLEARLY SHOW OCCUPANCIES, FBC | | | CHAPTER 5. NOTE IF THE BUILDING IS SPRINKLERED OR NOT | | | SPRINKLERED. | | | | | | 5. PLEASE PROVIDE THE PERMIT NUMBER FOR THE EXISTING | | | DUPLEX - - WHEN DEVELOPING THE PLAN, NOTE ITEMS WHICH | | | WERE INSTALLED WITHOUT A PERMIT AS SUCH, DO NOT NOTE | | | THEM AS "EXISTING". ONLY ELEMENTS WHICH WERE LEGALLY | | | PERMITTED AND INSPECTED CAN BE CONSIDERED "EXISTING". | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-27 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-27 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2022-07-27 07:38:48 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107 YOU CANNOT CHANGE THE OCCUPANCY WITH AN | | | INTERIOR DEMO PERMIT. SUBMIT AN APPLICATION THAT MORE | | | CLEARLY DESCRIBES THE SCOPE OF WORK, INCLUDE THE | | | ELIMINATION OF HABITABLE UNITS IN THE DESCRIPTION. THIS | | | PERMIT TYPE WILL BE CHANGED TO COMMERCIAL INTERIOR. | | | | | | 2. FBC 107 PROVIDE A PLAN SHOWING THE NEW CONFIGURATION | | | AND UNITS. THIS SHOULD INCLUDE ALL UNITS AND BE CLEAR | | | AS TO HOW MANY UNITS ARE IN THIS BUILDING. PROVIDE A | | | SITE PLAN SHOWING THE BUILDING ON THE SITE. | | | | | | 3. FBC B 708.1, ON THE PLAN SHOW ALL FIRE RATED WALLS. | | | IT APPEARS THAT WORK WAS DONE WITHOUT PERMITS, NOT | | | CLEAR IF THE TENANT SEPARATION WAS MAINTAINED. | | | | | | 4. FBC B CHAPTER 7, PROVIDE A PLAN WHICH SHOWS BUILDING | | | TYPE, SQUARE FOOT AREA, CLEARLY SHOW OCCUPANCIES, FBC | | | CHAPTER 5. NOTE IF THE BUILDING IS SPRINKLERED OR NOT | | | SPRINKLERED. | | | | | | 5. FBC B 1008, THE SCOPE OF WORK INDICATES THAT ALL | | | ELECTRIC WILL BE REMOVED. SEE FBC B 1008, MEANS OF | | | EGRESS ILLUMINATION, YOU CANNOT HAVE A STORAGE ROOM | | | WITHOUT ILLUMINATION. | | | | | | 6. WHEN DEVELOPING THE PLAN, NOTE ITEMS WHICH WERE | | | INSTALLED WITHOUT A PERMIT AS SUCH, DO NOT NOTE THEM AS | | | "EXISTING". ONLY ELEMENTS WHICH WERE LEGALLY PERMITTED | | | AND INSPECTED CAN BE CONSIDERED "EXISTING". | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-10-24 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-10-24 |
Time |
22:57 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-10-24 |
Time |
21:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-08-18 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-08-18 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-08-18 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-10-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-10-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-10-21 |
Time |
10:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2022-07-21 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-07-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-07-21 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2022-07-21 12:58:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION WITHIN THE SCOPE OF WORK OF | | | USING THE OCCUPANCY FOR STORAGE, WHICH IS CHAGING THE | | | OCCUPANCY FROM RESIDENTIAL TO STORAGE. | | | | | | PER NFPA 1 | | | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | | | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER | | | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE | | | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PROPOSED | | | MATERIALS/PRODUCTS/COMMODITIES BEING STORED. | | | | | | | | | 1A) PER NFPA 101 CH 42 STORAGE OCCUPANCIES ILLUMINATION | | | OF MEANS OF EGRESS AND EMEERGENCY LIGHTING IS REQUIRED | | | UNLESS IT IS USED ONLY IN DAYLIGHT HOURS WITH | | | APPLICABLE NATURAL LIGHTING. | | | | | | 42.2.8 ILLUMINATION OF MEANS OF EGRESS. | | | 42.2.8.1 MEANS OF EGRESS SHALL BE ILLUMINATED IN | | | ACCORDANCE WITH SEC TION 7.8. | | | 42.2.8.2 IN STRUCTURES OCCUPIED ONLY DURING DAYLIGHT | | | HOURS, MEANS OF | | | EGRESS SHALL BE PERMITTED TO BE ILLUMINATED WITH | | | WINDOWS ARRANGED TO | | | PROVIDE THE REQUIRED LEVEL OF ILLUMINATION ON ALL | | | PORTIONS OF THE MEANS | | | OF EGRESS DURING SUCH HOURS, WHEN APPROVED BY THE | | | AUTHORITY HAVING | | | JURISDICTION | | | | | | PLEASE REVIEW AND PROVIDE A NOTE OF COMPLINACE OR | | | PROVIDE PER THE REQUIREMENT. | | | | | | | | | | | | 1B) PER NFPA 101 CH 42 STORAGE OCCUPANCIES MARKING OF | | | THE MEANS OF EGRESS IS REQUIRED. | | | | | | 42.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS | | | SHALL HAVE | | | SIGNS IN ACCORDANCE WITH SECTION 7.10 | | | | | | 7.10.1.2 EXITS. | | | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS | | | THAT OBVIOUSLY | | | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED | | | BY AN APPROVED | | | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT | | | ACCESS | | | | | | PLEASE PROVIDE THE LOCATION OF THE EXIT(S) ON A FLOOR | | | PLAN AND THAT IT IS CLEARLY IDENTIFIABLE AS THE EXIT. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-01-06 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-01-06 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-01-05 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-01-05 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2023-01-05 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2023-01-03 |
Time |
16:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-11-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-11-21 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-20 |
Time |
06:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-08-18 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-08-18 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-07-19 |
Time |
07:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-01-19 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-01-19 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-01-05 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2023-01-19 13:56:51 | RECEIPT MU-2023-002262 - $0.00 NO FEES DUE. LEM | | 2023-01-05 14:21:15 | 1/5/23 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-07-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-27 |
Time |
07:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-27 |
Time |
07:53 |
Sent To |
|
|
| Notes |
| 2022-07-27 07:54:23 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE EMAIL THE RECEIPT | | | TO [email protected]. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2022-07-28 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-07-28 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-07-28 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2022-07-28 11:54:11 | NO MECHANICAL SYSTEM SHOWN IN PROJECT. ME |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-10-21 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-21 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-07-21 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-07-21 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-07-21 |
Time |
07:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-11-17 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2022-07-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-27 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-27 |
Time |
07:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-10-28 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-10-28 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-10-28 |
Time |
13:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-07-28 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-07-28 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-07-28 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2022-07-28 14:37:38 | 7/28/2022 | | | FAIL | | | PLEASE PROVIDE A SURVEY WITH AN APPLICATION | | | PLEASE ALSO INCLUDE CURRENT CONDITION SITE MAP, SITE | | | MAP OF WHAT IS GETTING REMOVED AND WHAT THE PROPOSED | | | SITE WOULD LOOK LIKE ONCE COMPETED. | | | | | | | | | | | | ALEXIS SANGELEER | | | ASSOCIATE PLANNER | | | [email protected] |
|
|