| 2022-11-01 06:34:36 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22070728 |
| | ADD: 500 N CONGRESS AVE. # 62 |
| | CONT: PROLINE BUILDERS |
| | TEL: 954-448-0298 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. OCT. 31ST/ 2022 |
| | ACTION: DENIED |
| | 1) SHEET A-1: |
| | 1A) PLEASE PROVIDE EITHER A UL OR GYPSUM ASSOCIATION |
| | LISTING AND SHOW COMPONENTS AND FIRE RATING FOR THE |
| | FLOOR/ CEILING HORIZONTAL ASSEMBLY. 2020 FBC-BUILDING |
| | CODE SECTIONS 420.3 & 711.2.4.3. |
| | |
| | 1B) PLEASE PROVIDE THE WALL ASSEMBLIES EITHER A UL OR |
| | GYPSUM ASSOCIATION LISTING AND SHOW COMPONENTS AND FIRE |
| | RATING FOR THE TENANT SEPARATION WALLS (DWELLING UNITS) |
| | IN COMPLIANCE WITH 420.2 & 708. |
| | |
| | 2) FLOOR /CEILING ASSEMBLY FOR THE 2ND FLOOR. FLOOR |
| | INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, |
| | MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD |
| | FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT |
| | TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND |
| | MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE |
| | STANDARDS |
| | TYPE III-TYPE V CONSTRUCTION: |
| | |
| | 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 2C) FBC-B-2017 720.2 CONCEALED INSTALLATION (TILE & |
| | MARBLE). INSULATING MATERIALS, WHERE CONCEALED AS |
| | INSTALLED IN BUILDINGS OF ANY TYPE OF CONSTRUCTION, |
| | SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND |
| | A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. FLAME |
| | SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS A |
| | DIMENSIONLESS NUMBER, DERIVED FROM VISUAL MEASUREMENTS |
| | OF THE SPREAD OF FLAME VERSUS TIME FOR A MATERIAL |
| | TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) AS REQUESTED BY THE MECHANICAL PLAN REVIEWER PLEASE |
| | SUBMIT THE DUCTWORK FOR THE A/C SYSTEM TO SEE IF THE |
| | DUCTWORK IS RUN UP BETWEEN THE FLOOR JOIST, IF SO THEN |
| | THE 2020 FBC-BUILDING CODE WILL REQUIRE RADIATION |
| | DAMPER ACTUATION 717.3.3.3. OF THE 2020 FBC-BUILDING |
| | CODE AND 717.5.2 FIRE BARRIERS (HORIZONTAL FIRE |
| | BARRIER, CEILING) ASSEMBLIES. |
| | |
| | 4) SHEET A-2 PROVIDES A FLORIDA PRODUCT APPROVAL NUMBER |
| | BUT PLEASE SUBMIT THE FULL PRODUCT APPROVAL WITH |
| | TECHNICAL SHEETS. COMPONENTS & CLADDING. PLEASE SUBMIT |
| | THE COMPONENTS AND CLADDING PRODUCT APPROVALS. 2020 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(B) WINDOWS & MULLIONS |
| | |
| | 5) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE |
| | OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |