Plan Review Details - Permit 22070727
Plan Review Stops For Permit 22070727
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-09-21 Cont ID  
Sent By cpuell Date 2022-09-21 Time 10:31 Rev Time 0.00
Received By cpuell Date 2022-09-21 Time 10:31 Sent To  
Notes
2022-09-21 10:31:28UPDATED COMM + WITH THE CORRECT ADDRESS

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2023-01-17 Cont ID  
Sent By jwitmer Date 2023-01-17 Time 08:12 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-12-13 Cont ID  
Sent By jwitmer Date 2022-12-13 Time 11:36 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-12-13 11:36:48TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By jwitmer Date 2022-11-01 Time 06:43 Rev Time 0.00
Received By jwitmer Date 2022-11-01 Time 06:41 Sent To  
Notes
2022-11-01 06:42:59TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-01-17 Cont ID  
Sent By jwitmer Date 2023-01-17 Time 08:12 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-12-13 Cont ID  
Sent By jwitmer Date 2022-12-13 Time 11:35 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-12-13 11:35:13WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22070727
 ADD: 500 N CONGRESS AVE. # 64 / 2ND FLOOR UNIT
 CONT: PROLINE BUILDERS
 TEL: 954-448-0298
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. DEC.13TH/ 2022
 ACTION: DENIED
 1) COMPLIED.
  
 2) 2ND REQUEST. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "CODE SECTIONS
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR THE TERM
 "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION".
 1ST ROUND COMMENTS. FLOOR /CEILING ASSEMBLY FOR THE 2ND
 FLOOR. FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR
 TILE, STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE
 FLOORING AND WOOD FLOORING ALL NEED TO HAVE HAD THE
 SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE
 FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS LISTED
 UNDER EACH OF THE STANDARDS
 TYPE III-TYPE V CONSTRUCTION:
  
 2A) 1ST ROUND COMMENTS. FBC-B 2017 1207.3
 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
  
 2B) 1ST ROUND COMMENTS. FBC-B 2017 1207.2 AIR-BORNE
 SOUND. WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) 1ST ROUND COMMENTS. FBC-B-2017 720.2 CONCEALED
 INSTALLATION (TILE & MARBLE). INSULATING MATERIALS,
 WHERE CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE
 OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450. FLAME SPREAD INDEX. A COMPARATIVE MEASURE,
 EXPRESSED AS A DIMENSIONLESS NUMBER, DERIVED FROM
 VISUAL MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME
 FOR A MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR
 UL 723.
  
 3) COMPLIED.
  
 4-5) NOT APPLICABLE
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By jwitmer Date 2022-11-01 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2022-11-01 Time 06:41 Sent To  
Notes
2022-11-01 06:53:23WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22070727
 ADD: 500 N CONGRESS AVE. # 64
 CONT: PROLINE BUILDERS
 TEL: 954-448-0298
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 01ST/ 2022
 ACTION: DENIED
 1) SHEET A-1:
 1A) PLEASE PROVIDE EITHER A UL OR GYPSUM ASSOCIATION
 LISTING AND SHOW COMPONENTS AND FIRE RATING FOR THE
 FLOOR/ CEILING HORIZONTAL ASSEMBLY. 2020 FBC-BUILDING
 CODE SECTIONS 420.3 & 711.2.4.3. IT IS NOT KNOWN IF THE
 ATTIC DRAFTSTOPPING IS AT EACH DWELLING UNIT OR
 EXCEPTION # 2 WAS TAKEN REQUIRING DRAFTSTOPPING EVERY
 3,000 SQUARE FEET.
  
 1B) PLEASE PROVIDE THE WALL ASSEMBLIES EITHER A UL OR
 GYPSUM ASSOCIATION LISTING AND SHOW COMPONENTS AND FIRE
 RATING FOR THE TENANT SEPARATION WALLS (DWELLING UNITS)
 IN COMPLIANCE WITH 420.2 & 708.
  
 2) FLOOR /CEILING ASSEMBLY FOR THE 2ND FLOOR. FLOOR
 INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE,
 MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS
 TYPE III-TYPE V CONSTRUCTION:
  
 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  
 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FBC-B-2017 720.2 CONCEALED INSTALLATION (TILE &
 MARBLE). INSULATING MATERIALS, WHERE CONCEALED AS
 INSTALLED IN BUILDINGS OF ANY TYPE OF CONSTRUCTION,
 SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND
 A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. FLAME
 SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS A
 DIMENSIONLESS NUMBER, DERIVED FROM VISUAL MEASUREMENTS
 OF THE SPREAD OF FLAME VERSUS TIME FOR A MATERIAL
 TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) AS REQUESTED BY THE MECHANICAL PLAN REVIEWER PLEASE
 SUBMIT THE DUCTWORK FOR THE A/C SYSTEM TO SEE IF THE
 DUCTWORK IS RUN UP BETWEEN THE ROOF TRUSSES, IF SO THEN
 THE 2020 FBC-BUILDING CODE WILL REQUIRE RADIATION
 DAMPER ACTUATION 717.3.3.3. OF THE 2020 FBC-BUILDING
 CODE AND 717.5.2 FIRE BARRIERS (HORIZONTAL FIRE
 BARRIER, CEILING) ASSEMBLIES.
  
 4) SHEET A-2 PROVIDES A FLORIDA PRODUCT APPROVAL NUMBER
 BUT PLEASE SUBMIT THE FULL PRODUCT APPROVAL WITH
 TECHNICAL SHEETS. COMPONENTS & CLADDING. PLEASE SUBMIT
 THE COMPONENTS AND CLADDING PRODUCT APPROVALS. 2020
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(B) WINDOWS & MULLIONS
  
 5) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER???S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-10-12 Cont ID  
Sent By fgiaquin Date 2022-10-12 Time 21:44 Rev Time 0.00
Received By fgiaquin Date 2022-10-12 Time 19:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-13 Cont ID  
Sent By   Date 2022-12-13 Time   Rev Time  
Received By bdolan Date 2022-12-13 Time 10:59 Sent To  
Notes
2022-12-13 10:59:41PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 CAPT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-09-26 Cont ID  
Sent By pleduc Date 2022-09-26 Time   Rev Time  
Received By bdolan Date 2022-09-26 Time 09:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-30 Cont ID  
Sent By medwards Date 2023-01-30 Time 15:07 Rev Time 0.00
Received By medwards Date 2023-01-27 Time 15:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2023-01-17 Time   Rev Time 0.00
Received By aoliver Date 2023-01-12 Time 09:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-16 Cont ID  
Sent By medwards Date 2022-12-16 Time 10:12 Rev Time 0.00
Received By medwards Date 2022-12-09 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-11-01 Cont ID  
Sent By jwitmer Date 2022-11-01 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2022-09-21 Time 08:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-01-30 Cont ID  
Sent By medwards Date 2023-01-30 Time 14:57 Rev Time 0.00
Received By medwards Date 2023-01-30 Time 14:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-01-16 Cont ID  
Sent By medwards Date 2023-01-16 Time 13:22 Rev Time 0.00
Received By medwards Date 2023-01-16 Time 13:22 Sent To  
Notes
2023-01-16 13:27:06THE DRAWING SUBMITTED FOR THE MECHANICAL HAS A COPY OF
 THE DIGITAL SIGNATURE. PLEASE PROVIDE THE ORIGINAL
 DIGITALLY SIGNED DRAWING. FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-12-16 Cont ID  
Sent By medwards Date 2022-12-16 Time 10:08 Rev Time 0.00
Received By medwards Date 2022-12-16 Time 10:08 Sent To  
Notes
2022-12-16 10:08:23SHEET M-1 FOR 1ST FLOOR UNIT J62 IS MISSING NOW. M-1
 AND M-2 ARE NOW THE SAME DRAWING FOR THE 2ND FLOOR UNIT
 J64. PROVIDE ALL DRAWINGS RELEVANT TO THE SCOPE OF WORK
 FOR THIS PROJECT. IF THE FIRST FLOOR DUCTWORK IS TO BE
 INSTALLED IN A CHASE BELOW THE RATED CEILING/FLOOR
 ASSEMBLY PROVIDE A DETAIL OF THIS. FBC 107.3.5
  
 NOTE 5 OF THE RESPONSE LETTER STAES THAT THE BATH
 EXHAUST FANS WERE DUCTLESS, THE MECHANICAL CODE DOES
 NOT AND HAS NEVER ALLOWED THE BATH EXHAUST FAN TO BE
 DUCTLESS. PLEASE SEE FMC 501.3
  
 501.3 EXHAUST DISCHARGE. THE AIR REMOVED BY EVERY
 MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT WILL NOT CAUSE A PUBLIC NUISANCE
 AND NOT LESS THAN THE DISTANCES SPECIFIED IN SECTION
 501.3.1. THE AIR SHALL BE DISCHARGED TO A LOCATION FROM
 WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN
 ATTIC, CRAWL SPACE, OR BE DIRECTED ONTO WALKWAYS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-09-29 Cont ID  
Sent By medwards Date 2022-09-29 Time 07:48 Rev Time 0.00
Received By medwards Date 2022-09-29 Time 07:48 Sent To  
Notes
2022-09-29 07:48:481ST REVIEW FMC
 PERMIT: 22070727
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 PLEASE SEE COMMENTS FOR PERMIT APPLICATION 22070728
 BELOW, THESE COMMENTS WILL NEED TO BE ADDRESSED BEFORE
 THIS PERMIT APPLICATION CAN BE APPROVED:
  
 1) PROVIDE A MECHANICAL DRAWING SHOWING A DESIGN THAT
 INCLUDES THE FIRE RATED FLOOR CEILING ASSEMBLY REQUIRED
 FOR TENANT SEPARATION. FMC 607.6.2
  
 2) MECHANICAL DRAWINGS APPEAR TO BE A COPY OF THE
 DIGITALLY SIGNED DRAWING. PROVIDE THE ORIGINAL
 DIGITALLY SIGNED DRAWING. FS 471/481
  
  
 [BF] 607.6.2 MEMBRANE PENETRATIONS. DUCTS AND AIR
 TRANSFER OPENINGS CONSTRUCTED OF APPROVED MATERIALS, IN
 ACCORDANCE WITH SECTION 603, THAT PENETRATE THE CEILING
 MEMBRANE OF A FIRE-RESISTANCE-RATED FLOOR/CEILING OR
 ROOF/
 CEILING ASSEMBLY SHALL BE PROTECTED WITH ONE OF THE
 FOLLOWING:
  
 1. A SHAFT ENCLOSURE IN ACCORDANCE WITH SECTION 713 OF
 THE FLORIDA BUILDING CODE, BUILDING.
 2. A LISTED CEILING RADIATION DAMPER INSTALLED AT THE
 CEILING LINE WHERE A DUCT PENETRATES THE CEILING OF
 AFIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING
 ASSEMBLY.
 3. A LISTED CEILING RADIATION DAMPER INSTALLED AT THE
 CEILING LINE WHERE A DIFFUSER WITH NO DUCT ATTACHED
 PENETRATES THE CEILING OF A FIRE-RESISTANCE-RATED
 FLOOR/CEILING OR ROOF/CEILING ASSEMBLY.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-01-30 Cont ID  
Sent By medwards Date 2023-01-30 Time 14:57 Rev Time 0.00
Received By medwards Date 2023-01-30 Time 14:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-01-17 Cont ID  
Sent By jwitmer Date 2023-01-17 Time 08:18 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2023-01-17 08:18:32SEE MECHANICAL REVIEW ABOUT SIGNATURES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-12-16 Cont ID  
Sent By medwards Date 2022-12-16 Time 10:12 Rev Time 0.00
Received By medwards Date 2022-12-16 Time 10:12 Sent To  
Notes
2022-12-16 10:12:22SHEETS A-4, M-2 AND E-2 ARE NOT DIGITALLY SIGNED.
 PROVIDE DIGITALLY SIGNED DRAWINGS. FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-11-01 Cont ID  
Sent By jwitmer Date 2022-11-01 Time 06:42 Rev Time 0.00
Received By jwitmer Date 2022-11-01 Time 06:41 Sent To  
Notes
2022-11-01 06:42:04IT APPEARS THE DIGITAL SIGNATURE FOR ALL TRADES IS A
 COPY OF AN ORIGINAL, IT WILL NOT OPEN FOR 3RD PARTY
 VERIFICATION. FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 (3)(C) PLANS IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE???S
 SIGNATURE SHALL NOT BE USED ON ELECTRONIC/DIGITALLY
 SIGNED AND SEALED ENGINEERING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.