| 2022-07-22 16:26:23 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22070617 |
| | 7/22/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P4 & P5: PROVIDE A PLUMBING FIXTURE SCHEDULE- |
| | SECS. 404, 419, 422, & 425 FBC P. |
| | |
| | 2) P4 & P5: NEW SINKS IN THE WORK ROOM AND LAB ARE |
| | SHOWN. PLEASE CLARIFY THE USE OF THE SINKS AND WHAT THE |
| | CONTENT OF THE DRAINAGE WILL BE. REFER TO SEC. 803.1 |
| | FBC P- INDIRECT WASTE RECEPTORS AND CHEMICAL DILUTION |
| | OR NEUTRALIZING DEVICES MAY BE REQUIRED. |
| | |
| | 3) P4 & P5: HOT WATER SHALL BE DELIVERED FROM THE SINKS |
| | IN THE WORK ROOM AND LAB- SEC. 607.1 FBC P. THE PLANS |
| | INDICATE COLD WATER SUPPLY ONLY TO TWO OF THE THREE |
| | SINKS SHOWN IN THE LAB, AND THE WATER HEATER PIPING |
| | DETAIL INDICATES ONLY TEMPERED WATER SUPPLY WILL BE |
| | PROVIDED TO THE OTHER SINKS. PLEASE NOTE THAT TEMPERED |
| | WATER SHALL BE DELIVERED FROM THE LAVATORIES, HOWEVER |
| | HOT WATER AT A MINIMUM TEMPERATURE OF 110 DEGREES F |
| | SHALL BE DELIVERED FROM THE OTHER SINKS INCLUDING THE |
| | MOP SINK REFERENCED IN THE WATER HEATER DETAIL. PLEASE |
| | IDENTIFY THE MOP SINK LOCATION ON THE PLANS. |
| | |
| | 4) P4 & P5: REFER TO SEC. 411.1 FBC P- IF AN EMERGENCY |
| | SHOWER AND EYE WASH STATION ARE REQUIRED BY OSHA OR |
| | OTHER GOVERNING AGENCIES, THE FIXTURES SHALL CONFORM TO |
| | ISEA Z358.1. IF APPLICABLE THE PLANS SHALL BE REVISED |
| | AND MANUFACTURER'S SPECIFICATIONS SHALL BE SUBMITTED. |
| | |
| | 5) P4 & P5: PROVIDE EQUIPMENT SCHEDULES FOR THE |
| | 47-GALLON STORAGE WATER HEATER AND THE TANKLESS WATER |
| | HEATERS SHOWN AT THE LAVATORIES- SEC. 502.1 FBC P AND |
| | C404.2 FBC EC. |
| | |
| | 6) P4 & P5: SHOW THE MEANS OF TRAP SEAL PROTECTION FOR |
| | THE FLOOR DRAINS- SEC. 1002.4.1 FBC P. REFER TO COMMENT |
| | #2 ABOVE AND INDICATE THE CONTENT OF THE DRAINAGE BEING |
| | CONVEYED TO THE SANITARY SYSTEM FROM THE FLOOR DRAINS. |
| | |
| | 7) P4 & P5: PROVIDE AN ENLARGED DETAIL SHOWING THE |
| | WATER SUPPLY CONNECTION TO THE FILTRATION EQUIPMENT AND |
| | LOCATION OF THE BACKFLOW PREVENTER- SEC. 608.3 FBC P. |
| | |
| | 8) A3 & P4: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR |
| | THE OCCUPANCY IN COMPLIANCE WITH TABLE 403.1 FBC P. |
| | INDICATE THE REQUIRED AND PROVIDED NUMBER OF FIXTURES |
| | BASED ON THE TABLE. |
| | |
| | 9) A3 & P4: IDENTIFY THE TOILET ROOMS AS MALE, FEMALE, |
| | OR UNISEX- SEC. 403.4 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |