Plan Review Details - Permit 22070608
Plan Review Stops For Permit 22070608
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-09-06 Cont ID  
Sent By shill Date 2022-09-06 Time 11:30 Rev Time 0.00
Received By shill Date 2022-09-06 Time 11:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-08-25 Cont ID  
Sent By rmcphers Date 2022-08-25 Time 15:44 Rev Time 0.00
Received By rmcphers Date 2022-08-25 Time 15:36 Sent To  
Notes
2022-08-25 15:43:35EXTERIOR WOOD SIDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) WIND DESIGN CALCULATIONS PROVIDED USE ASCE 7-10 FOR
 THE WIND DESIGN - SHOULD BE ASCE 7-16 PER FBC CHAPTER
 35
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-15 Cont ID  
Sent By shill Date 2022-08-15 Time 13:30 Rev Time 0.00
Received By shill Date 2022-08-15 Time 13:30 Sent To  
Notes
2022-08-15 13:30:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2. FBC 107.3.5, REVISE PLAN TO SHOW BUILDING HEIGHT AND
 AREA, NUMBER OF FLOORS, BUILDING TYPE. YOU ARE
 PROPOSING A COMBUSTIBLE MATERIAL ON THE OUTSIDE OF THE
 BUILDING WITH NO OTHER INFORMATION. CODE COMPLIANCE
 CANNOT BE DETERMINED BASED ON THE INFORMATION PROVIDED.
  
 3. (REVISED) FBC B 1603.1.4, FBC B CHAPTER 35, THE ASCE
 STANDARD THAT WAS USED IN THE CALCULATIONS WAS
 ASCE7-10, ASCE7-16 REQUIRED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By shill Date 2022-08-03 Time 07:49 Rev Time 0.00
Received By shill Date 2022-08-03 Time 07:49 Sent To  
Notes
2022-08-03 08:12:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, PROVIDE A SITE PLAN SHOWING LOCATION OF
 PROPOSED IMPROVEMENT.
  
 2. FBC 107.3.5, REVISE PLAN TO SHOW BUILDING HEIGHT AND
 AREA, NUMBER OF FLOORS, BUILDING TYPE. YOU ARE
 PROPOSING A COMBUSTIBLE MATERIAL ON THE OUTSIDE OF THE
 BUILDING WITH NO OTHER INFORMATION. CODE COMPLIANCE
 CANNOT BE DETERMINED BASED ON THE INFORMATION PROVIDED.
  
 3. FBC B 1603.1.4, REVISE PLAN TO INCLUDE WIND DESIGN
 CRITERIA.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-08-30 Cont ID  
Sent By pleduc Date 2022-08-30 Time   Rev Time 0.00
Received By pleduc Date 2022-08-30 Time 10:04 Sent To  
Notes
2022-08-30 10:07:35FIRE PROVISO:
  
 PROTECT RESIDENTS FROM FALLING DEBRIS.
  
 ENSURE EXITS ARE PROTECTED AND FREE EGRESS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-08-11 Cont ID  
Sent By pleduc Date 2022-08-11 Time   Rev Time 0.00
Received By pleduc Date 2022-08-11 Time 12:14 Sent To  
Notes
2022-08-11 12:15:44FIRE PROVISO:
  
 PROTECT RESIDENTS FROM FALLING DEBRIS.
  
 ENSURE EXITS ARE PROTECTED AND FREE EGRESS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-07-18 Cont ID  
Sent By pleduc Date 2022-07-18 Time   Rev Time 0.00
Received By pleduc Date 2022-07-18 Time 16:11 Sent To  
Notes
2022-07-18 16:15:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF WORK ON THE EXTERIOR OF A
 BUILDING, HOWEVER, THERE IS NO SITE PALN SHOWING WHAT
 BUILDING NOR THE AREA OF A BUILDING WHERE THE WORK IS
 TO BE DONE.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDEA SIT PLAN WITH
 DETAILS OF THE BUILDING.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-09-06 Cont ID  
Sent By shill Date 2022-09-06 Time 11:30 Rev Time 0.00
Received By shill Date 2022-08-29 Time 16:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-25 Cont ID  
Sent By rmcphers Date 2022-08-25 Time 15:45 Rev Time 0.00
Received By rmcphers Date 2022-08-15 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-15 Cont ID  
Sent By shill Date 2022-08-15 Time 13:30 Rev Time 0.00
Received By shill Date 2022-08-08 Time 16:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-03 Cont ID  
Sent By shill Date 2022-08-03 Time 08:13 Rev Time 0.00
Received By shill Date 2022-07-15 Time 06:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-06 Cont ID  
Sent By shill Date 2022-09-06 Time 11:30 Rev Time 0.00
Received By shill Date 2022-09-06 Time 11:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-08-03 Cont ID  
Sent By shill Date 2022-08-03 Time 08:13 Rev Time 0.00
Received By shill Date 2022-08-03 Time 08:13 Sent To  
Notes
***NONE***