Plan Review Details - Permit 22070587
Plan Review Stops For Permit 22070587
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-09-06 Cont ID  
Sent By shill Date 2022-09-06 Time 17:50 Rev Time 0.00
Received By shill Date 2022-09-06 Time 17:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-09-01 Cont ID  
Sent By shill Date 2022-09-01 Time 14:08 Rev Time 0.00
Received By shill Date 2022-09-01 Time 14:08 Sent To  
Notes
2022-09-01 14:12:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LIST:
  
 TEST REPORTS FOR BOTH MSC90 AND SUPERSIM90 WERE
 SUBMITTED, LVT FLOORING.
  
 THE FLAME SPREAD WAS FOR SUPERSIM 90 WITH A TILE FLOOR,
 NEED A FLAME SPREAD WITH A COMBUSTIBLE FLOOR OR NO
 FLOORING.\
  
 MSC90 STC/IIC TEST REPORTS USE AN 8" SLAB, HOW HAVE YOU
 DETERMINED THAT THIS BUILDING HAS 8" FLOORS?
  
 PROFLEX MAKES A PRODUCT FOR THIS APPLICATION, LV200. IF
 YOU WOULD LIKE TO USE THIS PRODUCT PLEASE INDICATE THAT
 WHEN RESUBMITTING AND THE TEST REPORTS WILL BE UPLOADED
 FOR YOU.
  
 SEE PREVIOUS REVIEWS FOR CODE REFERENCES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-20 Cont ID  
Sent By shill Date 2022-08-20 Time 09:20 Rev Time 0.00
Received By shill Date 2022-08-20 Time 09:20 Sent To  
Notes
2022-08-20 09:21:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LIST:
  
 SUPERSAM 125 WITH LVT IS PROPOSED. WE HAVE STC AND IIC
 TESTS ON FILE FOR THIS PRODUCT. HOWEVER WE DO NOT HAVE
 FLAME SPREAD FOR THIS PRODUCT FOR A COMBUSTIBLE FLOOR.
 EITHER PROVIDE THAT TEST (ASTM E 84 OR UL723) OR
 PROPOSE A DIFFERENT PRODUCT. IF YOU PROPOSE A DIFFERENT
 UNDERLAYMENT:
  
 1. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT STC, IIC, FLAME SPREAD:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By shill Date 2022-08-03 Time 12:23 Rev Time 0.00
Received By shill Date 2022-08-03 Time 12:22 Sent To  
Notes
2022-08-03 12:25:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 SUPERSAM 125 WITH LVT IS PROPOSED. WE HAVE STC AND IIC
 TESTS ON FILE FOR THIS PRODUCT. HOWEVER WE DO NOT HAVE
 FLAME SPREAD FOR THIS PRODUCT FOR A COMBUSTIBLE FLOOR.
 EITHER PROVIDE THAT TEST (ASTM E 84 OR UL723) OR
 PROPOSE A DIFFERENT PRODUCT. IF YOU PROPOSE A DIFFERENT
 UNDERLAYMENT:
  
 1. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT STC, IIC, FLAME SPREAD:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-08-15 Cont ID  
Sent By cwalker Date 2022-08-15 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-07-18 Cont ID  
Sent By cwalker Date 2022-07-18 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-07-18 12:09:58PROVIDE PRODUCT SPECIFICATIONS FOR THE FIRE PERFORMANCE
 OF THE NEW VINYL FLOORING TO INCLUDE THE CRITICAL
 RADIANT FLUX OF THE MATERIAL. NFPA 101, 10.2.7
  
 C. WALKER
 561-804-4762
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-09-06 Cont ID  
Sent By shill Date 2022-09-06 Time 17:51 Rev Time 0.00
Received By shill Date 2022-09-02 Time 07:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-01 Cont ID  
Sent By shill Date 2022-09-01 Time 14:12 Rev Time 0.00
Received By shill Date 2022-08-25 Time 10:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-20 Cont ID  
Sent By shill Date 2022-08-20 Time 09:21 Rev Time 0.00
Received By shill Date 2022-08-14 Time 09:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-03 Cont ID  
Sent By shill Date 2022-08-03 Time 12:25 Rev Time 0.00
Received By shill Date 2022-07-15 Time 10:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-08-03 Cont ID  
Sent By shill Date 2022-08-03 Time 12:25 Rev Time 0.00
Received By shill Date 2022-08-03 Time 12:25 Sent To  
Notes
***NONE***