| Plan Review Stops For Permit 22070584 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-17 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-17 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-08-29 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-29 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2022-08-29 13:46:28 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) RFI #8 - PLEASE SHOW THE DROP CEILING HEIGHT - FBC | | | 1208.2 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-09-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-09-13 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-09-13 |
Time |
16:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-09-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
bdolan |
Date |
2022-08-29 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2022-09-06 12:45:04 | THIS PLAN WAS REVIEWED AND APPROVED BY LT. BRIAN DOLAN, | | | DIVISION OF FIRE PREVENTION, WITH THE FOLLOWING | | | COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL | | | AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR | | | CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS. | | | | | | ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND | | | SHOP DRAWINGS BY CERTIFIED CONTRACTORS. | | | | | | THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL REMAIN | | | ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION PERIODS. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-10-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-10-18 |
Time |
16:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-17 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-07 |
Time |
08:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-09-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-09-16 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-08-26 |
Time |
10:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-10-17 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-10-17 |
Time |
07:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-08-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-30 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-30 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2022-08-30 13:23:17 | THE MECHANICAL PLAN FOR THE FAN ASSEMBLY APPEARS TO BE | | | FOR ANOTHER LOCATION AS IT HAS THE WRONG ADDRESS AND | | | THE DESIGNER MUST DIGITALLY SIGN THE DRAWINGS. FBC | | | 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-10-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-10-21 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-10-21 |
Time |
10:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-10-10 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-10 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-10 14:08:04 | PENDING SIGNATURE VERIFICATION ON PAGES P0.1 AND P1.1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-29 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-29 |
Time |
08:16 |
Sent To |
|
|
| Notes |
| 2022-08-29 13:21:29 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22070584 | | | 8/29/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) RFI 1: PLEASE SUBMIT THE REVISED SHEET P2.1 SHOWING | | | THE OFFSETS TO THE APPROVED RISERS- SEC. 107.2.1 WPB. | | | | | | 2) RFI 68: PLEASE SUBMIT A REVISED SHEET A1.2 SHOWING | | | THE ACCESSIBLE SHOWER CONTROLS RELOCATED ON THE | | | OPPOSITE SIDE OF THE SIDE WITH THE WALL HUNG LAVATORY | | | ADJACENT- SEC. 608.2.2.1 FBC ACC. | | | | | | 3) RFI 68: PLEASE SUBMIT A REVISED PLUMBING ROOF | | | DRAINAGE PLAN WHICH INCLUDES THE RAINFALL RATE AND | | | GUTTER AND DOWNSPOUT SIZING CALCULATIONS- SECS. 1105.2, | | | 1106.3, & 1106.6 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-10-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-10-21 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-10-21 |
Time |
10:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-17 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-17 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2022-10-10 14:07:12 | P1.1 AND P0.1 APPEAR TO NOT BE SIGNED |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-09-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-09-13 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-09-13 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2022-08-30 13:24:30 | MECHANICAL DRAWING WILL NEED THE ORIGINAL DIGITAL | | | SIGNATURE. ME | | 2022-08-29 13:49:43 | ARCHITECTURAL AND STRUCTURAL SIGNATURES OK |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2022-09-13 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-09-13 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-09-13 |
Time |
13:07 |
Sent To |
|
|
| Notes |
|
|