Plan Review Details - Permit 22070563
Plan Review Stops For Permit 22070563
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-08-11 Cont ID  
Sent By shill Date 2022-08-11 Time 10:00 Rev Time 0.00
Received By shill Date 2022-08-03 Time 15:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-08-01 Cont ID  
Sent By mpeterso Date 2022-08-01 Time 15:06 Rev Time 0.00
Received By mpeterso Date 2022-08-01 Time 14:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-07-18 Cont ID  
Sent By cwalker Date 2022-07-18 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-07-18 12:27:49FIRE REVIEW COMMENTS:
 PROTECT ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR
 FIRE ALARM) FROM DAMAGE, PAINT, ETC. DURING ALL PHASES
 OF DEMOLITION AND CONSTRUCTION.
 ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE
 ALARM) SHALL REMAIN OPERATIONAL DURING ALL PHASES OF
 DEMOLITION AND CONSTRUCTION.
 ANY AND ALL WORK TO ANY LIFE SAFETY SYSTEM 9FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE CONDUCTED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-11 Cont ID  
Sent By shill Date 2022-08-11 Time 09:58 Rev Time 0.00
Received By shill Date 2022-07-15 Time 10:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-08-05 Cont ID  
Sent By jesmith Date 2022-07-21 Time 15:03 Rev Time 0.00
Received By rwbrown Date 2022-08-05 Time 05:45 Sent To  
Notes
2022-07-21 15:03:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070563 1501 S FLAGLER DR # 2B
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, PROVIDE A CROSS-SECTION SHOWER
 WALL/FLOOR/DRAIN AND THRESHOLD DETAIL
 DETAIL SHALL INCLUDE ALL COMPONENTS OF FBC PL 421.5.2
 AS FOLLOWS:
 LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2
 INCHES ABOVE THE FINISHED THRESHOLD LEVEL
 LINERS SHALL BE RECESSED AND FASTENED TO AN APPROVED
 BACKING
 LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY POINT
 LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAIN
 LINERS SHALL BE SECURELY FASTENED TO THE WASTE OUTLET
 AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT JOINT
 BETWEEN THE LINER AND THE OUTLET
 FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE
 LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY
 SOUND BASE.
 SPECIFY LINER MATERIAL COMPLYING WITH ONE OF THE
 FOLLOWING FBC PL SECTIONS-421.5.2.1, 421.5.2.2,
 421.5.2.3, 421.5.2.4, 421.5.2.5 OR 421.5.2.6. NOTE THAT
 FBC PL 421.5.2.1 PLASTICIZED POLYVINYL CHLORIDE (PVC)
 SHEETS MEETING THE REQUIREMENTS OF ASTM D4551 IS A
 COMMON LINER USED.
 FBC PL 421.4.1 BATHTUB FLOORS, SHOWER FLOORS, WALL
 AREAS ABOVE BUILT-IN TUBS THAT HAVE INSTALLED SHOWER
 HEADS AND WALLS IN SHOWER COMPARTMENTS SHALL BE
 CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL
 EXTEND TO A HEIGHT OF NOT LESS THAN 6 ABOVE THE ROOM
 FLOOR LEVEL, AND NOT LESS THAN 70 INCHES ABOVE THE
 DRAIN OF THE TUB OR SHOWER. SUCH WALLS SHALL FORM A
 WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE
 TUB OR SHOWER FLOOR.
  
 2. PER FBC PL 412.3INDIVIDUAL SHOWER AND TUB-SHOWER
 COMBINATION VALVES SHALL BE BALANCED-PRESSURE,
 THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER
 COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE
 EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF
 THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD
 ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 UTILIZED FOR COMPLIANCE WITH THIS SECTION.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-19 Cont ID  
Sent By mpeterso Date 2022-07-19 Time 13:59 Rev Time 0.00
Received By mpeterso Date 2022-07-19 Time 13:57 Sent To  
Notes
2022-07-19 13:59:567/19/22 SIGNATURE REVIEW OF PAPER PLANS/DOCUMENTS
 PASSED AND ROUTED TO STORAGE.MP