| 2022-10-18 11:53:39 | 1ST GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FRC G2413.4.1 - YOU'VE LISTED THE LONGEST RUN |
| | AT 60 FEET. HOWEVER, THE LONGEST RUN IS CALCULATED FROM |
| | THE SOURCE TO THE MOST REMOTE APPLIANCE AND IN THIS |
| | CASE WOULD BE = 80 FEET. |
| | |
| | 2. 2020 FRC G2439.5 (614.6) MAKEUP AIR FOR DRYER. |
| | PLEASE SHOW THE CALCULATION FOR THE REQUIREMENT OR |
| | EXCEPTION TO THE NEED FOR MAKE-UP AIR FOR THE DRYER. |
| | |
| | 3. 2017 WPB AMENDS 107.2.1 - SEEMS TO BE CONFLICTING |
| | INFORMATION. YOUR DESCRIPTION SAYS "INSTALL 250 GALLON |
| | LP TANK". HOWEVER, YOU'VE DETAILED NATURAL GAS AND |
| | SHOWN A METER? IF A TANK IS INSTALLED, INCLUDE ALL |
| | DETAILS, LOCATION AND TIE DOWNS. IF NOT, UPDATE THE |
| | PERMIT DESCRIPTION AND OTHER CONFLICTING INFORMATION. |
| | |
| | 4. 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO |
| | DESIGNED THE DRAWING PRINT THEIR NAME, SIGN THEIR NAME, |
| | AS WELL AS PUT YOUR CONTRACTOR NUMBER ON THE DRAWING AS |
| | REQUIRED BY THE WEST PALM BEACH AMENDMENTS TO CHAPTER |
| | 1. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | REFERENCED CODES: |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |