Plan Review Details - Permit 22070445
Plan Review Stops For Permit 22070445
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-09-22 Cont ID  
Sent By rmcdouga Date 2022-09-22 Time 11:19 Rev Time 0.00
Received By rmcdouga Date 2022-09-22 Time 11:18 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By rmcdouga Date 2022-08-05 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2022-08-05 Time 09:28 Sent To  
Notes
2022-08-05 09:29:40PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM
 BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME
 NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE ADDRESS, PERMIT NUMBER AND ?ASBESTOS? IN
 THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-09-22 Cont ID  
Sent By rmcdouga Date 2022-09-22 Time 13:05 Rev Time 0.00
Received By rmcdouga Date 2022-09-22 Time 11:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-08-05 Cont ID  
Sent By rmcdouga Date 2022-08-05 Time 13:32 Rev Time 0.00
Received By rmcdouga Date 2022-08-05 Time 09:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-10-18 Cont ID  
Sent By jleahy Date 2022-10-18 Time 13:24 Rev Time 0.00
Received By jleahy Date 2022-10-18 Time 13:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-10-17 Cont ID  
Sent By jleahy Date 2022-10-17 Time 09:40 Rev Time 0.00
Received By jleahy Date 2022-10-17 Time 08:46 Sent To  
Notes
2022-10-17 09:42:00FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SYMBOLS MISSING FOR MOST DEVICES, PLEASE PROVIDE SO WE
 WILL KNOW WHICH SYSTEMS ARE BEING INSTALLED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-08-31 Cont ID  
Sent By jleahy Date 2022-08-31 Time 10:51 Rev Time 0.00
Received By jleahy Date 2022-08-26 Time 16:27 Sent To  
Notes
2022-08-31 10:52:43FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PLANS ARE INCOMPLETE, MISSING WALLS AND RISER DIAGRAM.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-07-23 Cont ID  
Sent By jleahy Date 2022-07-23 Time 09:39 Rev Time 0.00
Received By jleahy Date 2022-07-23 Time 07:36 Sent To  
Notes
2022-07-23 09:40:30PLEASE CHECK PLANS THERE IS SOMETHING WRONG WITH THEM
 NOT READABLE. MISSING WALLS AND SYMBOLS JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-08-25 Cont ID  
Sent By pleduc Date 2022-08-25 Time   Rev Time 0.00
Received By pleduc Date 2022-08-25 Time 15:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-07-15 Cont ID  
Sent By pleduc Date 2022-07-15 Time   Rev Time 0.00
Received By pleduc Date 2022-07-15 Time 11:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-20 Cont ID  
Sent By rwbrown Date 2022-10-20 Time 08:58 Rev Time 0.00
Received By rwbrown Date 2022-10-19 Time 16:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-19 Cont ID  
Sent By rmcdouga Date 2022-10-19 Time 12:45 Rev Time 0.00
Received By rmcdouga Date 2022-09-23 Time 10:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-22 Cont ID  
Sent By rmcdouga Date 2022-09-22 Time 13:05 Rev Time 0.00
Received By rmcdouga Date 2022-08-24 Time 17:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-18 Cont ID  
Sent By lmarchan Date 2022-08-18 Time 11:06 Rev Time 0.00
Received By lmarchan Date 2022-07-14 Time 14:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-07-15 Cont ID  
Sent By medwards Date 2022-07-15 Time 11:01 Rev Time 0.00
Received By medwards Date 2022-07-15 Time 11:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-10-20 Cont ID  
Sent By rwbrown Date 2022-10-20 Time 08:55 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-09-26 Cont ID  
Sent By rwbrown Date 2022-09-26 Time 09:23 Rev Time 0.00
Received By rwbrown Date 2022-09-26 Time 09:21 Sent To  
Notes
2022-09-26 09:23:503RD PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. --THE MIXING VALVE FOR "HOT WATER" DELIVERY MUST BE
 PLACED AT THE HOT WATER SOURCE PER MY PREVIOUS COMMENT.
 2020 FPC 613.1
  
 -- NOT ADDRESSED -- ALL HOT WATER MUST BE LIMITED BY A
 DEVICE "OTHER THAN THE THERMOSTAT ON THE WATER HEATER".
 (607.1.1) AND PER 613.1 MUST BE INSTALLED AT THE HOT
 WATER SOURCE. YOUR RESPONSE ADDRESSES TEMPERED WATER,
 NOT HOT WATER. YOUR DETAIL FOR TEMPERED WATER IS
 SUFFICIENT.
 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE
 THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE
 LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE
 A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT
 WATER DELIVERY. THIS WOULD BE IN ADDTION TO THE
 REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING
 607.1.2/419.5.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-08-25 Cont ID  
Sent By rwbrown Date 2022-08-25 Time 07:15 Rev Time 0.00
Received By rwbrown Date 2022-08-25 Time 07:14 Sent To  
Notes
2022-08-25 07:18:222ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. -- NOT ADDRESSED -- ALL HOT WATER MUST BE LIMITED BY
 A DEVICE "OTHER THAN THE THERMOSTAT ON THE WATER
 HEATER". (607.1.1) AND PER 613.1 MUST BE INSTALLED AT
 THE HOT WATER SOURCE. YOUR RESPONSE ADDRESSES TEMPERED
 WATER, NOT HOT WATER. YOUR DETAIL FOR TEMPERED WATER IS
 SUFFICIENT.
 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE
 THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE
 LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE
 A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT
 WATER DELIVERY. THIS WOULD BE IN ADDTION TO THE
 REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING
 607.1.2/419.5.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-18 Cont ID  
Sent By rwbrown Date 2022-07-18 Time 09:17 Rev Time 0.00
Received By rwbrown Date 2022-07-18 Time 09:16 Sent To  
Notes
2022-07-18 09:17:441ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE
 THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE
 LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE
 A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT
 WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE
 REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING
 607.1.2/419.5.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-10-20 Cont ID  
Sent By rwbrown Date 2022-10-20 Time 08:58 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-10-19 Cont ID  
Sent By rmcdouga Date 2022-10-19 Time 12:45 Rev Time 0.00
Received By mpeterso Date 2022-10-19 Time 13:10 Sent To  
Notes
2022-10-19 13:11:35ALL PLANS PASSED SIGNATURE REVIEW. MP
2022-10-17 09:45:25ELECTRICAL PAGES SIGNATURES ARE APPROVED JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-22 Cont ID  
Sent By rmcdouga Date 2022-09-22 Time 13:05 Rev Time 0.00
Received By rmcdouga Date 2022-09-22 Time 11:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By rwbrown Date 2022-07-18 Time 08:47 Rev Time 0.00
Received By rmcdouga Date 2022-07-18 Time 08:47 Sent To  
Notes
2022-08-05 13:22:14THE ENGINEER, JAVAD AHMAD'S DIGITAL SIGNATURE ON THE
 DRAWINGS IS SELF-CERTIFIED. THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS REQUIRES ENGINEERS TO USE AN
 APPROVED THIRD PARTY AGENCY TO CERTIFY THEIR
 SIGNATURES. FS 471 & FAC 61G15
  
  
2022-07-15 11:02:01MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-29 Cont ID  
Sent By eschneid Date 2022-08-29 Time 09:35 Rev Time 0.25
Received By eschneid Date 2022-08-29 Time 09:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-08-18 Cont ID  
Sent By escheide Date 2022-08-18 Time 10:14 Rev Time 0.50
Received By eschneid Date 2022-08-18 Time 10:14 Sent To  
Notes
2022-08-18 10:17:39FAILED
  
 1) THE ELEVATIONS, FLOOR PLAN AND NOTE THAT THE SIGN
 J-BOX IS INSIDE THE STORE ROOF COMPLY WITH ZONING.
  
 2) THE MECHANICAL SHEETS ARE ILLEGIBLE SO ZONING IS
 UNABLE TO DETERMINE IF THERE IS ANY NEW ROOFTOP
 MECHANICAL EQUIPMENT. IF NONE, PLANS PASS ZONING. IF
 NEW ROOFTOP MECHANICAL, YOU MUST PROVIDE VERIFICATION
 OF COMPLIANT SCREENING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]