Plan Review Details - Permit 22070389
Plan Review Stops For Permit 22070389
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-09-22 Cont ID  
Sent By rmcphers Date 2022-09-22 Time 12:49 Rev Time 0.00
Received By rmcphers Date 2022-09-22 Time 12:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-09-20 Cont ID  
Sent By rmcphers Date 2022-09-20 Time 09:40 Rev Time 0.00
Received By rmcphers Date 2022-09-20 Time 09:40 Sent To  
Notes
2022-09-20 09:41:14REVISION TO LAYOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE LOCATION OF THE ACCESSIBLE LOWERED BAR COUNTER
 TOP AREA NEEDS TO BE SHOWN ON DRAWING A1.1.1 - FBC A
 226.1
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-16 Cont ID  
Sent By rmcphers Date 2022-08-16 Time 09:32 Rev Time 0.00
Received By rmcphers Date 2022-08-16 Time 09:32 Sent To  
Notes
2022-08-16 09:42:11REVISION TO LAYOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ACCESSIBLE SEATING LOCATION AT THE
 BAR - FBC A 226.1
  
 2) PLEASE SHOW THE ACCESSIBLE SEATING LOCATION IN EACH
 AREA OF DINING - FBC 226.2

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-06 Cont ID  
Sent By jleahy Date 2022-10-04 Time 16:51 Rev Time 0.00
Received By jleahy Date 2022-10-04 Time 16:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-08-23 Cont ID  
Sent By jleahy Date 2022-08-23 Time 13:54 Rev Time 0.00
Received By jleahy Date 2022-08-23 Time 13:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-09-14 Cont ID  
Sent By cwalker Date 2022-09-14 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-08-04 Cont ID  
Sent By cwalker Date 2022-08-04 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-08-04 10:15:23FIRE PROVISO NOTE:
  
 ALL EXITS SHALL BE CLEARLY MARKED. NFPA 101, 7.10
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2022-10-26 Cont ID  
Sent By ccole Date 2022-10-26 Time 07:47 Rev Time 0.00
Received By ccole Date 2022-10-26 Time 07:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-10-21 Cont ID  
Sent By ccole Date 2022-10-21 Time 13:04 Rev Time 0.00
Received By ccole Date 2022-10-21 Time 12:18 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-09-16 Cont ID  
Sent By ccole Date 2022-09-16 Time 16:40 Rev Time 0.00
Received By ccole Date 2022-09-16 Time 15:34 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By ccole Date 2022-08-03 Time 08:26 Rev Time 0.00
Received By ccole Date 2022-08-02 Time 13:17 Sent To  
Notes
2022-08-03 08:26:591ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22070389
 8/3/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P5.1 GAS PIPING ISOMETRIC CORRECTIONS:
 A) THE 1-1/4-INCH MAIN SUPPLY PIPE FROM THE METER
 REGULATOR TO THE TEE IS UNDERSIZED PER THE SIZING TABLE
 402.4(2) FBC FG THAT IS LISTED ON THE PLAN. BASED ON
 THE 1,512,000 BTU LOAD AT 42 FT. TDL A MINIMUM 2-INCH
 SUPPLY PIPE IS REQUIRED.
 B) PER TABLE 402.4(2), THE 3/4-INCH PIPES SUPPLYING THE
 495,000 BTU OVEN/STEAMERS SHALL BE INCREASED IN SIZE TO
 1-1/4 INCH.
  
 2) P5.1: PLEASE CORRECT THE COMBUSTION AIR CALCULATIONS
 TO SHOW THE KITCHEN APPLIANCE LOAD AT 1,313,000 BTUS,
 AND 460 CFMS OF AIR REQUIRED. PLEASE NOTE THAT HOOD
 MAKEUP IS DEDICATED REPLACEMENT AIR FOR HOOD EXHAUST
 AND CANNOT BE THE SOURCE OF COMBUSTION AIR FOR THE
 APPLIANCES- SEE SEC. 304.9.3 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2022-10-26 Time   Rev Time 0.00
Received By aoliver Date 2022-10-25 Time 06:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2022-10-21 Time   Rev Time 0.00
Received By lmarchan Date 2022-10-11 Time 15:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-04 Cont ID  
Sent By jleahy Date 2022-10-04 Time 16:51 Rev Time 0.00
Received By jleahy Date 2022-09-08 Time 08:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-23 Cont ID  
Sent By jleahy Date 2022-08-23 Time 13:55 Rev Time 0.00
Received By jleahy Date 2022-08-01 Time 10:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-08-12 Cont ID  
Sent By medwards Date 2022-08-12 Time 11:32 Rev Time 0.00
Received By medwards Date 2022-08-12 Time 11:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-10-26 Cont ID  
Sent By ccole Date 2022-10-26 Time 07:47 Rev Time 0.00
Received By ccole Date 2022-10-26 Time 07:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-10-21 Cont ID  
Sent By ccole Date 2022-10-21 Time 16:50 Rev Time 0.00
Received By ccole Date 2022-10-21 Time 12:18 Sent To  
Notes
2022-10-21 16:51:17 
 3RD REVIEW FBC-2020 PLUMBING
 PERMIT-22070389
 10/21/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW AND 2ND REVIEW ARE LISTED BELOW WITH
 ADDITIONAL NOTES.
  
 1) P2.1 THE SANITARY DRAWING SHOWS DRAINAGE FROM THE
 ICE CHESTS (B.5 & B.8) AND ICE MAKERS (B.11 & B.12)
 DISCHARGING INTO THE GREASE WASTE LINE INSTEAD OF THE
 SANTARY AS REQUIRED - SEC. 1003.3.1 FBC P.
  
 2) P5.1: THE REVISED SANITARY ISOMETRIC THE RISER SHOWS
 DRAINAGE FROM THE ICE CHESTS (B.5 & B.8) AND ICE MAKERS
 (B.12) DISCHARGING INTO THE GREASE WASTE LINE INSTEAD
 OF THE SANTARY AS REQUIRED- SEC. 1003.3.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-09-16 Cont ID  
Sent By ccole Date 2022-09-16 Time 16:11 Rev Time 0.00
Received By ccole Date 2022-09-16 Time 15:34 Sent To  
Notes
2022-09-16 16:29:532ND REVIEW FBC-2020 PLUMBING
 PERMIT-22070389
 8/2/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES
  
 1) FAILED. SHEETS P2.1 & P5.1: THE DRAINAGE FROM HAND
 SINKS- 21 & 50 SHALL DISCHARGE INTO THE SANITARY SYSTEM
 AND NOT THE GREASE WASTE AS SHOWN ON THE PLANS- SEC.
 1003.3.1 FBC P. PLEASE CORRECT THE DRAWINGS.
  
 THE SANITARY RISER SHOWS HANDSINK- 50 DRAINING INTO THE
 GREASE WASTE.
  
 2) FAILED. P2.1 & P5.1: THE DRAINAGE FROM THE MOP SINK,
 THE FLOOR DRAINS IN THE WALK-IN COOLER, AND THE FLOOR
 DRAINS AT THE UNDER BAR DUMP SINK (B.1) & THE
 WAREWASHER (B.3) SHALL DISCHARGE INTO THE GREASE WASTE
 LINE AND NOT THE SANITARY AS SHOWN ON THE PLANS- SEC.
 1003.3.1 FBC P- PLEASE CORRECT THE DRAWINGS. PLEASE
 NOTE THE LOCATION OF B.1 IS NOT SHOWN ON THE SANITARY
 AND WATER RISERS, AND THE SANITARY RISER SHOWS THE
 DRAINAGE FROM THE CORNER SINK (30) DISCHARGING FROM THE
 FLOOR DRAIN INTO THE SANITARY LINE.
  
 THE REVISED P.2.1 SHOWS DRAINAGE FROM THE ICE CHESTS
 (B.5 & B.8) AND ICE MAKERS(B.11 & B.12) DISCHARGING
 INTO THE GREASE WASTE LINE INSTEAD OF THE SANTARY- SEC.
 1003.3.1 FBC P.
 NO CORRECTIONS WERE MADE TO THE SANITARY RISER ON P.5.1
 WITH THE EXCEPTION OF THE DRAINAGE FROM HANDSINK-21 WAS
 RELOCATED TO THE SANITARY. PLEASSE MATCH THE RISER WITH
 THE PIPING LAYOUT PLAN.
  
  
 4) FAILED. P5.1 PLEASE PLACE A NOTE ON THE PLAN
 INDICATING THE GREASE INTERCEPTOR SHALL BE INSTALLED
 UNDER A SEPARATE PERMIT- SEC. 105.1 WPB. PLEASE NOTE
 THE FOLLOWING: DUE TO A CHANGE IN PROCESS, THE GREASE
 INTERCEPTOR PERMIT IS REQUIRED TO BE SUBMITTED PRIOR TO
 ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By ccole Date 2022-08-03 Time 07:50 Rev Time 0.00
Received By ccole Date 2022-08-02 Time 13:17 Sent To  
Notes
2022-08-03 07:51:221ST REVIEW FBC-2020 PLUMBING
 PERMIT-22070389
 8/2/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P2.1 & P5.1: THE DRAINAGE FROM HAND SINKS 21
 & 50 SHALL DISCHARGE INTO THE SANITARY SYSTEM AND NOT
 THE GREASE WASTE AS SHOWN ON THE PLANS- SEC. 1003.3.1
 FBC P. PLEASE CORRECT THE DRAWINGS.
  
 2) P2.1 & P5.1: THE DRAINAGE FROM THE MOP SINK, THE
 FLOOR DRAINS IN THE WALK-IN COOLER, AND THE FLOOR
 DRAINS AT THE UNDER BAR DUMP SINK (B.1) & THE
 WAREWASHER (B.3) SHALL DISCHARGE INTO THE GREASE WASTE
 LINE AND NOT THE SANITARY AS SHOWN ON THE PLANS- SEC.
 1003.3.1 FBC P- PLEASE CORRECT THE DRAWINGS. PLEASE
 NOTE THE LOCATION OF B.1 IS NOT SHOWN ON THE SANITARY
 AND WATER RISERS, AND THE SANITARY RISER SHOWS THE
 DRAINAGE FROM THE CORNER SINK (30) DISCHARGING FROM THE
 FLOOR DRAIN INTO THE SANITARY LINE.
  
 3) P5.1: SPECS AND CALCULATIONS HAVE BEEN PROVIDED FOR
 A SCHIER GB-250 GREASE INTERCEPTOR HOWEVER A SCHIER
 SI-50 SOLIDS INTERCEPTOR IS SHOWN ON THE RISER DRAWING-
 PLEASE CORRECT- SEC. 107.2.1 WPB.
  
 4) P5.1 PLEASE PLACE A NOTE ON THE PLAN INDICATING THE
 GREASE INTERCEPTOR SHALL BE INSTALLED UNDER A SEPARATE
 PERMIT- SEC. 105.1 WPB. PLEASE NOTE THE FOLLOWING: DUE
 TO A CHANGE IN PROCESS, THE GREASE INTERCEPTOR PERMIT
 IS REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO
 BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED
 BY EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
 5) P3.1 & P5.1: SHOW THE MEANS OF PROVIDING TEMPERED
 WATER DELIVERY FROM THE LAVATORIES- SECS. 419.5 &
 607.1.2 FBC P.
  
 6) P3.1 & P5.1: PROVIDE A MEANS OF LIMITING THE HOT
 WATER TEMPERATURE AT THE MOP SINK, WAREWASHERS, PREP
 SINKS ETC.- SEC. 607.1.1 FBC P. BECAUSE THE THERMOSTAT
 ON THE WATER HEATER CANNOT BE THE MEANS OF LIMITING THE
 TEMPERATURE, TYPICALLY A MASTER THERMOSTATIC MIXING
 VALVE OR POINT OF USE MIXING VALVES ARE INSTALLED.
  
 7) A9.0.1 DETAIL A: PROVIDE THE LENGTH AND WIDTH
 DIMENSIONS OF THE RESTROOMS- SEC. 107.2.1 WPB.
  
 8) A9.0.1 DETAIL A: SHOW THE DIMENSIONS OF THE CLEAR
 FLOOR SPACES FOR THE WATER CLOSETS AND LAVATORIES-
 SECS. 604.3 & 606.2 FBC ACC.
  
 9) A9.0.1 DETAILS 1 & 6: SHOW THE HEIGHT MEASUREMENTS
 OF THE GRAB BARS MEASURED FROM THE FINISHED FLOORS TO
 THE TOPS OF THE GRAB BARS- SEC. 609.4 FBC ACC.
  
 10) A9.0.1 DETAILS 1 & 6: SHOW THE HEIGHT MEASUREMENTS
 OF THE MIRRORS MEASURED FROM THE FINISHED FLOORS TO THE
 BOTTOMS OF THE REFLECTIVE SURFACES- SEC. 603.3 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-10-26 Cont ID  
Sent By ccole Date 2022-10-26 Time 07:47 Rev Time 0.00
Received By ccole Date 2022-10-26 Time 07:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-10-21 Cont ID  
Sent By ccole Date 2022-10-21 Time 13:04 Rev Time 0.00
Received By ccole Date 2022-10-21 Time 12:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-20 Cont ID  
Sent By rmcphers Date 2022-09-20 Time 09:48 Rev Time 0.00
Received By rmcphers Date 2022-09-20 Time 09:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-08-16 Cont ID  
Sent By rmcphers Date 2022-08-16 Time 09:48 Rev Time 0.00
Received By rmcphers Date 2022-08-16 Time 09:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-08-10 Cont ID  
Sent By ajones Date 2022-08-10 Time 14:00 Rev Time 0.00
Received By afowlkes Date 2022-08-10 Time 14:00 Sent To  
Notes
***NONE***