| Plan Review Stops For Permit 22070231 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
P |
Date |
2022-08-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-08-17 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2022-08-17 |
Time |
06:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2022-08-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-08-16 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-16 08:17:16 | TO THE BUILDING CONTRACTOR: | | | PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION | | | THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE. | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT | | | THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN | | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | | INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT | | | LINE. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2022-08-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-08-04 |
Time |
13:21 |
Rev Time |
|
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-04 13:21:36 | TO THE BUILDING CONTRACTOR: | | | PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION | | | THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE. | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT | | | THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN | | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | | INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT | | | LINE. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-08-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-08-16 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2022-08-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-08-04 |
Time |
13:30 |
Rev Time |
|
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-04 13:30:31 | BUILDING PROVISO; 2020 FBC-B 2509.2 BASE FOR TILE. | | | MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND | | | SHOWER AREAS AND WALLS AND CEILING PANELS IN SHOWER | | | AREAS SHALL BE OF MATERIALS LISTED IN TABLE 2509.2 AND | | | INSTALLED IN ACCORDANCE WITH MANUFACTURER?S | | | RECOMMENDATIONS. WATER RESISTANT GYPSUM (MR BOARD) | | | SHALL NOT BE USED FOR SHOWER & TUB ENCLOSURES BUT CAN | | | BE USED FOR BACKING BOARD FOR A BASE FOR TILE IN WATER | | | CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE | | | WITH GA-216 OR ASTM C840 AND THE MANUFACTURE?S | | | RECOMMENDATIONS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-08-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-08-23 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-08-23 |
Time |
12:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-07-29 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-07-29 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-07-29 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2022-07-29 10:18:26 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | KITCHEN ISLAND NEEDS OUTLET(S) PER 210.52 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-08-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-08-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-08-11 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2022-08-11 15:52:59 | FIRE PROVISO: | | | | | | PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND | | | EQUIPMENT. | | | | | | DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM | | | DEVICES/EQUIPMENT. | | | | | | THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT | | | DEMO AND CONSTRUCTION. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-07-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-07-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-07-13 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2022-07-13 14:00:37 | FIRE PROVISO: | | | | | | PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND | | | EQUIPMENT. | | | | | | DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM | | | DEVICES/EQUIPMENT. | | | | | | THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT | | | DEMO AND CONSTRUCTION. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-08-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-08-23 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-08-10 |
Time |
06:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-08-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
cdecoeur |
Date |
2022-07-12 |
Time |
08:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-08-12 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-08-12 |
Time |
10:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-07-18 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-07-18 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-07-18 |
Time |
13:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2022-08-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-08-05 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-08-05 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2022-08-05 07:39:54 | THERE IS NO ARCHITECT OR ENGINEER FOR THIS PROJECT. |
|
|