| Plan Review Stops For Permit 22070117 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-09-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-09-07 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-09-07 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-08-31 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-08-31 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2022-08-31 16:42:59 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD CALCULATIONS ARE FOR A UNIT THAT | | | THAT WEIGHS 850 LBS. THE GENERATOR SPECIFICATIONS THAT | | | WERE SUBMITTED ARE FOR A UNIT THAT WEIGHS 455 LBS. AND | | | ARE NOT ACCEPTABLE. SUBMIT ENGINEERING CALCULATIONS FOR | | | THE CORRECT SIZE AND WEIGHT UNIT. FBC-R107.2.1 | | | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. | | | FBC-R303.5.1 INTAKE OPENINGS.MECHANICAL AND GRAVITY | | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-08-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-08-11 |
Time |
17:29 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-08-11 |
Time |
17:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2022-09-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-19 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-19 |
Time |
06:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2022-08-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-17 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-16 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2022-08-17 08:58:19 | | | | 2ND REVIEW FBC-2020 RES. GAS | | | PERMIT- 22070117 | | | 8/17/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. COMMENTS PRINTED BELOW | | | FROM THE 1ST REVIEW WERE NOT ADDRESSED- PLEASE COMPLY. | | | | | | 1) GAS RISER: REVISE THE RISER DRAWING TO SHOW THE | | | EXISTING GAS PIPING TO THE POOL HEATER APPROVED UNDER | | | PERMIT- 22061538. IT IS ACKNOWLEDGED THAT INSTALLATION | | | OF THE POOL HEATER IS NOT IN THE SCOPE OF THIS PERMIT | | | HOWEVER A COMPLETE GAS RISER IS REQUIRED UNDER THIS | | | PERMIT BASED ON SECS. G2412.3 & G2412.4 FBC RES. | | | | | | 2) GAS RISER: SHOW THE SIZE OF THE MAIN SUPPLY PIPE | | | FROM THE METER TO THE 1ST TEE- TABLE 402.4(5) FBC FG. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-08-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-08 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-08 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2022-08-08 14:10:17 | | | | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 22070117 | | | 8/8/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) GAS RISER: REVISE THE RISER DRAWING TO SHOW THE | | | EXISTING GAS PIPING TO THE POOL HEATER APPROVED UNDER | | | PERMIT- 22061538. THE GAS PIPING HAS PASSED ROUGH | | | INSPECTION AND FINAL INSPECTION IS SCHEDULED FOR | | | 8/9/22. IT IS ACKNOWLEDGED THAT INSTALLATION OF THE | | | POOL HEATER IS NOT IN THE SCOPE OF THIS PERMIT HOWEVER | | | A COMPLETE GAS RISER IS REQUIRED UNDER THIS PERMIT | | | BASED ON SECS. G2412.3 & G2412.4 FBC RES. | | | | | | 2) GAS RISER: SHOW THE SIZE OF THE MAIN SUPPLY PIPE | | | FROM THE METER TO THE 1ST TEE- TABLE 402.4(5) FBC FG. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-08-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-01 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-01 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2022-08-01 10:57:15 | NO REVIEW AT THIS TIME PENDING PP REVIEW. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-09-21 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-09-21 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-09-21 |
Time |
16:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-09-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-09-07 |
Time |
07:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-08-31 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-08-04 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-08-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-08-01 |
Time |
07:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-20 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2022-07-25 07:22:15 | ADD B, E AFTER ZONING, AFFIDAVIT REVIEW | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
N |
Date |
2022-09-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-19 |
Time |
06:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-19 |
Time |
06:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2022-09-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-08 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2022-08-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-08 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-08 |
Time |
12:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2022-08-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-01 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-01 |
Time |
11:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
2 |
Status |
P |
Date |
2022-08-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-08-16 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-08-16 |
Time |
11:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2022-08-03 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-08-03 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-08-03 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2022-08-03 08:55:10 | 553.791, F.S. PRIVATE PROVIDER PLAN REVIEW COMPLIANCE | | | AFFIDAVIT. | | | - PLEASE PROVIDE PLAN REVIEW COMPLIANCE AFFIDAVIT. | | | UPLOAD INTO SUPPORTING DOCUMENTS IN PROJECTDOX. | | | MAKE SURE TO LIST ALL REVIEWED DOCUMENTS AND RELATE TO | | | THE DOCUMENTS BY PAGE NUMBER, AUTHOR AND DATE. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-09-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-09-07 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-09-07 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-08-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-08 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-08 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2022-08-08 14:16:37 | 2ND SIGNATURE REVIEW | | | 22070117 | | | 8/8/22 | | | | | | PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST | | | REVIEW PRINTED BELOW STILL EXISTS- PLEASE COMPLY. | | | | | | 1) SHEET E-1 WHICH SHOWS THE GENERATOR PAD ENGINEERING | | | IS NOT DIGITALLY SIGNED AND SEALED BY THE ENGINEER OF | | | RECORD- FL. STATUTE 471.025, AND SECTION 61G15-23.005 | | | FAC. | | | | | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR | | | ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND | | | DOCUMENTS. | | | A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL | | | ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY | | | CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION. | | | THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE | | | A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES | | | NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.) | | | YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE | | | ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT | | | USE A THIRD PARTY. | | | YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT | | | IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE | | | AND DOCUMENT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-08-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-01 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-01 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2022-08-01 11:18:50 | SIGNATURE REVIEW | | | 22070117 | | | 8/1/22 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET E-1 WHICH SHOWS THE GENERATOR PAD ENGINEERING | | | IS NOT DIGITALLY SIGNED AND SEALED BY THE ENGINEER OF | | | RECORD- FL. STATUTE 471.025, AND SECTION 61G15-23.005 | | | FAC. | | | | | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR | | | ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND | | | DOCUMENTS. | | | A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL | | | ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY | | | CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION. | | | THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE | | | A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES | | | NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.) | | | YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE | | | ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT | | | USE A THIRD PARTY. | | | YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT | | | IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE | | | AND DOCUMENT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2022-09-21 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-09-21 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-09-21 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2022-09-16 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-09-16 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-09-16 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2022-09-16 13:01:30 | | | | 9/16/2022 | | | | | | FAIL | | | | | | PLEASE LABEL SETBACKS CORRECTLY | | | | | | | | | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR | | | FEET INTO A SETBACK. | | | | | | WASHINGTON ROAD IS CONSIDERED YOUR FRONT SETBACK | | | MONROE DRIVE IS CONSIDERED YOUR CORNER SETBACK | | | | | | | | | | | | ALEXIS SANGELEER | | | ASSOCIATEPLANNER | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-08-11 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-08-11 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-08-11 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2022-08-11 13:58:28 | 8/11/2022 | | | FAILED | | | | | | | | | PLEASE ADDRESS PREVIOUS COMMENTS MADE IN REFERENCE TO | | | LABELING THE GENERATOR SETBACKS CORRECTLY. | | | | | | | | | | | | ALEXIS SANGELEER | | | ASSOCIATE PLANNER | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-07-26 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-07-26 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2022-07-26 15:31:08 | 7/26/2022 | | | FAIL | | | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR | | | FEET INTO A SETBACK. | | | | | | WASHINGTON ROAD IS CONSIDERED YOUR FRONT SETBACK | | | MONROE DRIVE IS CONSIDERED YOUR CORNER SETBACK | | | | | | | | | ALEXIS SANGELEER | | | ASSOCIATE PLANNER | | | [email protected] |
|
|