Plan Review Details - Permit 22070117
Plan Review Stops For Permit 22070117
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-09-07 Cont ID  
Sent By rmcdouga Date 2022-09-07 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2022-09-07 Time 09:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-31 Cont ID  
Sent By rmcdouga Date 2022-08-31 Time 16:28 Rev Time 0.00
Received By rmcdouga Date 2022-08-31 Time 16:28 Sent To  
Notes
2022-08-31 16:42:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD CALCULATIONS ARE FOR A UNIT THAT
 THAT WEIGHS 850 LBS. THE GENERATOR SPECIFICATIONS THAT
 WERE SUBMITTED ARE FOR A UNIT THAT WEIGHS 455 LBS. AND
 ARE NOT ACCEPTABLE. SUBMIT ENGINEERING CALCULATIONS FOR
 THE CORRECT SIZE AND WEIGHT UNIT. FBC-R107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING.
 FBC-R303.5.1 INTAKE OPENINGS.MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-08-11 Cont ID  
Sent By jleahy Date 2022-08-11 Time 17:29 Rev Time 0.00
Received By jleahy Date 2022-08-11 Time 17:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2022-09-19 Cont ID  
Sent By ccole Date 2022-09-19 Time 07:19 Rev Time 0.00
Received By ccole Date 2022-09-19 Time 06:45 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2022-08-17 Cont ID  
Sent By ccole Date 2022-08-17 Time 08:56 Rev Time 0.00
Received By ccole Date 2022-08-16 Time 11:36 Sent To  
Notes
2022-08-17 08:58:19 
 2ND REVIEW FBC-2020 RES. GAS
 PERMIT- 22070117
 8/17/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS PRINTED BELOW
 FROM THE 1ST REVIEW WERE NOT ADDRESSED- PLEASE COMPLY.
  
 1) GAS RISER: REVISE THE RISER DRAWING TO SHOW THE
 EXISTING GAS PIPING TO THE POOL HEATER APPROVED UNDER
 PERMIT- 22061538. IT IS ACKNOWLEDGED THAT INSTALLATION
 OF THE POOL HEATER IS NOT IN THE SCOPE OF THIS PERMIT
 HOWEVER A COMPLETE GAS RISER IS REQUIRED UNDER THIS
 PERMIT BASED ON SECS. G2412.3 & G2412.4 FBC RES.
  
 2) GAS RISER: SHOW THE SIZE OF THE MAIN SUPPLY PIPE
 FROM THE METER TO THE 1ST TEE- TABLE 402.4(5) FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-08-08 Cont ID  
Sent By ccole Date 2022-08-08 Time 14:09 Rev Time 0.00
Received By ccole Date 2022-08-08 Time 12:06 Sent To  
Notes
2022-08-08 14:10:17 
 1ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22070117
 8/8/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: REVISE THE RISER DRAWING TO SHOW THE
 EXISTING GAS PIPING TO THE POOL HEATER APPROVED UNDER
 PERMIT- 22061538. THE GAS PIPING HAS PASSED ROUGH
 INSPECTION AND FINAL INSPECTION IS SCHEDULED FOR
 8/9/22. IT IS ACKNOWLEDGED THAT INSTALLATION OF THE
 POOL HEATER IS NOT IN THE SCOPE OF THIS PERMIT HOWEVER
 A COMPLETE GAS RISER IS REQUIRED UNDER THIS PERMIT
 BASED ON SECS. G2412.3 & G2412.4 FBC RES.
  
 2) GAS RISER: SHOW THE SIZE OF THE MAIN SUPPLY PIPE
 FROM THE METER TO THE 1ST TEE- TABLE 402.4(5) FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2022-08-03 Cont ID  
Sent By ccole Date 2022-08-01 Time 10:56 Rev Time 0.00
Received By ccole Date 2022-08-01 Time 10:15 Sent To  
Notes
2022-08-01 10:57:15NO REVIEW AT THIS TIME PENDING PP REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-09-21 Cont ID  
Sent By asangele Date 2022-09-21 Time 16:39 Rev Time 0.00
Received By asangele Date 2022-09-21 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2022-09-19 Time   Rev Time 0.00
Received By aoliver Date 2022-09-07 Time 07:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-31 Cont ID  
Sent By rmcdouga Date 2022-08-31 Time 16:43 Rev Time 0.00
Received By rmcdouga Date 2022-08-04 Time 09:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-01 Cont ID  
Sent By shill Date 2022-08-01 Time 07:10 Rev Time 0.00
Received By shill Date 2022-07-20 Time 08:44 Sent To  
Notes
2022-07-25 07:22:15ADD B, E AFTER ZONING, AFFIDAVIT REVIEW
  

Review Stop P PLUMBING
Rev No 4 Status N Date 2022-09-19 Cont ID  
Sent By ccole Date 2022-09-19 Time 06:45 Rev Time 0.00
Received By ccole Date 2022-09-19 Time 06:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2022-09-08 Cont ID  
Sent By ccole Date 2022-09-08 Time 07:42 Rev Time 0.00
Received By ccole Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-08-08 Cont ID  
Sent By ccole Date 2022-08-08 Time 12:23 Rev Time 0.00
Received By ccole Date 2022-08-08 Time 12:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-08-01 Cont ID  
Sent By ccole Date 2022-08-01 Time 11:10 Rev Time 0.00
Received By ccole Date 2022-08-01 Time 11:10 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2022-08-16 Cont ID  
Sent By dbattles Date 2022-08-16 Time 11:22 Rev Time 0.00
Received By dbattles Date 2022-08-16 Time 11:22 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By dbattles Date 2022-08-03 Time 08:52 Rev Time 0.00
Received By dbattles Date 2022-08-03 Time 08:52 Sent To  
Notes
2022-08-03 08:55:10553.791, F.S. PRIVATE PROVIDER PLAN REVIEW COMPLIANCE
 AFFIDAVIT.
 - PLEASE PROVIDE PLAN REVIEW COMPLIANCE AFFIDAVIT.
 UPLOAD INTO SUPPORTING DOCUMENTS IN PROJECTDOX.
 MAKE SURE TO LIST ALL REVIEWED DOCUMENTS AND RELATE TO
 THE DOCUMENTS BY PAGE NUMBER, AUTHOR AND DATE.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-07 Cont ID  
Sent By rmcdouga Date 2022-09-07 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2022-09-07 Time 09:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-08-08 Cont ID  
Sent By ccole Date 2022-08-08 Time 14:14 Rev Time 0.00
Received By ccole Date 2022-08-08 Time 13:44 Sent To  
Notes
2022-08-08 14:16:372ND SIGNATURE REVIEW
 22070117
 8/8/22
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST
 REVIEW PRINTED BELOW STILL EXISTS- PLEASE COMPLY.
  
 1) SHEET E-1 WHICH SHOWS THE GENERATOR PAD ENGINEERING
 IS NOT DIGITALLY SIGNED AND SEALED BY THE ENGINEER OF
 RECORD- FL. STATUTE 471.025, AND SECTION 61G15-23.005
 FAC.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-01 Cont ID  
Sent By ccole Date 2022-08-01 Time 11:17 Rev Time 0.00
Received By ccole Date 2022-08-01 Time 11:12 Sent To  
Notes
2022-08-01 11:18:50SIGNATURE REVIEW
 22070117
 8/1/22
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E-1 WHICH SHOWS THE GENERATOR PAD ENGINEERING
 IS NOT DIGITALLY SIGNED AND SEALED BY THE ENGINEER OF
 RECORD- FL. STATUTE 471.025, AND SECTION 61G15-23.005
 FAC.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2022-09-21 Cont ID  
Sent By asangele Date 2022-09-21 Time 16:38 Rev Time 0.00
Received By asangele Date 2022-09-21 Time 16:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2022-09-16 Cont ID  
Sent By asangele Date 2022-09-16 Time 13:00 Rev Time 0.00
Received By asangele Date 2022-09-16 Time 13:00 Sent To  
Notes
2022-09-16 13:01:30 
 9/16/2022
  
 FAIL
  
 PLEASE LABEL SETBACKS CORRECTLY
  
  
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR
 FEET INTO A SETBACK.
  
 WASHINGTON ROAD IS CONSIDERED YOUR FRONT SETBACK
 MONROE DRIVE IS CONSIDERED YOUR CORNER SETBACK
  
  
  
 ALEXIS SANGELEER
 ASSOCIATEPLANNER
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2022-08-11 Cont ID  
Sent By asangele Date 2022-08-11 Time 13:53 Rev Time 0.00
Received By asangele Date 2022-08-11 Time 13:53 Sent To  
Notes
2022-08-11 13:58:288/11/2022
 FAILED
  
  
 PLEASE ADDRESS PREVIOUS COMMENTS MADE IN REFERENCE TO
 LABELING THE GENERATOR SETBACKS CORRECTLY.
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By asangele Date 2022-07-26 Time 15:26 Rev Time 0.00
Received By asangele Date 2022-07-26 Time 15:25 Sent To  
Notes
2022-07-26 15:31:087/26/2022
 FAIL
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN FOUR
 FEET INTO A SETBACK.
  
 WASHINGTON ROAD IS CONSIDERED YOUR FRONT SETBACK
 MONROE DRIVE IS CONSIDERED YOUR CORNER SETBACK
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]