Plan Review Details - Permit 22070103
Plan Review Stops For Permit 22070103
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-08-02 Cont ID  
Sent By cpuell Date 2022-08-02 Time 16:12 Rev Time 0.00
Received By cpuell Date 2022-08-02 Time 16:12 Sent To  
Notes
2022-08-02 16:13:47WORK IS FOR 211 AND 213 MARLBOROUGH RD. 213 MARLBOROUGH
 RD A KITCHEN WILL BE DOWNSTAIRS BUT NOT UPSTAIRS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2023-05-04 Cont ID  
Sent By jgomez Date 2023-05-04 Time 19:05 Rev Time 0.00
Received By jgomez Date 2023-05-04 Time 18:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-04-24 Cont ID  
Sent By jgomez Date 2023-04-24 Time 18:35 Rev Time 0.00
Received By jgomez Date 2023-04-24 Time 16:47 Sent To  
Notes
2023-04-24 18:57:52RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #22070103
 211 MARLBOROUGH RD
  
 1- REVISED DRAWING A-02.1 DOESN'T HAVE THE ARCHITECT'S
 DIGITAL SIGNATURE.
 NEED TO SUBMIT DRAWING ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-03-08 Cont ID  
Sent By jgomez Date 2023-03-08 Time 16:38 Rev Time 0.00
Received By jgomez Date 2023-03-08 Time 13:44 Sent To  
Notes
2023-03-08 16:39:34RESIDENTIAL (R3) REVISION, THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #22070103
 211 MARLBOROUGH RD
  
 PREVIOUS COMMENT:
 9- PROVIDE COMPLETE FRAMING PLANS FOR NEW 30"X96"
 SKYLIGHT AND FOR NEW SOLAR TUBES. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NO ADDRESSED. PROVIDE COMPLETE FRAMING
 DETAILS. PROVIDE ROOF FRAMING PLAN AND SPECIFY ALL
 FRAMING MEMBERS & CONNECTORS.
  
 11- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
  
 PREVIOUS COMMENT:
 A)SOLATUBE FLORIDA PRODUCT APPROVAL SUBMITTED
 (FL11480-R13) DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD ON SHEET S-000.
 NEED TO PROVIDE PRODUCT APPROVAL THAT MEETS OR EXCEEDS
 CALCULATED DESIGN PRESSURES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 PREVIOUS COMMENT:
 B)SKYLIGHT (30"X96") NOA 20-1013.05 SUBMITTED DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECORD ON SHEET S-000. NEED TO PROVIDE PRODUCT APPROVAL
 THAT MEETS OR EXCEEDS CALCULATED DESIGN PRESSURES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 PREVIOUS COMMENT:
 D)WINDOW MULLIONS FLORIDA PRODUCT APPROVAL FL34545
 SUBMITTED. NOTE: NEED TO SPECIFY MULLION SIZE TO VERIFY
 PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 PREVIOUS COMMENT:
 E)FIXED WINDOW FLORIDA PRODUCT APPROVAL FL34706
 SUBMITTED: SHEET 2 OF 7 OF INSTALLATION DRAWINGS SHOWS
 TYPE GLASS "B" TO BE USED. THIS TYPE OF GLASS IS NOT
 COVERED IN THE DESIGN LOADS CAPACITY TABLES FOR 4"-2" X
 6'-10" WINDOW "A1" SPECIFIED ON SHEET A-09. SEE SHEETS
 3 OF 7 AND 4 OF 7 OF INSTALLATION DRAWINGS AND REVISE
 AS REQUIRED OR PROVIDE PRODUCT APPROVAL THAT WORKS TO
 MEET THE CALCULATED DESIGN PRESSURES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 PREVIOUS COMMENT:
 F)FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS
 GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
 NOTE: THERE ARE DIFFERENT TYPES OF CONSTRUCTION IN THIS
 HOUSE. CONCRETE ROOF (NEW TERRACE) AND WOOD FRAMED
 (EXISTING ROOFS). ALSO, THERE ARE SOME FLAT ROOF TO BE
 COVERED WITH TILE AND THERE IS THE MAIN ROOF, NOT A
 DECK. PROVIDE PRODUCT APPROVAL COMPATIBLE EACH PROPOSED
 APPLICATION.
  
 RESPONSE:
 THE DESIGN PRESSURES OF SELECTED SYSTEM W-77 ON PAGE 15
 OF 20 OF FLORIDA PRODUCT APPROVAL FL2533-R28 SUBMITTED
 DON'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES.
 NEED TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 AS REQUIRED BY LIMITATION 5.7.2 OF PAGE 5 OF 5 OF
 PRODUCT APPROVAL SUBMITTED.
  
 NOTE:
 THERE ARE ROOFING SUBPERMITS FOR THIS PROJECT. TO AVOID
 CONFLICTS/DELAYS AND TO EXPEDITE THE BUILDING REVIEW
 PROCESS IT WILL BE BETTER TO SUBMIT ALL THE ROOFING
 PRODUCT APPROVALS ALONG WITH THE ROOFING PERMITS.
  
 PREVIOUS COMMENT:
 G) ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 SEE NOTE ABOVE REGARDING ROOF PRODUCT APPROVALS.
  
 PREVIOUS COMMENT:
 H)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS
 LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED.
  
 RESPONSE:
 SEE NOTE ABOVE REGARDING ROOF PRODUCT APPROVALS.
  
 PREVIOUS COMMENT:
 I) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY
 MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC.
 R905.3.7.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 SEE NOTE ABOVE REGARDING ROOF PRODUCT APPROVALS.
  
 12-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL REVISED PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-11-18 Cont ID  
Sent By jgomez Date 2022-11-18 Time 15:07 Rev Time 0.00
Received By jgomez Date 2022-11-17 Time 18:00 Sent To  
Notes
2022-11-08 15:16:14RESIDENTIAL (R3) REVISION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #22070103 211 MARLBOROUGH RD
  
 1- OK.
 2- OK.
  
 3- OK. CBAA CASE #1455 WAS APPROVED.
  
 ORIGINAL COMMENT:
 4- WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON THE
 ARCHITECTURAL EXTERIOR ELEVATIONS DON'T MATCH THE
 DESIGN PRESSURES CALCULATED BY THE STRUCTURAL ENGINEER.
 REVISE AS REQUIRED TO MATCH. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 DESIGN PRESSURES WERE REMOVED FROM THE ENGINEER'S
 DRAWINGS. DESIGN PRESSURES SHOWN ON THE ARCHITECTURAL
 PLANS ARE TOO LOW FOR BUILDING LOCATED IN EXPOSURE "D"
 AS SPECIFIED BY THE ENGINEER OF RECORD UNDER THE WIND
 DESIGN DATA. REVISE AS REQUIRED. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 5- OK.
 6- OK.
 7- OK.
 8- OK.
  
 ORIGINAL COMMENT:
 9- PROVIDE COMPLETE FRAMING PLANS FOR NEW 30"X96"
 SKYLIGHT AND FOR NEW SOLAR TUBES. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER SAYS FRAMING DETAILS HAVE
 BEEN ADDED TO STRUCTURAL DRAWINGS. STRUCTURAL DRAWINGS
 SAYS SKYLIGHT SEE ARCH ???L DRAWINGS. INFORMATION WAS
 NOT PROVIDED. PROVIDE COMPLETE FRAMING DETAILS. SPECIFY
 ALL FRAMING MEMBERS & CONNECTORS.
  
 ORIGINAL COMMENT:
 10- GUARDRAILS: DESIGNER OF RECORD NEEDS TO PROVIDE THE
 DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 BALCONY AND TERRACE GUARDRAILS AS REQUIRED BY TABLE
 R301.5, SEC. AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT
 DESIGN DETAILS AND SPECIFICATIONS ARE MET.
  
 RESPONSE:
 ARCHITECTURAL PLANS SAYS SEE STRUCTURAL DRAWINGS.
 STRUCTURAL DRAWINGS SAYS SEE ARCHITECTURAL DRAWINGS.
 INFORMATION WAS NOT SUBMITTED.
  
 NOTE; ITEM #11 WILL BE REVIEWED ONCE DESIGN PRESSURES
 ARE REVISED. SEE ITEM #4 ABOVE. PLEASE MAKE SURE BELOW
 COMMENTS FOR EACH PRODUCT APPROVAL IS ADDRESSED TO
 AVOID CONFLICTS/DELAYS.
 11- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)SOLATUBE FLORIDA PRODUCT APPROVAL SUBMITTED
 (FL11480-R13) DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD ON SHEET S-000.
 NEED TO PROVIDE PRODUCT APPROVAL THAT MEETS OR EXCEEDS
 CALCULATED DESIGN PRESSURES.
  
 B)SKYLIGHT (30"X96") NOA 20-1013.05 SUBMITTED DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECORD ON SHEET S-000. NEED TO PROVIDE PRODUCT APPROVAL
 THAT MEETS OR EXCEEDS CALCULATED DESIGN PRESSURES.
  
 C)SINGLE OUTSWING FRENCH DOOR FL34006 SUBMITTED DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECORD ON SHEET S-200. NEED TO PROVIDE PRODUCT APPROVAL
 THAT MEETS OR EXCEEDS CALCULATED DESIGN PRESSURES.
 NOTE: PLEASE UPLOAD THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND CORRESPONDING INSTALLATION DRAWINGS ON THE
 SAME PDF FILE. DO NOT UPLOAD IN SEPARATE FILES.
  
 D)WINDOW MULLIONS FLORIDA PRODUCT APPROVAL FL34545
 SUBMITTED. NOTE: NEED TO SPECIFY MULLION SIZE TO VERIFY
 PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 E)FIXED WINDOW FLORIDA PRODUCT APPROVAL FL34706
 SUBMITTED: SHEET 2 OF 7 OF INSTALLATION DRAWINGS SHOWS
 TYPE GLASS "B" TO BE USED. THIS TYPE OF GLASS IS NOT
 COVERED IN THE DESIGN LOADS CAPACITY TABLES FOR 4"-2" X
 6'-10" WINDOW "A1" SPECIFIED ON SHEET A-09. SEE SHEETS
 3 OF 7 AND 4 OF 7 OF INSTALLATION DRAWINGS AND REVISE
 AS REQUIRED OR PROVIDE PRODUCT APPROVAL THAT WORKS TO
 MEET THE CALCULATED DESIGN PRESSURES.
  
 F)FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS
 GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
 NOTE: THERE ARE DIFFERENT TYPES OF CONSTRUCTION IN THIS
 HOUSE. CONCRETE ROOF (NEW TERRACE) AND WOOD FRAMED
 (EXISTING ROOFS). ALSO, THERE ARE SOME FLAT ROOF TO BE
 COVERED WITH TILE AND THERE IS THE MAIN ROOF, NOT A
 DECK. PROVIDE PRODUCT APPROVAL COMPATIBLE EACH PROPOSED
 APPLICATION.
  
 G) ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
  
 H)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS
 LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED.
  
 I) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY
 MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC.
 R905.3.7.1 FBC-RESIDENTIAL.
  
 12-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 TO BE COORDINATED WITH ITEM #11 ABOVE. PLEASE MAKE SURE
 ALL PRODUCT APPROVALS ARE REVIEWED/APPROVED TO AVOID
 CONFLICTS/DELAYS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By jgomez Date 2022-08-05 Time 14:59 Rev Time 0.00
Received By jgomez Date 2022-08-05 Time 10:53 Sent To  
Notes
2022-08-05 15:00:57RESIDENTIAL (R3) REVISION, ADDITION/ALTERATION BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #22070103 211 MARLBOROUGH RD
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
  
 COMMENTS FOR MAIN HOUSE REVISION ONLY (NOTE: DETACHED
 GARAGE REVIEW DONE UNDER PERMIT #22070105):
 1- THIS REVISION IS ONLY FOR THE WORK AT THE MAIN
 HOUSE. ALL THE PLANS SUBMITTED FOR WORK AT THE TWO
 STORY DETACHED GARAGE NEEDS TO BE SUBMITTED UNDER
 SEPARATE PERMIT. THIS IS REQUIRED IN ORDER TO AVOID
 CONFLICTS AND FOR PROPER TRACKING AND RECORDS
 MANAGEMENT SINCE THE DETACHED GARAGE HAS A DIFFERENT
 ADDRESS. THERE IS ALREADY A SEPARATE PERMIT FOR THE
 DETACHED GARAGE. SEE PERMIT #22070105. SEC. 107.2.1.3
 CITY AMENDMENTS.
 NOTE: SINCE OTHER PLAN REVIEWERS MADE COMMENTS RELATING
 TO THE GARAGE, THEN PLEASE MAKE SURE TO ADDRESS GARAGE
 COMMENTS ON PERMIT 22070105 WHEN RESUBMITTING. THIS
 WILL AVOID MORE CONFLICTS/DELAYS.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION FOR THE
 ADDITIONAL WORK IS TOO LOW. VALUATION TO INCLUDE ALL
 LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND
 DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS.
 PROVIDE COMPLETE COST BREAKDOWN INCLUDING DESIGN
 PROFESSIONAL FEES.
  
 3- THIS HOUSE IS LOCATED IN FLOOD ZONE AE WITH A BASE
 FLOOD ELEVATION (BFE) OF 6 FEET BASED ON NAVD 88. IT
 LOOKS LIKE THE PROPOSED ADDITION AND ADDITIONAL WORK TO
 THE EXISTING MAIN HOUSE IS CONSIDERED A SUBSTANTIAL
 IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL
 HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR
 ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET.
 THEREFORE, THE MIN. REQUIRED FINISHED FLOOR ELEVATION
 IS 8 FEET. CITY ORDINANCE 4729-17. SEC. 18-33 TECHNICAL
 AMENDMENTS TO FLORIDA BUILDING CODE. SEC. 107.3.5.3
 CITY AMENDMENTS.
 PLANS NEED TO SHOW THE PROPOSED FINISHED FLOOR
 ELEVATION. NEED TO PROVIDE THE CONSTRUCTION DRAWINGS
 ELEVATION CERTIFICATE AND SURVEY SHOWING THE FINISH
 FLOOR ELEVATIONS FOR REVIEW.
  
 DURING THE PERMITTING OF THIS STRUCTURE THREE DIFFERENT
 FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED:
 A) CONSTRUCTION DRAWINGS.
 B) BUILDING UNDER CONSTRUCTION.
 C) FINISHED CONSTRUCTION.
  
 4- WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON THE
 ARCHITECTURAL EXTERIOR ELEVATIONS DON'T MATCH THE
 DESIGN PRESSURES CALCULATED BY THE STRUCTURAL ENGINEER.
 REVISE AS REQUIRED TO MATCH. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE FRAMING PLANS, SECTIONS AND
 SPECIFICATIONS FOR CONSTRUCTION OF NEW CHIMNEY ON REAR
 PORCH AND TERRACE ABOVE. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS, SPECIFY ALL EXTERIOR WALL COMPONENTS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: STRUCTURAL PLANS DON'T SHOW OPENING ON TERRACE
 CONCRETE SLAB.
  
 6- PROVIDE COMPLETE FRAMING PLANS, SECTIONS AND
 SPECIFICATIONS FOR CONSTRUCTION OF NEW WOOD CORNICE &
 BARREL TILE ROOF SHOWN ON THE WEST ELEVATION. SPECIFY
 ALL FRAMING MEMBERS AND CONNECTORS, ETC. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 7- CLARIFY/REVISE SIZE OF EMERGENCY OVERFLOW SCUPPERS
 SPECIFIED ON SHEET A-02.1 TO SHOW COMPLIANCE WITH SEC.
 R903.4.1 FBC-RESIDENTIAL.
 2" EMERGENCY OVERFLOW SCUPPER DOESN'T COMPLY.
  
 8- SPECIFY CARBON MONOXIDE ALARM WITHIN ALL SLEEPING
 ROOMS, INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC.
 R315.1 FBC-RESIDENTIAL.
  
 9- PROVIDE COMPLETE FRAMING PLANS FOR NEW 30"X96"
 SKYLIGHT AND FOR NEW SOLAR TUBES. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 10- GUARDRAILS: DESIGNER OF RECORD NEEDS TO PROVIDE THE
 DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 BALCONY AND TERRACE GUARDRAILS AS REQUIRED BY TABLE
 R301.5, SEC. AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT
 DESIGN DETAILS AND SPECIFICATIONS ARE MET.
  
 11- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)SOLATUBE FLORIDA PRODUCT APPROVAL SUBMITTED
 (FL11480-R13) DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD ON SHEET S-000.
 NEED TO PROVIDE PRODUCT APPROVAL THAT MEETS OR EXCEEDS
 CALCULATED DESIGN PRESSURES.
  
 B)SKYLIGHT (30"X96") NOA 20-1013.05 SUBMITTED DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECORD ON SHEET S-000. NEED TO PROVIDE PRODUCT APPROVAL
 THAT MEETS OR EXCEEDS CALCULATED DESIGN PRESSURES.
  
 C)SINGLE OUTSWING FRENCH DOOR FL34006 SUBMITTED DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECORD ON SHEET S-200. NEED TO PROVIDE PRODUCT APPROVAL
 THAT MEETS OR EXCEEDS CALCULATED DESIGN PRESSURES.
 NOTE: PLEASE UPLOAD THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND CORRESPONDING INSTALLATION DRAWINGS ON THE
 SAME PDF FILE. DO NOT UPLOAD IN SEPARATE FILES.
  
 D)WINDOW MULLIONS FLORIDA PRODUCT APPROVAL FL34545
 SUBMITTED. NOTE: NEED TO SPECIFY MULLION SIZE TO VERIFY
 PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 E)FIXED WINDOW FLORIDA PRODUCT APPROVAL FL34706
 SUBMITTED: SHEET 2 OF 7 OF INSTALLATION DRAWINGS SHOWS
 TYPE GLASS "B" TO BE USED. THIS TYPE OF GLASS IS NOT
 COVERED IN THE DESIGN LOADS CAPACITY TABLES FOR 4"-2" X
 6'-10" WINDOW "A1" SPECIFIED ON SHEET A-09. SEE SHEETS
 3 OF 7 AND 4 OF 7 OF INSTALLATION DRAWINGS AND REVISE
 AS REQUIRED OR PROVIDE PRODUCT APPROVAL THAT WORKS TO
 MEET THE CALCULATED DESIGN PRESSURES.
  
 F)FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS
 GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
 NOTE: THERE ARE DIFFERENT TYPES OF CONSTRUCTION IN THIS
 HOUSE. CONCRETE ROOF (NEW TERRACE) AND WOOD FRAMED
 (EXISTING ROOFS). ALSO, THERE ARE SOME FLAT ROOF TO BE
 COVERED WITH TILE AND THERE IS THE MAIN ROOF, NOT A
 DECK. PROVIDE PRODUCT APPROVAL COMPATIBLE EACH PROPOSED
 APPLICATION.
  
 G) ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
  
 H)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS
 LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED.
  
 I) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY
 MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC.
 R905.3.7.1 FBC-RESIDENTIAL.
  
 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-11-03 Cont ID  
Sent By mpeterso Date 2022-11-03 Time 08:35 Rev Time 0.00
Received By mpeterso Date 2022-11-03 Time 08:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By mpeterso Date 2022-07-25 Time 11:20 Rev Time 0.00
Received By mpeterso Date 2022-07-25 Time 11:20 Sent To  
Notes
2022-07-25 11:25:30ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE ALL ELECTRIC METER, ATS, DISCONNECT,
 AND PANEL EQUIPMENT LOCATIONS ON SITE AND FLOOR PLANS.
 107.2
 2) PLEASE DETAIL COMPLIANCE WITH NEC 225.30 FOR GARAGE
 BUILDING FEEDERS
 3) PLEASE PROVIDE DETAILS ON COMPLIANCE WITH NEC 250.32
 PROVISIONS FOR GROUNDING ELECTRODE SYSTEM AT GARAGE
 SEPARATE BUILDING
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2022-10-21 Cont ID  
Sent By ccole Date 2022-10-21 Time 09:40 Rev Time 0.00
Received By ccole Date 2022-10-21 Time 09:20 Sent To  
Notes
2022-10-21 09:41:41GAS PIPING AND APPLIANCE INSTALLATIONS FOR THE HOUSE
 SHALL BE UNDER A SEPARATE PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By ccole Date 2022-07-25 Time 15:59 Rev Time 0.00
Received By ccole Date 2022-07-25 Time 15:21 Sent To  
Notes
2022-07-25 16:01:23 
 1ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22070103
 7/25/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-01.1: THE REVISED PLAN SHOWS A NEW BBQ GAS
 GRILL IN THE COVERED LOGGIA. PLEASE CLARIFY IF THE GAS
 TO THE GRILL WILL BE SUPPLIED BY A POTABLE LP TANK OR A
 PERMANENT NATURAL GAS SUPPLY PIPE FROM A NEW OR
 EXISTING GAS SERVICE- SEC. 107.2.1 WPB.
  
 2) PLEASE NOTE GAS WAS NOT REVIEWED UNDER THE MASTER
 PERMIT 21100750 BECAUSE A REQUEST WAS MADE FOR IT TO BE
 UNDER SEPARATE PERMIT. TO DATE A GAS PERMIT APPLICATION
 AND PLANS HAS NOT BEEN SUBMITTED- PLEASE COMPLY. IN
 ACCORDANCE WITH SEC. 107.3.5.3 WPB, THE SEPARATE PERMIT
 SUBMITTAL SHALL INCLUDE:
 A) GAS RISER DRAWING.
 B) LOCATION OF ALL GAS-FIRED APPLIANCES.
 C) COMBUSTION AIR CALCULATIONS.
 D) VENTING PLANS.
 E) SUBMITTALS- MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION MANUALS FOR APPLIANCES.
 3) PLEASE NOTE A SEPARATE GAS PERMIT IS REQUIRED FOR
 INSTALLATION OF GAS PIPING AND APPLIANCES IN THE GUEST
 HOUSE- SEC. 105.1 & 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2023-04-05 Cont ID  
Sent By fmittner Date 2023-04-05 Time 15:33 Rev Time 0.00
Received By fmittner Date 2023-04-05 Time 15:33 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-08-05 Cont ID  
Sent By ahamilto Date 2022-08-05 Time 15:23 Rev Time 0.00
Received By fmittner Date 2022-08-05 Time 15:23 Sent To  
Notes
2022-08-05 15:24:10WINDOW GLASS TO BE CLEAR NO TINTING AND NO LOE-E
 VISIBLE FORM STREET, EXTERNAL DIMENSIONAL MUNTINS.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-05-04 Cont ID  
Sent By jgomez Date 2023-05-04 Time 19:07 Rev Time 0.00
Received By jgomez Date 2023-04-26 Time 09:46 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-04-24 Cont ID  
Sent By jgomez Date 2023-04-24 Time 18:59 Rev Time 0.00
Received By jgomez Date 2023-04-18 Time 15:59 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-06 Cont ID  
Sent By aoliver Date 2023-04-06 Time 07:14 Rev Time 0.00
Received By aoliver Date 2023-03-02 Time 16:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-18 Cont ID  
Sent By jgomez Date 2022-11-18 Time 15:12 Rev Time 0.00
Received By jgomez Date 2022-10-17 Time 08:25 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-05 Cont ID  
Sent By jgomez Date 2022-08-05 Time 17:41 Rev Time 0.00
Received By jgomez Date 2022-07-20 Time 15:30 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2023-05-04 Cont ID  
Sent By aoliver Date 2023-05-04 Time 14:35 Rev Time 0.00
Received By aoliver Date 2023-04-25 Time 07:41 Sent To  
Notes
2023-05-04 14:36:52NO IMPACT FEES DUE, SEE EMAIL UPLOADED AO
2023-04-25 07:41:474/25/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2023-03-08 Cont ID  
Sent By jgomez Date 2023-03-08 Time 16:43 Rev Time 0.00
Received By jgomez Date 2023-03-08 Time 16:42 Sent To  
Notes
2023-03-08 16:43:11IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By jgomez Date 2022-08-05 Time 15:10 Rev Time 0.00
Received By jgomez Date 2022-08-05 Time 15:09 Sent To  
Notes
2022-08-05 15:10:33IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-11-01 Cont ID  
Sent By medwards Date 2022-11-01 Time 09:31 Rev Time 0.00
Received By medwards Date 2022-11-01 Time 09:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-21 Cont ID  
Sent By medwards Date 2022-07-21 Time 08:40 Rev Time 0.00
Received By medwards Date 2022-07-21 Time 08:40 Sent To  
Notes
2022-07-21 08:40:241ST REVIEW FMC
 PERMIT: 22070103
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 MAIN HOUSE:
  
 1) PROVIDE ENERGY CALCULATIONS FOR THE ADDITION. FBC
 101.5.1.1.2
  
 2) PROVIDE MECHANICAL EQUIPMENT SIZING FOR HVAC-2, IF
 THIS IS A LIKE FOR LIKE CHANGE OUT PROVIDE THE REQUIRED
 LIKE FOR LIKE CHANGE OUT FORM. FRC M1401.3
  
  
 DETACHED GARAGE:
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS CHANGE OF
 USE. FBC 101.5.1.1.2
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS CHANGE OF USE INCLUDING THE GARAGE MINI SPLIT.
 FRC M1401.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status N Date 2022-11-18 Cont ID  
Sent By jgomez Date 2022-11-18 Time 15:08 Rev Time 0.00
Received By jgomez Date 2022-11-18 Time 15:08 Sent To  
Notes
2022-11-08 15:16:30HISTORIC CBAA CASE #1455 WAS APPROVED.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By jgomez Date 2022-08-05 Time 15:05 Rev Time 0.00
Received By jgomez Date 2022-08-05 Time 15:05 Sent To  
Notes
2022-08-05 15:06:011- THIS HOUSE IS LOCATED IN FLOOD ZONE AE WITH A BASE
 FLOOD ELEVATION (BFE) OF 6 FEET BASED ON NAVD 88. IT
 LOOKS LIKE THE PROPOSED ADDITION AND ADDITIONAL WORK TO
 THE EXISTING MAIN HOUSE IS CONSIDERED A SUBSTANTIAL
 IMPROVEMENT (SEE SUBSTANTIAL IMPROVEMENT DEFINITION
 BELOW). THE ADDITION AND THE EXISTING HOUSE SHALL HAVE
 THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR
 ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET.
 THEREFORE, THE MIN. REQUIRED FINISHED FLOOR ELEVATION
 IS 8 FEET. CITY ORDINANCE 4729-17. SEC. 18-33 TECHNICAL
 AMENDMENTS TO FLORIDA BUILDING CODE. SEC. 107.3.5.3
 CITY AMENDMENTS.
 PLANS NEED TO SHOW THE PROPOSED FINISHED FLOOR
 ELEVATION. NEED TO PROVIDE THE CONSTRUCTION DRAWINGS
 ELEVATION CERTIFICATE AND SURVEY SHOWING THE FINISH
 FLOOR ELEVATIONS FOR REVIEW.
  
 DURING THE PERMITTING OF THIS STRUCTURE THREE DIFFERENT
 FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED:
 A) CONSTRUCTION DRAWINGS.
 B) BUILDING UNDER CONSTRUCTION.
 C) FINISHED CONSTRUCTION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-10-21 Cont ID  
Sent By ccole Date 2022-10-21 Time 09:40 Rev Time 0.00
Received By ccole Date 2022-10-21 Time 09:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By ccole Date 2022-07-25 Time 15:19 Rev Time 0.00
Received By ccole Date 2022-07-25 Time 14:36 Sent To  
Notes
2022-07-25 15:21:291ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22070103
 7/25/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P-01.1 & P-01.2: A SEPARATE PRIMARY PERMIT AND
 SUB-PERMITS UNDER THE PRIMARY ARE REQUIRED FOR THE
 GARAGE CONVERSION TO GUEST HOUSE- SEC. 105.1 & 107.2.1
 WPB.
  
 2) P-01.1 & P-01.2: TWO DWELLINGS ON THE SAME LOT WILL
 REQUIRE WATER USERS TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. A REDUCED PRESSURE
 ZONE BACKFLOW DEVICE WILL BE REQUIRED FOR THE WATER
 METER PER SECS. C, D & E- CITY OF WEST PALM CROSS
 UTILITIES CROSS-CONNECTION CONTROL MANUAL.
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 3) P-01.1 & P-01.2: PLEASE SHOW THE SOURCE OF THE HOT
 WATER FOR THE NEW FIXTURES IN THE GUEST HOUSE- SEC.
 P2801.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status N Date 2023-04-24 Cont ID  
Sent By jgomez Date 2023-04-24 Time 18:36 Rev Time 0.00
Received By jgomez Date 2023-04-24 Time 18:36 Sent To  
Notes
2023-04-24 18:37:33ALL ROOFING PRODUCT APPROVALS REVIEWED UNDER ROOF
 PERMIT 22070747

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2023-03-08 Cont ID  
Sent By jgomez Date 2023-03-08 Time 16:40 Rev Time 0.00
Received By jgomez Date 2023-03-08 Time 16:40 Sent To  
Notes
2023-03-08 16:41:00NOTE:
 THERE ARE ROOFING SUBPERMITS FOR THIS PROJECT. TO AVOID
 CONFLICTS/DELAYS AND TO EXPEDITE THE BUILDING REVIEW
 PROCESS IT WILL BE BETTER TO SUBMIT ALL THE ROOFING
 PRODUCT APPROVALS ALONG WITH THE ROOFING PERMITS.
  
  
 ROOFING REVIEW:
  
 NOTE; ITEM #1 WILL BE REVIEWED ONCE DESIGN PRESSURES
 ARE REVISED. SEE ITEM #4 ABOVE. PLEASE MAKE SURE BELOW
 COMMENTS FOR EACH PRODUCT APPROVAL IS ADDRESSED TO
 AVOID CONFLICTS/DELAYS.
  
 1- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A) FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY
 IS GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
 NOTE: THERE ARE DIFFERENT TYPES OF CONSTRUCTION IN THIS
 HOUSE. CONCRETE ROOF (NEW TERRACE) AND WOOD FRAMED
 (EXISTING ROOFS). ALSO, THERE ARE SOME FLAT ROOF TO BE
 COVERED WITH TILE AND THERE IS THE MAIN ROOF, NOT A
 DECK. PROVIDE PRODUCT APPROVAL COMPATIBLE EACH PROPOSED
 APPLICATION.
  
 B) ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
  
 C)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS
 LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED.
  
 D) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY
 MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC.
 R905.3.7.1 FBC-RESIDENTIAL.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 TO BE COORDINATED WITH ITEM #1 ABOVE. PLEASE MAKE SURE
 ALL PRODUCT APPROVALS ARE REVIEWED/APPROVED TO AVOID
 CONFLICTS/DELAYS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-11-18 Cont ID  
Sent By jgomez Date 2022-11-18 Time 15:09 Rev Time 0.00
Received By jgomez Date 2022-11-18 Time 15:08 Sent To  
Notes
2022-11-18 15:09:18ROOFING REVIEW:
  
 NOTE; ITEM #1 WILL BE REVIEWED ONCE DESIGN PRESSURES
 ARE REVISED. SEE ITEM #4 ABOVE. PLEASE MAKE SURE BELOW
 COMMENTS FOR EACH PRODUCT APPROVAL IS ADDRESSED TO
 AVOID CONFLICTS/DELAYS.
  
 1- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A) FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY
 IS GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
 NOTE: THERE ARE DIFFERENT TYPES OF CONSTRUCTION IN THIS
 HOUSE. CONCRETE ROOF (NEW TERRACE) AND WOOD FRAMED
 (EXISTING ROOFS). ALSO, THERE ARE SOME FLAT ROOF TO BE
 COVERED WITH TILE AND THERE IS THE MAIN ROOF, NOT A
 DECK. PROVIDE PRODUCT APPROVAL COMPATIBLE EACH PROPOSED
 APPLICATION.
  
 B) ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
  
 C)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS
 LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED.
  
 D) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY
 MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC.
 R905.3.7.1 FBC-RESIDENTIAL.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 TO BE COORDINATED WITH ITEM #1 ABOVE. PLEASE MAKE SURE
 ALL PRODUCT APPROVALS ARE REVIEWED/APPROVED TO AVOID
 CONFLICTS/DELAYS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By jgomez Date 2022-08-05 Time 15:07 Rev Time 0.00
Received By jgomez Date 2022-08-05 Time 15:07 Sent To  
Notes
2022-08-05 15:09:05ROOFING REVIEW:
  
 1- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A) FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY
 IS GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
 NOTE: THERE ARE DIFFERENT TYPES OF CONSTRUCTION IN THIS
 HOUSE. CONCRETE ROOF (NEW TERRACE) AND WOOD FRAMED
 (EXISTING ROOFS). ALSO, THERE ARE SOME FLAT ROOF TO BE
 COVERED WITH TILE AND THERE IS THE MAIN ROOF, NOT A
 DECK. PROVIDE PRODUCT APPROVAL COMPATIBLE EACH PROPOSED
 APPLICATION.
  
 B) ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
  
 C)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS
 LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED.
  
 D) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY
 MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC.
 R905.3.7.1 FBC-RESIDENTIAL.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-05-04 Cont ID  
Sent By jgomez Date 2023-05-04 Time 19:06 Rev Time 0.00
Received By jgomez Date 2023-05-04 Time 18:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-04-24 Cont ID  
Sent By jgomez Date 2023-04-24 Time 18:58 Rev Time 0.00
Received By jgomez Date 2023-04-24 Time 18:37 Sent To  
Notes
2023-04-24 18:59:07SIGNATURE REVIEW:
  
 1- REVISED DRAWING A-02.1 DOESN'T HAVE THE ARCHITECT'S
 DIGITAL SIGNATURE.
 NEED TO SUBMIT DRAWING ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-03-08 Cont ID  
Sent By jgomez Date 2023-03-08 Time 16:47 Rev Time 0.00
Received By jgomez Date 2023-03-08 Time 16:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-18 Cont ID  
Sent By jgomez Date 2022-11-18 Time 09:41 Rev Time 0.00
Received By jgomez Date 2022-11-18 Time 09:33 Sent To  
Notes
2022-11-01 09:34:33MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By jgomez Date 2022-08-05 Time 15:26 Rev Time 0.00
Received By jgomez Date 2022-08-05 Time 15:19 Sent To  
Notes
2022-08-05 15:27:381- ALL STRUCTURAL DRAWINGS SUBMITTED HAVE A COPY OF A
 DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE NOT ALLOWED
 TO BE PRINTED. ALL DOCUMENTS PREPARED BY A LICENSED
 ENGINEER NEED TO HAVE THE ORIGINAL VERIFIABLE DIGITAL
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.004 FAC AND CHAPTER 471 F.S.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
2022-07-21 08:42:05MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 3 Status P Date 2023-03-28 Cont ID  
Sent By vbroglia Date 2023-03-28 Time 14:18 Rev Time 0.00
Received By vbroglia Date 2023-03-28 Time 14:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-11-15 Cont ID  
Sent By fmittner Date 2022-11-15 Time 08:39 Rev Time 0.00
Received By fmittner Date 2022-11-15 Time 08:39 Sent To  
Notes
2022-11-15 08:39:29STILL NO SEPARATE LANDSCAPE PERMIT FILED

Review Stop Z ZONING
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By ahamilto Date 2022-08-05 Time 15:24 Rev Time 0.00
Received By fmittner Date 2022-08-05 Time 15:24 Sent To  
Notes
2022-08-05 15:34:15NEED TO FILE SEPERATE LANDSCAPE PERMIT