Plan Review Details - Permit 22070066
Plan Review Stops For Permit 22070066
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-20 Cont ID  
Sent By shill Date 2022-08-20 Time 06:57 Rev Time 0.00
Received By shill Date 2022-08-20 Time 06:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 17:32 Rev Time 0.00
Received By shill Date 2022-07-25 Time 17:32 Sent To  
Notes
2022-07-25 17:32:45PRODUCT APPROVALS ARE DEFERRED
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-07-21 Cont ID  
Sent By jleahy Date 2022-07-21 Time 11:00 Rev Time 0.00
Received By jleahy Date 2022-07-21 Time 10:56 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2022-09-01 Cont ID  
Sent By ccole Date 2022-09-01 Time 16:30 Rev Time 0.00
Received By ccole Date 2022-09-01 Time 16:12 Sent To  
Notes
2022-09-01 16:31:37GAS PIPING FOR THE NEW WATER HEATER SHALL BE UNDER A
 SEPARATE PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-08-23 Cont ID  
Sent By ccole Date 2022-08-23 Time 12:09 Rev Time 0.00
Received By ccole Date 2022-08-23 Time 07:44 Sent To  
Notes
2022-08-23 12:10:241ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22070066
 8/23/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. A GAS REVIEW WAS SET UP
 BECAUSE THE REVISED PLAN SHOWS A NEW GAS FIRED TANKLESS
 WATER HEATER ON THE EXTERIOR OF THE HOUSE.
  
 1) SHEET P-1: A GAS RISER DRAWING IS REQUIRED PER SEC.
 107.3.5.3 WPB, AND CHAPTER 24 FBC RES. PLEASE PROVIDE
 THE FOLLOWING INFORMATION ON THE DRAWING:
 A) LOCATION OF METER AND TYPE OF GAS.
 B) DELIVERY PRESSURE AT THE METER.
 C) WATER HEATER BTU LOAD, OTHER GAS APPLIANCE LOADS,
 AND THE TOTAL LOAD.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS & SHUTOFF VALVES.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) P-1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW GAS
 WATER HEATER INDICATING THE MAKE AND MODEL AND BTU
 CAPACITY- SEC. G2448.1 FBC RES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-08-17 Cont ID  
Sent By amhamilt Date 2022-08-17 Time 10:34 Rev Time 0.00
Received By amhamilt Date 2022-08-17 Time 10:34 Sent To  
Notes
2022-08-17 10:36:36PERMIT HAS PASSED PROVISIONALLY:
  
 BUILDING NEEDS TO BE RE-DESIGNATED AT NEW LOCATION
 PRIOR TO ISSUANCE OF CO (AFTER MOVE).
 ALL MUNTINS ON NEW WINDOWS MUST BE EXTERNALLY APPLIED
 WITH A DIMENSIONAL PROFILE (OGEE OR PYRAMID)
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2022-07-12 Cont ID  
Sent By amhamilt Date 2022-07-12 Time 15:37 Rev Time 0.00
Received By amhamilt Date 2022-07-12 Time 15:37 Sent To  
Notes
2022-07-12 15:46:36THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 WINDOW SCHEDULE INDICATES GREY TINT ON GLASS, ONLY
 CLEAR GLASS PERMITTED ON HISTORIC BUILDINGS. PLEASE
 REVISE. PLEASE ALSO INDICATE ALL MUNTINS ON NEW WINDOWS
 WILL BE EXTERNALLY APPLIED WITH A DIMENSIONAL PROFILE
 (OGEE OR PYRAMID)
  
 BUILDING NEEDS TO BE RE-DESIGNATED AT NEW LOCATION
 PRIOR TO ISSUANCE OF CO (AFTER MOVE)
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2022-09-01 Time   Rev Time 0.00
Received By lmarchan Date 2022-08-30 Time 15:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-08-23 Time   Rev Time 0.00
Received By aoliver Date 2022-08-09 Time 06:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 17:34 Rev Time 0.00
Received By shill Date 2022-07-06 Time 06:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-09-19 Cont ID  
Sent By lmarchan Date 2022-09-19 Time 14:50 Rev Time 0.00
Received By lmarchan Date 2022-09-01 Time 16:43 Sent To  
Notes
2022-09-19 14:50:37RECEIPT MU-2022-042560 - $2430.79 PAID
2022-09-01 16:43:339/1/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 17:33 Rev Time 0.00
Received By shill Date 2022-07-25 Time 17:33 Sent To  
Notes
2022-07-25 17:34:02PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE EMAIL THE RECEIPT
 TO [email protected].
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-08-23 Cont ID  
Sent By medwards Date 2022-08-23 Time 10:46 Rev Time 0.00
Received By medwards Date 2022-08-23 Time 10:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-08 Cont ID  
Sent By medwards Date 2022-07-08 Time 09:12 Rev Time 0.00
Received By medwards Date 2022-07-08 Time 09:12 Sent To  
Notes
2022-07-08 09:51:591) PROVIDE A SCOPE OF WORK FOR THE MECHANICAL SYSTEMS.
 ARE THE UNITS NEW? IF SO, PROVIDE THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS.FRC M1401.3
  
 2) REVISE THE DRAWINGS TO SHOW THE RETURN AIR DUCTS AND
 THE SIZES. IT APPEARS THAT THE DESIGN IS FOR ABOVE
 CEILING PLENUMS IN SOME LOCATIONS ON BOTH FLOORS.FBC
 107.2.1
  
 3) REVISE THE DRAWING AND REMOVE THE RETURN AIR GRILLE
 FROM THE MASTER BATH AS RETURN AIR CANNOT BE FROM A
 BATHROOM. FBC 107.2.1
  
 4) REVISE THE PLAN TO SHOW THE DRYER EXHAUST DUCT AND
 THE TERMINATION LOCATION. FRC M1502
  
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-09-01 Cont ID  
Sent By ccole Date 2022-09-01 Time 16:30 Rev Time 0.00
Received By ccole Date 2022-09-01 Time 16:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-08-23 Cont ID  
Sent By ccole Date 2022-08-23 Time 11:53 Rev Time 0.00
Received By ccole Date 2022-08-23 Time 07:17 Sent To  
Notes
2022-08-23 11:54:251ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22070066
 8/23/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE REVIEW IS BASED ON
 UPDATED PLUMBING PLANS.
  
 1) SHEET P-1: THE REVISED PLAN SHOWS EXISTING 1/2-INCH
 WATER LINES WHICH WILL HAVE TO BE INCREASED IN SIZE IN
 SPECIFIC AREAS IN ORDER TO ACCOMMODATE THE ADDITIONAL
 NEW PLUMBING FIXTURES AND INCREASE IN WSFU DEMAND- SEE
 TABLES P2903.1 & P2903.6 FBC RES. PLEASE PROVIDE A
 WATER RISER DRAWING- SEC. 107.3.5.3 WPB.
  
 2) SHEET P-1: A NEW GAS-FIRED TANKLESS WATER HEATER HAS
 BEEN ADDED ON THE EXTERIOR OF THE HOUSE. A SEPARATE GAS
 REVIEW HAS BEEN SET UP- PLEASE REFER TO THOSE COMMENTS.
 CONCERNING THE PLUMBING, THE WATER HEATER SHALL BE
 SIZED LARGE ENOUGH TO SUPPLY HOT WATER TO THE INCREASED
 NUMBER OF PLUMBING FIXTURES. PLEASE REVIEW THE
 MANUFACTURER?S GUIDELINES FOR HOT WATER PIPE SIZING
 RECOMMENDATIONS AND SHOW THE PIPE SIZES IN THE RISER
 DRAWING- SEC. 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-07 Cont ID  
Sent By ccole Date 2022-07-07 Time 10:13 Rev Time 0.00
Received By ccole Date 2022-07-07 Time 09:24 Sent To  
Notes
2022-07-07 10:15:391ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22070066
 7/7/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1: PROVIDE A SANITARY DRAIN AND VENT
 ISOMETRIC FOR THE 1ST FLOOR POWDER ROOM- SEC. 107.3.5.3
 WPB.
  
 2) P-1: SHOW THE LOCATION OF THE NEW WATER HEATER AND
 PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN- SECS.
 P2801.1 & P2801.4 FBC RES.
  
 3) SHOW THE LOCATIONS OF THE REQUIRED CLEANOUT AT THE
 JUNCTION OF THE NEW SANITARY BUILDING DRAIN AND
 EXISTING SEWER LINE- SEC. P3005.2.3 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status N Date 2022-07-07 Cont ID  
Sent By ccole Date 2022-07-07 Time 11:12 Rev Time 0.00
Received By ccole Date 2022-07-07 Time 11:12 Sent To  
Notes
2022-07-07 11:13:48A SEPARATE PERMIT IS REQUIRED FOR THE IRRIGATION
 SYSTEM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-01 Cont ID  
Sent By ccole Date 2022-09-01 Time 16:30 Rev Time 0.00
Received By ccole Date 2022-09-01 Time 16:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-20 Cont ID  
Sent By shill Date 2022-08-20 Time 06:58 Rev Time 0.00
Received By shill Date 2022-08-20 Time 06:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 17:32 Rev Time 0.00
Received By shill Date 2022-07-25 Time 17:32 Sent To  
Notes
2022-07-21 11:05:27ELECTRICAL PAGE SIGNATURE APPROVED JLEAHY
2022-07-08 09:52:52MECHANICAL DIGITAL SIGNATURE APPROVED ME

Review Stop Z ZONING
Rev No 1 Status P Date 2022-07-12 Cont ID  
Sent By asangele Date 2022-07-12 Time 16:39 Rev Time 0.00
Received By amhamilt Date 2022-07-12 Time 16:39 Sent To  
Notes
2022-07-12 16:41:20PROPOSED FUTURE OUTBUILDING NOT INCLUDED UNDER SCOPE OF
 THIS PERMIT, SQUARE FOOTAGE OF THIS PROPOSED BUILDING
 WOULD EXCEED PERMITTED SQUARE FOOTAGE UNDER SF14-C2
 ZONING STANDARDS.
  
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  